Operating Instructions WirelessHART Fieldgate SWG70 Intelligent WirelessHART gateway with Ethernet and RS-485 interfaces BA00064S/04/en/13.13 Version 1.01.
WirelessHART Fieldgate SWG70 Table of Contents Table of Contents Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Registered Trademarks . . . . . . . . . . . . . . . . . . . . . . 3 1 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.1 1.2 1.3 1.4 1.5 1.6 1.7 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installation, commissioning and operation . . . . . . . . Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents WirelessHART Fieldgate SWG70 10 Engineering . . . . . . . . . . . . . . . . . . . . 60 A Appendix: Modbus Interface . . . . . . . . 90 10.1 A.1 10.3 Instrument List . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1.2 Creation and editing of an Instrument List Modbus Mapping . . . . . . . . . . . . . . . . . . . . . . . . . 10.2.1 Modbus Settings . . . . . . . . . . . . . . . . . . . . 10.2.2 Input Status .
WirelessHART Fieldgate SWG70 Revision History Revision History Package version Manual Changes Remarks 1.00.xx BA064S/04/en/06.10 – Original manual 1.01.xx BA00064S/04/en/13.13 New Functions Navigation changed, see Chapter 7.6 Channel Blacklisting possible, Chapter 8.2.2 Topology with signal strength; Chapter 9.2.4/10.3 Network tables revised, e.g. Chapter 8.2.
1 Safety WirelessHART Fieldgate SWG70 1 Safety 1.1 Designated use Fieldgate SWG70 serves as a gateway device for WirelessHART networks. It enables WirelessHART devices to communicate with each other and manages security and connectivity. The Fieldgate converts wireless device data to a format that is compatible with host systems. 1.2 Installation, commissioning and operation Fieldgate SWG70 has been designed to operate safely in accordance with current technical safety and EU directives.
WirelessHART Fieldgate SWG70 1 Safety 1.4 Conformance All declarations of conformity are to be found on the accompanying CD ROM in the folder Fieldgate SWG70=>Documentation=>Certificates. CE Mark In attaching the CE Mark, Endress+Hauser confirms that Fieldgate SWG70 conforms to all relevant EU directives. Declarations of conformity are available for both Ex and Non-Ex versions.
1 Safety WirelessHART Fieldgate SWG70 1.7 Conventions and icons In order to highlight safety relevant or alternative operating procedures in the manual, the following conventions have been used, each indicated by a corresponding icon in the margin. Safety conventions Icon Meaning DANGER! This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury. WARNING! This symbol alerts you to a dangerous situation.
WirelessHART Fieldgate SWG70 2 Identification 2 Identification 2.1 Unpacking 2.1.
2 Identification WirelessHART Fieldgate SWG70 2.2 Device designation The device designation together with other information is to be found on the nameplate affixed to the front of the Fieldgate, see Fig. 2-1. 3 2 1 CMIIT ID 2011DJ5310 4 Fig.
WirelessHART Fieldgate SWG70 3 Function and System Design 3 3.1 Function and System Design WirelessHART protocol The HART protocol has until now used the wired 4–20mA loop with a superimposed digital signal as physical layer. Although full digital communication is available in multidrop mode, the majority of transmitters are connected to analog I/O cards and digital communication is used only for parameterization, diagnosis and maintenance purposes.
3 Function and System Design WirelessHART Fieldgate SWG70 3.2 WirelessHART network Fieldgate SWG70 is the master device in the WirelessHART network. Acting as network manager, it recognizes other devices wanting to join the network. It makes contact with each in turn and initiates the procedures required for them to join. The network organizes itself without any intervention on the part of the user.
WirelessHART Fieldgate SWG70 3 Function and System Design 3.3 Connection to host applications Fieldgate SWG70 also makes wireless communication accessible to HART-capable host systems via its Ethernet or serial interfaces through the following functions. 3.3.1 Instrument List WirelessHART devices in the network are made available to host systems via an instrument list. This list contains one or more I/O cards. Every I/O card has one or more channels.
3 Function and System Design WirelessHART Fieldgate SWG70 3.3.2 Cache The WirelessHART gateway stores information received over the WirelessHART network and makes it available to the host for further processing. This ensures that information is available immediately for the host system without having to send a request to the device and wait for the response. The following commands and answers to requests are cached in the gateway.
WirelessHART Fieldgate SWG70 4 Mechanical Installation 4 Mechanical Installation NOTE! • It is recommended that Fieldgate SWG70, adapters and devices be setup on the test bench and the network be tested before the components are installed in the field. 4.1 Mounting considerations 4.1.1 Positioning the Fieldgate Install the gateway first, before installing other WirelessHART devices. This way you can check for proper operation of new devices as they are installed.
4 Mechanical Installation WirelessHART Fieldgate SWG70 4.1.3 Antenna characteristics Fig. 4.1 shows the antenna gain in the vertical and horizontal planes. Fig.
WirelessHART Fieldgate SWG70 4 Mechanical Installation 4.1.4 Antenna range Fig. 4.2 is a schematic representation of Fig. 4.1 and shows the wave propagation with the signal attenuation. The antenna is an omni-directional dipole antenna. If you point the antenna upwards, the signal radiates horizontally at an angle of approx. 39 degrees above and below the horizontal (donut shaped). The most power is in the horizontal plane, decreasing to 50% at an angle of 39°.
