Specifications
© Wired Rite Systems, Inc. 800-538-7483 www.wiredrite.com Docsst-4-01.8 Rev 0 Page 7
PROGRAMMING
Parameter Value Description
“A”
Plunger Mode
1 Single plunger (Start/Stop only)
2* Dual plunger (Start/Stop/Throttle)
“b”
Throttle Mode (Only if A is set to 2)
1* Throttle relays latch ON and OFF (maintained)
2 Throttle relays are momentary (on-demand)
3 T1 latches ON, T2 momentary, STOP turns both OFF
4 T1 & T2 latch ON, T2 OFF, STOP turns both OFF
5† Timed operation (see “E”)
6 T1 latches ON, T1 OFF & T2 latches ON, T1 & T2 OFF
7 T1 momentary ON, T2 momentary ON, repeat
8 No throttle mode
9†
As soon as MASTER Power is applied:
T1 latches ON, T2 momentary, STOP turns both OFF
A†
As soon as MASTER Power is applied:
T1 latches ON, T2 latches ON/OFF with Throttle input signal,
STOP turns both OFF
“C”
AUX (Emergency Power) Mode
1* AUX (Emergency Power) from the J1 Pin 4 input (THROTTLE)
2 AUX (Emergency Power) from the J1 Pin 5 input (START/STOP)
3 RESERVED
4 AUX (Emergency Power) from J1 Pin 2 (AUX TRIG)
5 Auto Stop on Loss of Pressure Mode (see appendix V)
“D”
AUX (Emergency Power Time)
0-9, 3* Time delay for Emergency Power relay actuation,
“E”
Throttle Mode Timer
0-9, 0* Time delay for throttle timed operation,
“F”
Glow Plug Timer
0-9, 0* Delay time for starter activation
“H”
Start Duration Timer
0-9, 5* Maximum time for starter cranking
“J”
Emergency Power Duration Time
0-d, 8* Maximum time for Emergency Power operation
“L”
Diagnostic display On/Off
0* Diagnostic Display Off
1 Diagnostic Display On
“o”
Auto Stop Pressure Delay Timer
3-d, 7* Pressure Sender delay time out when in Auto Stop Mode
“P”
Pressure Switch Descriptor
0* Normally open and ground signal indicates pressure present.
1 Normally closed and ground signal indicates NO pressure.
2 Normally open and positive signal indicates pressure present.
3 Normally closed and positive signal indicates NO pressure,
Table 3. Programmable parameters and settings. *Denotes Factory Setting. † See timer notes Appendix VI
Value Delay Time Value Delay Time Value Delay Time
0 No delay / timeout 5 10 seconds A 1 minute
1 1 second 6 15 seconds b 2 minutes
2 2 seconds 7 20 seconds C 3 minutes
3 3 seconds 8 30 seconds d 4 minutes
4 5 seconds 9 45 seconds
Table 4. Programmable Delay Timer Values