Operating instructions
WirelessHART Fieldgate SWG70 7 Commissioning
Endress+Hauser 31
5 Change the IP address and the Subnet Mask of the host computer to match the IP address of
the Fieldgate.
– IP Address 192.168.1.XXX and network mask (Subnet Mask) 255.255.255.0.
6 Click on the OK button to complete the procedure, close the other dialogs with OK and
Close.
7.2.2 Check the connection
The simplest way to check the connection is to call up the Fieldgate SWG70 Web Server:
1 In your Internet browser enter the address of Fieldgate SWG70: 192.168.1.1 and press Enter:
2 Accept the site certificate in the dialog which now appears.
3 Now the Login of the Web page appears. To open the Fieldgate SWG70 Web pages
–Enter User name (default: admin) and Password (default: admin) and press OK
4 If you are not able to connect to the Fieldgate:
– Ping the Fieldgate using the Command prompt
– Check that any proxy server is switched off or not used for this address range
– Check ports 80, 443, 502 and 5094 in all firewalls are open
– Check that you have the correct Ethernet cable (crossover for direct PC connection)
– Check that the Ethernet cable has been correctly connected, Chapter 5.3
– Check your IP address setting again