5.13 Grant DataLogger 1000 series Squirrel Meter Driver
RTU Driver : 1000 Squirrels Datalogger V1.0
KeyCode : 1KS
This driver will interface to the Grant “1000 Squirrels” Datalogger.
Driver configuration:
RTU
TYpe 1KS – Set the RTU driver to the Grant data logger.
DEbug <off | on>
RXTimeout <2000>
MAXRetries <2>
COMM
POrt < COM2> – The RTU driver must use COM2 (RS232).
BAud <9600>
DAtabits <8>
PArity <None>
STopbits <1>
IKS Driver I/O Configuration
GDN ADd <pid> <index> <address> <f1> <f2> <f3> <f4> <type>
IO Point Configuration
Address : not used
F1 : Command
F2 : see below.
F3 : see below
F4 : not used.
Type : see below.
Channel Data
F1 72 - Channel Data
F2 Channel # [1…n]
F3 Event bit [0…n] Signal channel only.
F4 not used.
Type Float - Calculated using channel configuration data
Int - Raw data.
UInt - Pulse counter channels.
Discrete - Event bit (use F3 to determine bit offset)