Owner manual

- 16 -
Fig. 5 Temperature Controller (4.25”L X 3.75D X 4.25”H)
Parts included:
Packaged Cooling system
Temperature Controller (4.5”LX4.5”WX3.75”D) + Air Probe
Parts not included:
Insulated ducts
CAUTION:
Low ambient condition kit is required if the installation area will be below
50°F.
2. Location
Place the unit in a properly ventilated location. If it is not, heat exhausted by
the condensing unit will build up and the cooling system will not operate
properly.
Cooling unit shall be elevated to avoid possible flooding and shaded from
direct sun. It shall not be exposed to temperatures higher than 110 °F or
lower than 50 °F.
Leave minimum 5 feet clearance for hot air exhaust and leave minimum 1 foot
clearance for the ambient fresh air intake.
Supply air flow shall be unobstructed for minimum 12” for a direct blow
installation; leave 2” clearance for a deflector installation; return air shall be
unobstructed for minimum 6”.
Overall cold –air supply and room-air return duct length can be up to 50 ft
long; overall hot-air exhaust and ambient-air intake duct length can be up to
50 ft long.
Secure the ducts with conduits to the cellar exterior walls and make sure they
are not curled, twisted, bent and clogged.