4 Mechanical Installation WirelessHART Fieldgate SWG70 4.1.5 Examples for good and poor positioning The positioning is good when the network participants are within the antenna range: PWR COM FLT height distance Fig. 4-3: Example of good positioning The positioning is poor when neighbours are not in the antenna range or within the weaker signal zone of the antenna: / PWR COM FLT height distance Fig.
WirelessHART Fieldgate SWG70 4 Mechanical Installation 4.2 Mounting the antenna WARNING! • When Fieldgate SWG70 is installed in Ex-Zone 2, the connection/disconnection of cables is permitted only in the absence of any potentially explosive atmosphere or when the Fieldgate is not connected to the power supply. NOTE! • Use only the antenna supplied or a remote antenna that conforms to the requirements in Chapter 4.2.2.
4 Mechanical Installation WirelessHART Fieldgate SWG70 4.2.3 Connecting a remote antenna WARNING! • Outdoor installations can be subject to lightning strikes. Install a surge arrestor, to protect the installation against transients or damage caused by lightning strikes. NOTE! • Tension relief and bending radii: Ensure sufficient relief of tension on the cables during installation and note the minimum bending radii of the cables.
WirelessHART Fieldgate SWG70 4 Mechanical Installation 4.3 Mounting the Fieldgate In addition to fulfilling the conditions for good wireless communication, the mounting location should be well accessible for mounting and electrical installation. Make sure that there is enough space to open the housing cover and to access the terminals, switches, and cable glands. Choose a mounting location that meets the climatic limits specified and radio requirements in the technical data.
5 Electrical Installation WirelessHART Fieldgate SWG70 5 Electrical Installation 5.1 Connections and interfaces The connections and interfaces are only accessible with an open enclosure. In the case of the DIP switches, the user has the choice of using the switch settings, or overriding the settings by software, see Chapter 8.
WirelessHART Fieldgate SWG70 5 Electrical Installation 5.2 Connecting to power supply and grounding There are two 24 VDC power supply terminal blocks located inside Fieldgate SWG70, allowing for redundant power supply. Open the housing cover to access the terminal blocks. NOTE! • Tension relief and bending radii: Ensure sufficient relief of tension on the cables during installation and note the minimum bending radii of the cables.
5 Electrical Installation WirelessHART Fieldgate SWG70 5.3 Connecting to Ethernet Fieldgate SWG70 is equipped with a fully galvanic isolated 10 Base-T/100 Base-TX Ethernet interface. You may connect it to an existing Ethernet Hub, Switch or Router. NOTE! • Keep in mind that an access point of the Ethernet network has to be available. The maximum length of the cable running from the gateway to the access point is 100 m, depending on cable type and communication speed.
WirelessHART Fieldgate SWG70 5 Electrical Installation 5.4 Connecting to RS-485 Fieldgate SWG70 is equipped with a fully galvanic isolated RS-485 interface. A second RS-485 terminal block allows several gateways to be connected through a daisy chain. A terminating resistor is required at each end of the RS-485 cable. If the RS-485 is not routed to other devices (no daisy-chain connection), activate the terminating resistor integrated in the fieldgate.
5 Electrical Installation WirelessHART Fieldgate SWG70 5.5 Cable glands and housing cover The degree of protection IP 65 (NEMA Type 4) cannot be achieved if the cables and cable glands are not fitted correctly.
WirelessHART Fieldgate SWG70 6 Operation 6 Operation 6.1 Operating and display elements Inside the fieldgate housing there are LED indicators, DIP switches and reset buttons. The controls and indicators are accessible with open enclosure.
6 Operation WirelessHART Fieldgate SWG70 6.1.1 LEDs Five leds indicate the status of Fieldgate SWG70: 2 1 3 4 5 A B SHD RS485 A B SHD RS485 SHD T1 T2 RX– RX+ TX– TX+ ETHERNET +24V 0V LINE1 +24V 0V LINE2 ON OFF Fig.
WirelessHART Fieldgate SWG70 6 Operation 6.1.2 Buttons Fieldgate has two pushbuttons. Warning! • When Fieldgate SWG70 is installed in Ex-Zone 2 and the power is switched on, the operation of the pushbuttons is permitted only in the absence of any potentially explosive atmosphere. 2 1 A B SHD RS485 A B SHD RS485 SHD T1 T2 RX– RX+ TX– TX+ ETHERNET +24V 0V LINE1 +24V 0V LINE2 ON OFF 1 2 3 4 5 6 7 8 Fig.
6 Operation WirelessHART Fieldgate SWG70 6.1.3 DIP switches Warning! • When Fieldgate SWG70 is installed in Ex-Zone 2 and connected to the power supply, the operation of DIP switches is permitted only in the absence of any potentially explosive atmosphere. NOTE! • The same functions can be initiated from the Fieldgate SWG70 Web inteface and DTM, see Chapter 8.4, Wired Communication Fieldgate SWG70 has one 8-gang DIP switch.
