Operating instructions

10 Engineering WirelessHART Fieldgate SWG70
62 Endress+Hauser
Procedure for FieldCare In addition to the previous method, in FieldCare the instrument list can also be generated by
importing a network tree created in off-line mode.
1 Create a FieldCare project as described in Chapters 7.5.1 and 7.5.2
Put the HART Communication IP CommDTM and Fieldgate SWG70 CommDTM
on line
2 Instead of scanning for devices use the Add Device context menu to add first an adapter, then
the device or devices attached to it.
For WirelessHART devices without an adapter, just add the device
3 Continue until the network tree is complete
Edit the long tags so that they correspond to those stored in your devices
4 Click on Offline Parameterize=> Engineering => Instrument List to display the empty
instrument list
You may have to enable the Engineering menu first
5 Press Import Project Tree to import the network tree
6 Press Export CSV to store the instrument list on your computer
7Close the Offline Parameterize dialogue and open the Online Parameterize dialog
Select Engineering => Instrument List to display the empty instrument list
8 Press Import CSV and import the file you have just created
9 Press Apply to download the instrument list to the Fieldgate
10 When the devices join the network at a later time, they will be assigned to their allotted
positions in the Operating Modes list
11 When all devices have joined the network, return to the Instrument List and press Refresh
to import the latest list
12 Press Export CSV to store a copy of the list on your computer
The file can be re-imported into the Instrument List by pressing Import and navigating
to the folder containing the file.