Owner`s manual
5
OZONE SUPPLY TUBING CONNECTION LOCATIONS:
OZONE-READY SPAS
If your spa is factory equipped with an ozone injection point, follow the
manufacturer’s installation instructions. Check with your dealer. After installa-
tion, you will need to test the suction at the injection point. Refer to the
section titled “DEL Suction Test” for instructions on performing this test.
NON OZONE-READY SPAS:
LOCATION “A” & “B” (see Figures 2 & 3): These are the most common
connection locations. The assembly procedures are the easiest and sufficient
ozone dispersion is provided. They can be used if the air control valves
completely close.
LOCATION “C” (see Figure 2): This location is used if the air control valve
does not have a defined closed position.
LOCATION “D” (see Figure 5): This connection procedure is used on spas
which have a two-speed pump and where the venturi air line is inaccessible or
will not provide sufficient suction to operate the ozone generator properly. A
DEL RIGID INJECTOR MANIFOLD (DEL Part Number IU-201) is required and
can be ordered from your local dealer. This connection is also used if an air
blower is provided to “supercharge” the jets.
LOCATION “E” (see Figure 5): Use this location on spas with a single-speed
pump. A DEL ADJUSTABLE INJECTOR MANIFOLD (DEL Part Number IU-
206) is required and can be ordered from your local dealer.
Locations “D” and “E” provide the most efficient method for dispersing
ozone into the spa’s water.
OZONE SUPPLY TUBING CONNECTION:
Once a suitable location has been chosen, follow the appropriate connection
instructions below.
LOCATIONS “A”, “B”, “C”:
NOTE: In the case where there are two air control valves, it may be helpful to
determine which one has the best air suction. To do this, operate the pump on
low speed with both air control valves open. Observe the action of the jets.
The lowest jet with the most bubbles will suggest the best location in the air
venturi line for the ozone supply tubing connection.