WirelessHART Fieldgate SWG70 7 Commissioning 7 Commissioning NOTE! • It is recommended that Fieldgate SWG70, adapters and devices be setup on the test bench and the network be tested before the components are installed in the field. 7.1 Preliminaries 7.1.1 Software package The CD ROM delivered with Fieldgate SWG70 contains the following components which must be installed on your computer prior to configuration as described in Chapter 7.4.
7 Commissioning WirelessHART Fieldgate SWG70 7.2 Ethernet connection The Ethernet connection of Fieldgate SWG70 allows communication with a computer via the integral Web Server or via FieldCare.
WirelessHART Fieldgate SWG70 7 Commissioning 5 Change the IP address and the Subnet Mask of the host computer to match the IP address of the Fieldgate. – IP Address 192.168.1.XXX and network mask (Subnet Mask) 255.255.255.0. 6 Click on the OK button to complete the procedure, close the other dialogs with OK and Close. 7.2.2 Check the connection The simplest way to check the connection is to call up the Fieldgate SWG70 Web Server: 1 In your Internet browser enter the address of Fieldgate SWG70: 192.
7 Commissioning WirelessHART Fieldgate SWG70 7.3 RS-485 connection Once the gateway has been connected to the RS-485 bus (see Chapter 5.4), you may connect the RS485 bus to your PC. This can be done by using a RS485–RS232 converter or a RS485–USB converter. Procedure 1 Connect the RS-485–RS-232 converter or the RS-485–USB converter to your PC. 2 In the case of the RS-485-USB converter install any driver that is delivered with the device.
WirelessHART Fieldgate SWG70 7 Commissioning 7.4 Installing FieldCare If you do not already have FieldCare running on your computer, you can install FieldCare Device Setup from the corresponding DVD: will normally start automatically, otherwise via setup.exe. 7.4.1 Installing the Fieldgate DTM and HART IP CommDTM 1 Insert the Fieldgate CD ROM into the CD ROM drive: the setup program starts: – If this is not the case, double click on Setup.
7 Commissioning WirelessHART Fieldgate SWG70 7.4.2 Update the FieldCare DTM catalog Before they can be used, the new DTMs must be integrated in the FieldCare DTM Catalog.
WirelessHART Fieldgate SWG70 7 Commissioning 7.5 Create a FieldCare Project Creating a FieldCare project will allow you to configure Fieldgate SWG70 and any HART device (field device or adapter) in the wireless network via its DTM. The configuration of a field device can be taken from the manufacturer’s operating manual, the configuration of the adapter is described in Operating Instructions BA061S/04/en, SWA70 Wireless Adapter. 7.5.
7 Commissioning WirelessHART Fieldgate SWG70 7.5.2 Add the Fieldgate SWG70 1 Right-click on the HART IP Communication node and select Add Device: 2 The Add New Device dialog opens: – Select WirelessHART Fieldgate SWG70 and press OK 3 The dialog closes and the Fieldgate SWG70 DTM is added below the HART IP node 4 If the factory IP address (192.168.1.
WirelessHART Fieldgate SWG70 7 Commissioning 7.5.
7 Commissioning WirelessHART Fieldgate SWG70 7.5.4 Scan for wireless devices in the network After Fieldgate SWG70 has been configured, see Chapter 8.2 onwards, you may want to scan for other devices in the network 1 Right-click on the Fieldgate SWG70 node and select Create Network...
WirelessHART Fieldgate SWG70 7 Commissioning 7.5.5 Scan for devices connected to adapters It is also possible to scan for the devices connected to the adapters. Depending on the size of the network and the connected field devices, however, it is possible that time out problems occur. In this case, FieldCare issues a warning and the user can choose to cut the connection, wait for connection or retry the connection. 1 Open a fast pipe to the corresponding adapter, see Chapter 8.2.
7 Commissioning WirelessHART Fieldgate SWG70 7.6 User interface The Web Server and DTM of the Fieldgate SWG70 are structured in the same manner, so that the configuration is identical. Before starting, the Web Server must be open, see Chapter 7.2.2 or the Online parameterization dialog of the DTM must be open, see Chapter 7.5.3. The user interface is structured as follows: Parameters (DTM dialog: Online Parameterization) Chapter 8 Identification Chapter 8.1 Wireless Communication Chapter 8.
WirelessHART Fieldgate SWG70 8 Fieldgate Configuration 8 Fieldgate Configuration Parameter contains all parameters related to the set-up of Fieldgate SWG70. In FieldCare the corresponding function is called by right-clicking on the Fieldgate SWG70 node and selecting Online Parameterization. 8.1 Identification The parameters to be found in this leaf pertain to the identification of Fieldgate SWG70. The default parameters of Fieldgate SWG70 will appear in the appropriate input fields.
8 Fieldgate Configuration WirelessHART Fieldgate SWG70 8.2 Wireless Communication 8.2.1 Basic Setup This leaf contains the parameters required to set up the WirelessHART communication offered by the Fieldgate SWG70.
WirelessHART Fieldgate SWG70 8 Fieldgate Configuration NOTE! • The Join Key parameters, can only be entered when DIP Switch 8 (inside the gateway housing) is set to ON (factory default), see Chapter 6.1.3.
