Operating instructions
WirelessHART Fieldgate SWG70 9Diagnostics
Endress+Hauser 59
HART parameters
Parameter Parameter Meaning
Extended Device Malfunction Manager fault Non-recoverable hardware fault: Fieldgate manager
Non-Volatile Memory Defect Non-recoverable hardware fault: Non-voltatile memory
Volatile Memory Defect Non-recoverable hardware fault: Voltatile memory
Ethernet communication fault Non-recoverable hardware fault: Ethernet controller
Electronic defect Non-recoverable hardware fault: Other case
RS-485 communication fault Non-recoverable hardware fault: RS-485 controller
Gateway Operation in Progress Block transfer Fieldgate transferring block
Delayed answer Fieldgate awaiting answer from device (buffer)
Self test Fieldgate is in self test mode, see Chapter 8.6.5
File update Fieldgate writing to non-volatile memory file
Start-up phase Fieldgate is starting up and building the network
Extended List changes Instrument List Changed Instrument list has changed since last refresh
Active Device List Changed Device list has changed since last refresh
Cumulative Device Status Primary Variable Out of Limits PV of a device in the network is out of limits
Non-Primary Variable Out of
Limits
SV, TV, QV of a device in the network is out of limits
Loop Current Saturated Loop current of a a device in the network above 20 mA
Loop Current Fixed Loop current of a a device in the network is fixed to
4 mA (multidrop mode)
More Status Available Device in the network has more status available flagged
Cold Start Device in the network has cold start flagged
Configuration Changed Configuration of a device in the network has changed
Device Malfunction Device in the network has malfunctioned
Cumulative Extended Device
Status
Maintenance required The status "Maintenance required" has been set for a
device in the network
Device Variable Alert The status "Device Variable Alert" has been set for a
device in the network
Critical Power Failure The status "Critical Power Failure" has been set for a
device in the network
Device Operation in Progress "Configuration Changed bit
reset" procedure
Fieldgate has reset the "Configuration Changes" bit of
one of the devices
"Sub-Device update" procedure Fieldgate is carrying out the identification of a device
connected to an adapter
"Device update" procedure Fieldgate is carrying out the identification of an adapter