Operating instructions

7 Commissioning WirelessHART Fieldgate SWG70
34 Endress+Hauser
7.4.2 Update the FieldCare DTM catalog
Before they can be used, the new DTMs must be integrated in the FieldCare DTM Catalog.
NOTE!
• For FieldCare Standard and Professional, administrator rights are required to update the
DTM catalog
• For new FieldCare installations, follow the instructions in the FieldCare Getting Started booklet
1 Start FieldCare and log on as administrator (not necessary for FieldCare Device Setup)
2In the Start-Up Screen dialog, press Continue and in the FieldCare dialog press Open
An empty Project workspace appears
3 Right-click on the DTM Catalog menu and select Update...
The Update DTM Catalog dialog appears
–Press Update to start the search for new DTMs (make take several minutes)
4 When the search is complete, the new DTM will be shown in the left-hand pane:
Select the Wireless Fieldgate and HART IP DTMs and press Move >>
–Press OK to close the dialog and register the changes
You are now ready to start configuration, see Chapter 8
NOTE!
If a WirelessHART Fieldgate DTM or HART IP Communication DTM was already in the catalog,
it is automatically updated and appears as "Changed" in the right-hand panel