Operating instructions

8 Fieldgate Configuration WirelessHART Fieldgate SWG70
48 Endress+Hauser
8.3.3 HART
The parameters contained in this leaf pertain to the set up of the HART communication to the host
on the interfaces offered by Fieldgate SWG70.
1 Click on the Wired Communication => Protocols => HART to display the associated
parameters:
The significance of the parameters can be taken from the table overleaf, whereby mandatory
parameters are highlighted by bold type
2 If the default port number is changed, and FieldCare is in use, communication will be lost
Reconfigure the HART IP CommDTM communication parameters, see Chapter 7.5.2
Step 4, before making connection again
HART parameters
Parameter Meaning Example Default
Bus Address
Selection
Specifies whether hardware (DIP switch 0-3) or software bus
address settings are to be used
DIP Switch: 0 - 15
•Software: 0 - 63
Software Software
Bus Address Sets the HART address of the wireless fieldgate when Bus Address
Selection is set to Software
When DIP-Switch is selected, displays the setting
63 1
Baud Rate Selection Specifies whether hardware (DIP switch 4-5) or software baudrate
settings are to be used
DIP Switch: 9600 Bit/s - 57600 Bit/s
Software: 1200 Bit/s - 115200 Bit/s
Software Software
Baud Rate Sets the baudrate of the wireless fieldgate when Baud Rate
Selection is set to Software
When DIP-Switch is selected, displays the setting
19200 19200
Port Number Sets the Fieldgate SWG70 Ethernet port number for HART via
UDP/TCP transmission
If the port number is changed, the default port remains open
HART UDP allows access for two primary masters and two
secondary masters
HART TCP allows access for one primary masters and one
secondary master
5094