8 Fieldgate Configuration WirelessHART Fieldgate SWG70 8.2.2 Channel Blacklist Advanced Setup Where several wireless networks are in operation on a site and all are critical for plant operation, it is advisable to set up them up such a way that mutual interference is avoided. This is done by restricting the channels on which a particular network can broadcast.
WirelessHART Fieldgate SWG70 8 Fieldgate Configuration 8.2.3 Operating Modes Operating Modes contains a table listing all devices in the WirelessHART network together with their operation modes. Whenever a wireless device joins the network, it is automatically inserted into the list, provided it is not already listed. Wired HART devices connected to a WirelessHART adapter are also inserted. The list retains all the devices Fieldgate has detected over the lifetime of the network, i.e.
8 Fieldgate Configuration WirelessHART Fieldgate SWG70 8.3 Wired Communication 8.3.1 Serial The parameters contained in this leaf pertain to the set up of the serial interface offered by Fieldgate SWG70.
WirelessHART Fieldgate SWG70 8 Fieldgate Configuration 8.3.2 Ethernet The parameters contained in this leaf pertain to the set up of the communication to the host via Ethernet interface offered by Fieldgate SWG70.
8 Fieldgate Configuration WirelessHART Fieldgate SWG70 8.3.3 HART The parameters contained in this leaf pertain to the set up of the HART communication to the host on the interfaces offered by Fieldgate SWG70.
WirelessHART Fieldgate SWG70 8 Fieldgate Configuration 8.3.4 Modbus The parameters contained in this leaf pertain to the set up of the Modbus communication to the host on the interfaces offered by Fieldgate SWG70.
8 Fieldgate Configuration WirelessHART Fieldgate SWG70 8.3.5 AMS If Fieldgate SWG70 is to be integrated into Emerson’s Asset Management System (AMS), this must be done via an Ethernet port. The port number is set in this leaf.
WirelessHART Fieldgate SWG70 9 Diagnostics 9 Diagnostics Diagnosis contains all health and related information on Fieldgate SWG70. In FieldCare the corresponding function is called by right-clicking on the Fieldgate SWG70 node and selecting Diagnostics. 9.1 Identification The Identification leaf contains information on the hardware and software of Fieldgate SWG70. The significance of the parameters is described in the table below.
9 Diagnostics WirelessHART Fieldgate SWG70 9.2 Wireless Communication The Wireless Communication leaf contains information on the operation of Fieldgate SWG70 within the wireless network. 9.2.1 Overview Overview provides information about the I/O interfaces of the wireless network as well as network statistics. 1 Click on the Diagnostics => Wireless Communication => Overview leaf to display the associated parameters: – The significance of the parameters can be taken from the table below.
WirelessHART Fieldgate SWG70 9 Diagnostics 9.2.2 Details NOTE! • Diagnostic information is available only after the applicable statistics period has been completed (15 minutes). During this time, some information is set to 0 or replaced by wildcard characters. Details shows all devices in the WirelessHART network together with their diagnostic information. Whenever a wireless device joins the network, it is automatically inserted into the list if it is not already there.
9 Diagnostics WirelessHART Fieldgate SWG70 9.2.3 Burst Lists Burst mode is a special mode of a HART slave device which allows it to periodically send the response to a selected HART command without the being polled by the master. For a WirelessHART slave device, it is the main operating mode and can be used, for instance, to send the process values from an adapter or connected HART device to Fieldgate SWG70 at regular intervals. The burst lists, contain information on the devices operating in this mode.
WirelessHART Fieldgate SWG70 9 Diagnostics 9.2.4 Topology View (Diagnostics) Topology view is a graphical overview of all wireless devices within your network, including their connection status and connection paths. It is set up in Engineering => Topology View, see Chapter 10.3. 1 Click on the Diagnostics => Wireless Communication => Topology View leaf to open the view: – The lines between the devices represent the connection paths.
9 Diagnostics Topology parameters WirelessHART Fieldgate SWG70 Parameter Meaning Traffic Dotted line: Path is unused at the moment Thin line: Path used by one third of connections Medium lines: Path used by two thirds of connections Thick line: Path used by all connections Connection Quality Signal Red: Signal stability 0 - 10% of maximum possible Red: Signal stability 10 - 20% of maximum possible Orange: Signal stability 20 - 30% of maximum possible Gold: Signal stability 30 - 40% of maximum possible
WirelessHART Fieldgate SWG70 9 Diagnostics 9.3 Wired Communication The Wired Communication leaf contains information on the communication interface used to connect to a supervisory system. It contains two sub menus: Overview and HART. 9.3.1 Overview Overview contains the performance parameters of the wired communication interface 1 Click on the Diagnostics => Wired Communication=> Overview leaf to open the overview: – The significance of the parameters is described in the table below.
9 Diagnostics WirelessHART Fieldgate SWG70 9.3.2 HART The HART page shows the possible statuses that may exist for HART devices in the network. A tick box beside each parameter indicates whether the described condition is currently valid. 1 Click on the Diagnostics => Wired Communication => HART leaf to open the list: – The significance of the parameters is described in the table which follows.
