Operating instructions

WirelessHART Fieldgate SWG70 5 Electrical Installation
Endress+Hauser 23
5.4 Connecting to RS-485
Fieldgate SWG70 is equipped with a fully galvanic isolated RS-485 interface. A second RS-485
terminal block allows several gateways to be connected through a daisy chain.
A terminating resistor is required at each end of the RS-485 cable. If the RS-485 is not routed to
other devices (no daisy-chain connection), activate the terminating resistor integrated in the
fieldgate.
NOTE!
Keep in mind the location of the Modbus PLC or DCS. The maximum length of the cable running
from the gateway to the PLC/DCS is 1200m (at reduced communication speed).
• Use shielded twisted pair (STP) cables only.
If the cable shield is grounded, the grounding should only be connected to one end of the cable,
in order to avoid equipotential bonding currents.
Tension relief and bending radii: Ensure sufficient relief of tension on the cables during
installation and note the minimum bending radii of the cables.
Fig. 5-4: RS-485 interface
Connecting to RS-485 1 Check that the power is switched off
2 If applicable, unscrew the four screws of the housing cover (see Fig. 4-5 in Chapter 4.2) and
remove the housing cover.
3 Route the RS-485 cable through the first cable gland from left
The permissible cable diameter lies between 6 mm and 10 mm.
4 Connect the RS-485 cable to the left terminal block labelled "RS485" (see Figure 5-4) as
follows:
5 For a daisy-chain connection, route the second RS-485 cable through the second cable gland
from left and connect it to the right terminal block labelled "RS485", see table above.
6 To activate the RS-485 termination, set DIP switch number 7 to "ON" (see Chapter 6.1.3).
7 Screw the housing cover to the housing again.
8 Tighten the cable gland with appropriate torque, see Chapter 5.5.
1 First RS-485 connection 2 Second RS-485 connection for daisy chaining
KL1 KL2 KL3 KL4
+24V +24V0V 0V
LINE1 LINE2
A
B
SHD
RS485
T1
T2
RX–
RX+
TX–
TX+
ON
OFF
SHD
A
B
SHD
RS485
ETHERNET
KL5 KL6
A B SHD
RS485
A B SHD
RS485
1
2
Wire RS-485 cable Fieldgate terminal Remarks
RxD/TxD– (RS-485 A) A RS-485 differential
signal
RxD/TxD+ (RS-485 B) B
Shield SHD Cable shielding