5.4 DataTaker Driver
RTU Driver : Data Taker V1.2
KeyCode : DTK
RTU
TYpe DTK – Set the RTU driver to DataTaker.
DEbug <off | on>
MAXRetries <2> – The default is 2.
RXTimeout <1> – The default is 1.
COMM
POrt <COM1 | COM2 | COM4> – The RTU driver must use COM2
(RS232) or COM4 (RS485). COM1 is the network port for the TPAC.
BAud <1200 | 2400 | 4800 | 9600 | 14400 | 19200 | 28800 | 38400>
DAtabits <7 | 8>
PArity <None | Even | Odd>
STopbits <1 | 2>
DTK Driver I/O Configuration
To translate add or modify I/O points for the DataTaker use the format:
GDN ADd <pid> <index> <address> <f1> <f2> <f3> <f4> <type>
GDN IO Point Definition for DataTaker DT800
IO Point Definition Usage
Address Channel Address
F1 Channel Type
F2 Channel Modifier #1
F3 Channel Modifier #2
F4 Channel Modifier #3
Type See below
IO Point types
- Analog input/output: Float
- Digital input/output:
- State I/O: Discrete
- Nibble/Byte I/O: Unsigned Char
- Word: Unsigned Integer
- Counter: Unsigned Integer
- Miscellaneous
- Channel Variable: Float
- System Variable: Float
- System Time: Unsigned Long