WirelessHART Fieldgate SWG70 HART parameters 9 Diagnostics Parameter Parameter Extended Device Malfunction Manager fault Non-recoverable hardware fault: Fieldgate manager Non-Volatile Memory Defect Non-recoverable hardware fault: Non-voltatile memory Volatile Memory Defect Non-recoverable hardware fault: Voltatile memory Ethernet communication fault Non-recoverable hardware fault: Ethernet controller Electronic defect Non-recoverable hardware fault: Other case RS-485 communication fault Gate
10 Engineering WirelessHART Fieldgate SWG70 10 Engineering 10.1 Instrument List 10.1.1 General This leaf contains a list of instruments in the network. It is also possible to add individual devices that are still to be connected.
WirelessHART Fieldgate SWG70 10 Engineering 10.1.2 Creation and editing of an Instrument List Normally the Instrument List will be generated by refreshing after the network is up and running. It is possible, however, to create a list from scratch before any WirelessHART devices join the network. This allows the order in which the devices are displayed in the both the Instrument List and Operating Modes - and hence in the Modbus mapping - to be predetermined. The individual entries can also be edited.
10 Engineering Procedure for FieldCare WirelessHART Fieldgate SWG70 In addition to the previous method, in FieldCare the instrument list can also be generated by importing a network tree created in off-line mode. 1 Create a FieldCare project as described in Chapters 7.5.1 and 7.5.2 – Put the HART Communication IP CommDTM and Fieldgate SWG70 CommDTM on line 2 Instead of scanning for devices use the Add Device context menu to add first an adapter, then the device or devices attached to it.
WirelessHART Fieldgate SWG70 10 Engineering 10.2 Modbus Mapping 10.2.1 Modbus Settings Modbus Settings determines how the Modbus information is to be transmitted by Fieldgate SWG70 and where the information is to be found. It also allows the selection of automatic or manual mapping. The set-up of the Modbus communication parameters (address, baudrate etc.) is described in Chapter 8.3.4.
10 Engineering WirelessHART Fieldgate SWG70 10.2.2 Input Status Input Status allows the Modbus mapping of a device with single or multiple binary output. As Fieldgate SWG70 supports extended registers, values are normally assigned to the registers with the reference addresses 100001 to 165536. The reference addresses are obtained by adding the register number to 100,000.
WirelessHART Fieldgate SWG70 Input Status parameters 10 Engineering Parameter Meaning Example Default Table Register 1 Defines the start register for the Digital I/O device values – For Input Status the first value is normally 1 – The initial value can be overwritten only after a device has been selected in the Long Tag drop-down menu – Subsequent start registers are automatically generated 1 End Register End register for Digital I/O device values (generated automatically) 8 65536 Long Tag Cli
10 Engineering Semi-automatic generation of Input Status mapping table WirelessHART Fieldgate SWG70 1 Click on the Generate tab to open the Generate dialogue: 2 Enter an offset value in the Start register field.
WirelessHART Fieldgate SWG70 Manual entry of an Input Status mapping table 10 Engineering 1 Click on the Table tab to open the Table dialogue: 2 Select a device from the drop-down menu that appears when the Long Tag field is clicked 3 Enter an offset value in the Register field. – For a typical application the start value is normally 1 – Offset values > 1: only values (n +1) are allowed, where n is divisible by 8 For the first device entered, an extra field will be added for the registers 0 to e.g.
10 Engineering WirelessHART Fieldgate SWG70 10.2.3 Input Register Input Register allows the Modbus mapping of Fieldgate SWG70 and the connected HART devices. As Fieldgate SWG70 supports extended registers, values are normally assigned the Input Registers with the reference addresses 300001 to 365536 but for some Modbus systems the mapping must be made to the Holding Registers with the reference addresses 400001 to 465536, see Read Modbus Registers Mode in Chapter 10.2.1.
WirelessHART Fieldgate SWG70 Input Register parameters 10 Engineering Parameter Meaning Example Default Register Defines the start register for the HART device values – For Input Register the first value is normally 30000; some systems work only with Holding Registers starting at 40000 – The intial value can be overwritten only after a device has been selected in the Long Tag drop-down menu – Subsequent start registers are automatically generated 13 1 End Register End register for HART device va
10 Engineering Semi-automatic generation of Input Register mapping table WirelessHART Fieldgate SWG70 1 Click on the Generate tab to open the Generate dialogue: 2 Enter an offset value in the Start Register field. – For a typical application, e.g.
WirelessHART Fieldgate SWG70 Manual entry of an Input Register mapping table 10 Engineering 1 Click on the Table tab to open the Table dialogue: 2 Select a device from the drop-down menu that appears when the Long Tag field is clicked 3 Enter an offset value in the Register field. – Offset value >1: For the first device entered, an extra field will be added for the registers 0 to e.g.
10 Engineering WirelessHART Fieldgate SWG70 10.3 Topology View (Engineering) Topology view is a graphical overview of all wireless devices within your network, including their connection status and connection paths. The view set up in the dialog described here is shown in Diagnosis => Wireless Communication=> Topology View, see Chapter 9.2.4.
WirelessHART Fieldgate SWG70 Topology View set-up 10 Engineering The WirelessHART devices are automatically added to the topology view. If required, click Refresh to reload the device information. Note that reloading the device information takes some time. 1 Click Select Map to select a background image for the topology view. – For example, a satellite photo, a floor plan or a diagram – The image must be in .jpg format 2 In the dialogue that now appears, click Browse to navigate to the background image.
