PACKAGE STANDBY SYSTEMS PSS21/B PSS21/E DSE7310 INSTALLATION AND OPERATORS MANUAL
SAVE THESE INSTRUCTIONS TABLE OF CONTENTS This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries. Read and understand all instructions in the manual before starting and operating the generator set. USING THIS MANUAL Congratulations on your choice of a Winco generator set. You have selected a high-quality, precision-engineered generator set designed and tested to give you years of satisfactory standby service.
IMPORTANT SAFETY INSTRUCTIONS 2. a. b. SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries. This engine generator set has been designed and manufactured to allow safe, reliable performance. Poor maintenance, improper or careless use can result in potential deadly hazards; from electrical shock, exhaust gas asphyxiation, or fire.
TESTING POLICY: Before any generator is shipped from the factory, it is fully checked for performance. The generator is loaded to its full capacity, and the voltage, current, and frequency are carefully checked. Rated output of generators is based on engineering tests of typical units, and is subject to, and limited by, the temperature, altitude, fuel, and other conditions specified by the manufacturer of the applicable engines.
UNPACKING INSTRUCTIONS SPECIFICATIONS GENERATOR MODEL PSS21-3 PSS21-4 PSS21-17 PSS21-18 WATTS VOLTS 21,000 22,000 22,000 25,000 120/240 120/208 120/240 277/480 AMP 89.0* 76.4** 66.2** 37.6** HZ PH RPM 60 60 60 60 1 3 3 3 1800 1800 1800 1800 ** NOTICE ** When unpacking the generator set, be sure to inspect it carefully for freight loss or damage.
INSTALLING THE FUEL LINE **** CAUTION **** EQUIPMENT DAMAGE - These units must be mounted on a solid concrete pad to prevent air from exiting under the unit. Allowing air to exit under the unit may cause the unit to overheat from lack of proper air flow. Before beginning the installation process recheck the rating of the generator set and its transfer switch rating. Be certain they can handle the intended load and are compatible with the entrance voltage, phase and current ratings.
Supply Primary Secondary Tank Regulator Regulator 1 2 3 TWO (2) REGULATOR FUEL SYSTEM LP LIQUID WITHDRAWAL SYSTEMS Generator Set 4 When installing a unit equipped the LP liquid withdrawal a primary regulator is not required on the supply tank. The supply line is connected to a liquid withdrawal valve on the supply tank and runs directly to the fuellock strainer mounted on the engine generator set.
CAUTION – PERSONAL DANGER CAUTION - NEVER dispose of a battery in a fire. The battery is capable of exploding. CAUTION - DO NOT open or mutilate the battery. Released electrolyte is known to be harmful to the skin and eyes and to be very toxic. These engine generator sets are all NEGATIVE ground. Be very careful not to connect the battery in reverse polarity, as this may short circuit the battery charging system on the engine.
B - Generator Circuit Breaker, This circuit breaker provides overload protection for the generator. Your power feeds from B - Generator Circuit Breaker, This circuit breaker provides the transfer switch will connect to the bottom lugs on the circuit overload protection for the generator. Your power feeds from the breaker. The generator powertofeeds have already wired into transfer switch will connect the bottom lugs onbeen the circuit the upper lugs. breaker.
See the manual shipped with the Automatic Transfer Switch for See the manual shipped the Automatic Transfer connection locations in the with switch. Connections in eachSwitch switchfor connection locations switch. Connections in each switch will vary depending on in thethe type of switch and the manufacturer. will vary depending on the type of switch and the manufacturer.
The generator starting contacts connections are on the controller. Refer to the generator manual. Disconnect the generator battery and verify that the ignition switch is in the OFF position. Connect the generator starting wires to the appropriate terminals on terminal block TB7 ASCO 185 as shown onUL the SWITCH wiring diagram. For wiring convenience terminal block TB7 has ainremovable plug. See Your DC connection points the ASCO 185 ATS areFigure 4 terminals “4”A. and “5 on the interface terminal block.
A F. START – this Thisbutton button active only in the after MANUAL or STOP/ ECU, pressing in is STOP/RESET mode pressing the STARTmode. Pressing button (to power the willincancel any “passive) RESET thisECU) button the MANUAL mode will alarms on the engine ECU.for testing. The engine will continue to start the engine locally J run until either the STOP/RESET or the AUTO button is pressed. 1 2 H 3 F.
STARTING PROCEDURE (G1 and G3) and the G-N to be certain of a balanced voltage output and a solid neutral connection. The voltage between G1 and G-N should be about 120 volts AC (277 on 480 units). The same approximate voltage should be found between terminals G3 and G-N (120 volts AC).
TROUBLESHOOTING TABLES UNIT WILL NOT CRANK WHEN THE POWER FAILS 1. 1. DSE Controller not in "AUTO". 2. Transfer control switch not in "AUTOMATIC" position. 3. Incorrect wiring between transfer switch and generator. 4. Blown fuses on engine control box. 5. Defective DSE Control. 6. Loose or dirty battery terminals. 7. Defective auto start controller in the transfer switch. 8. Defective starter. 9. Defective start solenoid. 10. Defective ECU on engine. 2. 3. 4.
VOLTAGE REGULATOR WIRING VOLTAGE REGULATOR WIRING THREE PHASE AND SINGLE PHASE THREE PHASE AND SINGLE PHASE 60706-227 60706-240 Page 13 Page 13 2090-00 3025-00
THREE PHASE-LOW WYE 120/208 VOLTS THREE PHASE AC WIRING HIGH AND LOW WYE THREE PHASE-HIGH WYE 277/480 VOLTS 60706-240 60706-227 Page 14 Page 14 3025-00 2090-00
60706-227 60706-240 Page 15 Page 15 2090-00 3025-00 SINGLE PHASE 120/240 VOLTS THREE PHASE -DELTA 120/240 VOLTS THREE PHASE AC WIRING - DELTA SINGLE PHASE AC WIRING
ENGINE CONTROL SCHEMATIC 3025-00 Page 16 60706-240
60706-240 Page 17 3025-00 DIMENSIONS ARE SUBJECT TO CHANGE. ALWAYS OBTAIN A CERTIFIED DRAWING FOR CONSTRUCTION PURPOSES.
12 MONTH LIMITED WARRANTY WINCO, Incorporated warrants to the original purchaser for 12 months or 1000 hours which ever occurs first, that goods manufactured or supplied by it will be free from defects in workmanship and material, provided such goods are installed, operated and maintained in accordance with WINCO written instructions. WINCO’s sole liability, and Purchaser’s sole remedy for a failure under this warranty, shall be limited to the repair of the product.