Operating instructions
WirelessHART Fieldgate SWG70 7 Commissioning
Endress+Hauser 39
7.5.5 Scan for devices connected to adapters
It is also possible to scan for the devices connected to the adapters. Depending on the size of the
network and the connected field devices, however, it is possible that time out problems occur. In
this case, FieldCare issues a warning and the user can choose to cut the connection, wait for
connection or retry the connection.
1 Open a fast pipe to the corresponding adapter, see Chapter 8.2.3
2 Right-click on the Adapter node and select Create Network...
– You can also click on the Create Network icon to do this
– The adapter is put on-line and the two arrows turn green
3 The adapter DTM now scans the wired interface and automatically adds all HART devices
found to the network:
– Depending upon FieldCare configuration and number of devices, this may occur
automatically or after confirmation with OK in the Scanning Result dialog.
– Depending upon FieldCare configuration, if only one device is found, the corresponding
Device DTM will open, see below.
4 Repeat the process for all adapters in the network
5 To open the Device DTM of an unconnected transmitter right-click on the Transmitter node
and select Connect, then right-click again and select Online Parameterization