10 Engineering WirelessHART Fieldgate SWG70 6 Arrange the WirelessHART devices in the topology view by dragging and dropping the icons to a selected position. – For more accurate positioning use the slider to zoom in or out of the topology view.
WirelessHART Fieldgate SWG70 11 Additional Functions 11 Additional Functions Additional Functions contains a number of functions which maybe required during the Fieldgate life-cycle but not for everyday operation. The functions offered depend upon the parametrization tool. In FieldCare the corresponding function is called by right-clicking on the Fieldgate SWG70 node and selecting Additional Functions. 11.1 Reset Reset allows the Fieldgate, the instrument list and the network to be reset, see table.
11 Additional Functions WirelessHART Fieldgate SWG70 11.3 About About gives information about Fieldgate SWG70. If called from FieldCare, it also gives information about the DTM. 1 Click on the Additional Functions> About leaf to open the dialogue: 11.
WirelessHART Fieldgate SWG70 11 Additional Functions 11.5 Change Password (Web Server) Change Password allows the password to the Web Server to be changed. 1 Click on the Additional Functions => Change password leaf to open the dialogue 2 Enter the new password in the two fields provided 3 Press the Change Password >> button to download the new password 4 The action can be cancelled immediately after entering the new password if the Discard Operation >> button is pressed 11.
11 Additional Functions WirelessHART Fieldgate SWG70 11.7 Set Device Addresses (DTM) Set Device Addresses displays all adapters, together with their wired connections, that can be seen in the network. The device address is the device long tag stored in the device. Set Device Addresses allows the user to match the addressing of a physical device, i.e. the Long Tag in WirelessHART networks, to the one stored in the DTM. The function is not relevant to FieldCare but might be required for other FDT frames.
WirelessHART Fieldgate SWG70 11 Additional Functions 11.8 Upload Certificate (Web Server) 11.8.1 Self-signed security certificate A digital certificate is an electronic document that binds a public key with an identity, for example, an organization or a user. The binding between a public key and the identity is done by a signature. This signature can be self-signed or authenticated by a certification authority. Fieldgate SWG70 is delivered with a self-signed certificate for the HTTPS connection.
12 Measurement WirelessHART Fieldgate SWG70 12 Measurement The Measurement table provides a comprehensive overview of all cached parameters and values of all sub-devices.
WirelessHART Fieldgate SWG70 13 Maintenance and Repair 13 Maintenance and Repair 13.1 Maintenance 13.1.1 General The national requirements apply to maintenance, servicing, and inspection of associated apparatus. No maintenance is necessary if the devices are operated properly, observing the mounting instructions and ambient conditions. The devices may not be repaired, changed or manipulated. If there is a defect, the product must always be replaced with an original part. 13.1.2 Return to Endress+Hauser.
14 Trouble-Shooting WirelessHART Fieldgate SWG70 14 Trouble-Shooting 14.1 Network optimization Once the WirelessHART network is running, there are some simple measures that will help to enhance network performance and reliability. These measures are described in the following. NOTE! • After installation and configuration of the network, give it a couple of hours to stabilize itself, before taking the following steps. 14.1.
WirelessHART Fieldgate SWG70 14 Trouble-Shooting 14.1.3 Expand the Network In an industrial environment, there are several potential obstacles for radio waves, for example buildings, walls, pipes, or even moving obstacles like trucks. Those obstacles can reflect, bend, diffuse or block radio waves. The effects of reflection, bending and diffusion create new waves which may interfere with the original ones and with each other. They can amplify or nullify each other. This effect is called fading.
14 Trouble-Shooting WirelessHART Fieldgate SWG70 14.2 Diagnosis 14.2.1 Faults indicated by Fieldgate LEDS LED indication Problem/Remedy 1 Red LED is lit • Hardware fault which makes normal operation of the gateway impossible – Send Fieldgate back for repair 2 Red LED flashes • Under certain conditions the LED flashes while the gateway application tries to eliminate the fault. – If this indication persists, even after a reboot, send the Fieldgate back for repair 14.2.
WirelessHART Fieldgate SWG70 14 Trouble-Shooting 14.2.
15 Technical Data WirelessHART Fieldgate SWG70 15 Technical Data 15.1 Input Wireless interface WirelessHART communication interface Physical layer IEEE 802.15.4; 2006 Transmission rate Nominal 250 kBits/s Operating frequency 2.
WirelessHART Fieldgate SWG70 15 Technical Data 15.3 Power Supply Supply voltage 20 VDC to 30 VDC Power <5 W Connection facilities • Two 2-port terminal blocks, 2nd port for redundant power supply • Screw terminals: 0.2 mm2 to 4 mm2 for solid wire, 0.2 mm2 to 2.5 mm2 for stranded wires 15.
15 Technical Data WirelessHART Fieldgate SWG70 15.5 Mechanical Construction Overall dimensions W x H x D: 257 mm x 85 mm x 285 mm with cable glands and antenna 257 mm x 85 mm x 115 mm without cable glands and antenna 257 (10.12) mm (inch) 52 (2.05) 115 (4.53) 115 (4.53) 57 (2.24) 150 (5.91) 150 (5.91) 85 (3.35) 228 (8.98) Centers 240 - 250 (9.45 - 9.84) 52 (2.05) 228 (8.98) 85 (3.35) 257 (10.12) 20 (0.79) 20 (0.79) 10 (0.39) Fig.
