5.14 Bristol Babcock BSA Driver
RTU Driver : Bristol Babcock Protocol V1.0
KeyCode : BSA
This driver controls the Toshiba Tosvert-130 Transistor inverter. While there are various
models in the Tosvert-130 product line, the driver was designed for the G3 series. Other
models may be supported, but have not been tested.
Configuration of the driver is as follows.
Driver Configuration (with default values):
KeyCode : BSA
This driver will interface to a Teleflow RTU (Model 3530) via the BSAP protocol.
Driver Configuration (with default values):
RTU
TYpe BSA Set the RTU driver to the Bristol Babcock BSA.
DEbug <off | on>
COMM
POrt < COM2> The RTU driver must use COM2 (RS232).
BAud <9600>
DAtabits <8>
PArity <None>
STopbits <1>
BSA Driver I/O Configuration
The user needs knowledge of the Bristol Babcock configuration to configure I/O points in the
PAC.
Only two BSAP commands have been implemented.
Remote Database Access - Read by Data Array Number.
Remote Database Access - Write by Data Array Number.
GDN ADd <pid> <index> <address> <f1> <f2> <f3> <f4> <type>
IO Point Configuration
Address : RTU Address.
F1 Array index.
F2 : Column
F3 Row
F4 Bit index (Discrete only)
Type Float / Discrete