Most ROC devices have default communication settings of 9600 bits per second, 8 data bits,
no parity and 1 stop bit. If the communication is not working, use ROCLINK of GV101 to
verify the ROC settings. The next figure shows a sample ROC configuration.
Figure 23: ROC Configuration
ROC Driver I/O Configuration
Add or modify and I/O point to the TPAC with the following command and the parameters.
GDN ADd <pid> <index> <address> <f1> <f2> <f3> <f4> <type>
The following table describes the parameters that are necessary to configure a ROC I/O
point. A ROC protocol manual may be required to determine the parameter numbers and
point types.
ROC I/O Point configuration
Address F1 F2 F3 F4
(ROC address) (ROC group
number)
(Point type)
1-DI
2-DO
3-AI
4-AO
5-PI
Location 0-68 Parameter #
6-Pid PID # 0-3 Parameter #
7-AGA config.
10-AGA flow
Flow Run #0-XX Parameter #
17-Soft points Softpoint # 0-31 Data #
Address Group
256-History History point # 0-89 # of days before
yesterday (yesterday=0)
Other point types can be used for various user programs.