WirelessHART Fieldgate SWG70 15 Technical Data 15.
A Appendix: Modbus Interface WirelessHART Fieldgate SWG70 A Appendix: Modbus Interface A.1 Introduction A.1.1 Modbus protocol Modbus is a quasi-industrial standard developed some years ago by Gould-Modicon and provides a messaging service that may run on a variety of physical layers. For Fieldgate SWG70 there are two possibilities for connecting Modbus: • Modbus RTU (also known as Serial) can be connected point-to-point to the RS-485C interface as described in Chapter 5.4.
WirelessHART Fieldgate SWG70 A Appendix: Modbus Interface A.1.2 Modbus in Fieldgate Fieldgate SWG70 is equipped with both a Modbus serial and Ethernet interface. As a result, it can be operated in one of the following roles: • Modbus Serial Slave • Modbus TCP Slave A serial or TCP slave can be accessed by one Modbus master only. Establishing communication As a TCP slave, Fieldgate SWG70 will normally communicate with the master via Port 502.
1 0 Register WirelessHART Fieldgate SWG70 Reference address A Appendix: Modbus Interface 65536 100001 RW Coils (not supported by Fieldgate) 65535 0 RO Discrete Inputs 166536 65535 300001 0 RO Input registers 365536 65535 400001 0 RW Holding registers (for Fieldgate RO image of Input registers) 465536 65535 Fig. A-1: Mapping of Modbus registers Fieldgate SWG70 Refresh time Fieldgate SWG70 refreshes Modbus discrete inputs and input registers once every macrocycle.
WirelessHART Fieldgate SWG70 A Appendix: Modbus Interface A.1.3 Data types Fieldgate SWG70 supports three different data types, which are interpreted and stored as described below: • Floating point, Unsigned Integer16, Unsigned Integer8 Floating point Value range (±) 1.175 * 10-38 to 3.403 * 1038 Byte Structure 31 Sign Unsigned16 0 23 Exponent (8 bit) Fraction (23 bit) Storage Float Modbus Register 1 15 0 Swapped Float 31 16 Modbus Register 2 31 16 15 0 Value range 0 to 65.
A Appendix: Modbus Interface WirelessHART Fieldgate SWG70 A.2 Rules for mapping A.2.1 Automatic mapping of analog devices (HART CMD3) Each HART device is mapped into 12 consecutive Modbus input registers. The order of HART device mapping starting from register 13 is the same as the order of the sub-device identity summary (returned by HART CMD84). For example, the HART device with the sub-device index=1 is mapped starting at register 13.
WirelessHART Fieldgate SWG70 A Appendix: Modbus Interface A.2.2 Digital input/output devices There is no automatic mapping of the Input Status registers: the user must generate the mapping table either semi-automatically or manually.
A Appendix: Modbus Interface WirelessHART Fieldgate SWG70 A.3 Mapping formats A.3.1 Dynamic process variables For each HART device, the 5 possible Command 3 floating-point dynamic variables are sequentially mapped (units code values are not mapped). If a device does not support a specific dynamic value, a "NaN" (Not a Number) floating-point value is returned (namely, 0x7F, 0xA0, 0x00, 0x00).
WirelessHART Fieldgate SWG70 A Appendix: Modbus Interface A.3.3 HART CMD48 Read Additional Status Information Command 48 returns device status information not included in the response code or device status byte of Command 3. All field devices support at least bytes 0 ... 8. If a field device supports more than one analog channel, then bytes 9 ... 13 will be supported as well.
A Appendix: Modbus Interface WirelessHART Fieldgate SWG70 A.3.4 Read Discrete Inputs HART Specification 285 describes the requirements for discrete and hybrid field devices. A discrete device will return discrete values only. A hybrid device may return both analog and discrete values. Discrete inputs are read by means of HART Command 64,386, which returns a block of discrete variables (values and status). The length of the data string depends upon the device polled.
WirelessHART Fieldgate SWG70 B Appendix: CSV File Formats B Appendix: CSV File Formats B.1 Structure of CSV Files When creating or editing CSV files for import into Fieldgate SWG70, the following rules apply: • Use a semicolon ";" as separator for the values in the CSV file. If a value already contains a semicolon you must put the value into quote signs. If the value already contains quote signs, put the entire value into quote signs and replace the original quote signs with double quote signs.
B Appendix: CSV File Formats Information Codes WirelessHART Fieldgate SWG70 Information Code Value Description 0 (HART Status) 0 Device Status 1 Extended Device Status 2 Device Status & Extended Device Status 1 (CMD 48 Status) 2 (Device Variable) 0 ... 12 CMD 48 status word to be mapped 0 maps CMD 48 bytes 0&1 1 maps CMD 48 bytes 2&3 ... and so on 12 maps CMD 48 byte 24 only 0 ...
WirelessHART Fieldgate SWG70 B Appendix: CSV File Formats B.5 Details The files you can export under Diagnostics > Wireless Communication > Details contain the following columns. There are no mandatory columns as there is no import function. Nevertheless, you can export the data in CSV format for documentation.
C Appendix: HART OPC Connection C WirelessHART Fieldgate SWG70 Appendix: HART OPC Connection C.1 HART OPC server The HART OPC server is software which runs under Microsoft Windows and provides a standard OPC communications interface with HART-capable instrumentation. The HART OPC server acts as a transport mechanism for communicating with HART devices.
WirelessHART Fieldgate SWG70 C Appendix: HART OPC Connection 4 The Network Properties dialog opens – – – – Enter a network Name Enter the Number of Retries Enter the Retry Delay Base in ms Press OK to register the changes and add the network to your project NOTE! • For "RS-485" you must enter a Name, Address (COM port), Baudrate and Retries.
C Appendix: HART OPC Connection WirelessHART Fieldgate SWG70 7 The IO System Properties dialog opens – Press OK 8 The I/O system is added to the project 9 Now right-click on Fieldgate SWG70 node and select Learn – The HART Server now scans the entire WirelessHART network – Depending on how many devices are in the network, this may take some time 104 Endress+Hauser
WirelessHART Fieldgate SWG70 C Appendix: HART OPC Connection 10 After scanning is complete, the network is added to Fieldgate SWG70 node: – The result should be similar to the screenshot above – For more details on the structure, see Chapter 3.3.1.
C Appendix: HART OPC Connection C.3 WirelessHART Fieldgate SWG70 Viewing and editing device properties The HART server allows you to view and edit device properties at different levels of the network C.3.
WirelessHART Fieldgate SWG70 C Appendix: HART OPC Connection C.3.2 Adapter properties 1 Click on the first CH001 node in the first branch then right click on the Adapter Long Tag that appears in the right workspace and select Properties 2 The Adapter Properties dialog opens The significance of the parameters can be taken from the table below IO System Properties Parameter Meaning Adapter Identification Tag Name A string identifying Fieldgate SWG70 - up to 32 characters.
C Appendix: HART OPC Connection WirelessHART Fieldgate SWG70 C.3.
WirelessHART Fieldgate SWG70 C Appendix: HART OPC Connection 4 Press the Device tab to open the Device dialog This contains information on the tagging and range of the device – Gray fields are parameters loaded from the device memory – White fields can be edited, to store changes, press Send 5 The significance of the parameters can be taken from the table below Device parameters Parameter Meaning Device Info Message User message, transmitted with information from the device – up to 32 characters Tag
C Appendix: HART OPC Connection WirelessHART Fieldgate SWG70 6 Press the HART tab to open the HART dialog This contains information on the device hardware and software – Gray fields are parameters loaded from the device memory – White fields can be edited, to store changes, press Send 7 The significance of the parameters can be taken from the table below HART parameters Parameter Meaning HART Info Manufacturer ID Indicates manufacturer ID of the device in plain text and as a hexadecimal number Devic
WirelessHART Fieldgate SWG70 C Appendix: HART OPC Connection 8 Press the Status tab to open the Status dialog This indicates the current status of the device – Gray fields are parameters loaded from the device memory – Press Read to refresh the display 9 The significance of the parameters can be taken from the table below Status parameters Parameter Meaning Device Status Bit 0 to Bit 7 Standard HART status information – A red dot indicates that the status is currently active Command 48 Info ...
C Appendix: HART OPC Connection WirelessHART Fieldgate SWG70 10 Press the Command tab to open the Command dialog This allows a HART command to be sent to the device and the results to be displayed – Gray fields are parameters received from the device – White fields can be edited, send the command, press Send 11 The significance of the parameters can be taken from the table below Command parameters Parameter Meaning Request Command # (decimal) Enter the number of the command to be sent – The device mu
WirelessHART Fieldgate SWG70 C Appendix: HART OPC Connection C.3.4 Device data 1 Select a channel entry (CHx) beneath the gateway in the project window, Chapter B.3.1, Step 10 – In the right part of the application window, you can see the device connected to the selected channel. 2 Right-click on the device – Select Data from the context menu.
C Appendix: HART OPC Connection C.4 WirelessHART Fieldgate SWG70 OPC client The HART OPC Server can be used by any OPC Client Application to bring data into, e.g. a SCADA application. The example below uses the Data Spy client to view the data. This is supplied with ControlCare Application Designer and is part of ControlCare P View. 1 Open the client directly via Start => Program => ... or from the SCADA application 2 Expand the tree under HartServer.HartOpc.
WirelessHART Fieldgate SWG70 C Appendix: HART OPC Connection 5 Select the tag then press OK, the instrument data are displayed For more information on using OPC data , see the P View operating manual.
D Appendix: ANATEL Approval WirelessHART Fieldgate SWG70 D 116 Appendix: ANATEL Approval Endress+Hauser
WirelessHART Fieldgate SWG70 D Appendix: ANATEL Approval For your notes Endress+Hauser 117
D Appendix: ANATEL Approval WirelessHART Fieldgate SWG70 For your notes 118 Endress+Hauser
WirelessHART Fieldgate SWG70 D Appendix: ANATEL Approval For your notes Endress+Hauser 119
Index WirelessHART Fieldgate SWG70 Index A L Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 Additional Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 AMS Ethernet port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 M Burst Lists . . . . . . . . . . . . . .
www.endress.