PACKAGE STANDBY SYSTEMS PSS21/A DSE 7110 INSTALLATION AND OPERATIONS MANUAL
SAVE THESE INSTRUCTIONS TABLE OF CONTENTS This manual contains important instructions that INTRODUCTION should be followed during installation and maintenance GUIDE TO PRODUCT SAFETY of the generator and batteries. BASIC INFORMATION Description Read and understand all instructions in the manual DSE 7110 Description before starting and operating the generator set.
IMPORTANT SAFETY INSTRUCTIONS 2. FIRE HAZARD - Natural gas and L.P. present a hazard of possible explosion and/or fire. a. b. SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries. 3. Read and understand all instructions in the manual before starting and operating the generator set. This engine generator set has been designed and manufactured to allow safe, reliable performance.
TESTING POLICY: Before any generator is shipped from the factory, it is fully checked for performance. The generator is loaded to its full capacity, and the voltage, current, and frequency are carefully checked. Rated output of generators is based on engineering tests of typical units, and is subject to, and limited by, the temperature, altitude, fuel, and other conditions specified by the manufacturer of the applicable engines. fuel.
UNPACKING INSTRUCTIONS SPECIFICATIONS GENERATOR MODEL PSS21-3 PSS21-4 PSS21-17 PSS21-18 ** NOTICE ** WATTS VOLTS 21,000 22,000 22,000 25,000 120/240 120/208 120/240 277/480 AMP 89.0* 76.4** 66.2** 37.6** HZ PH RPM 60 60 60 60 1 3 3 3 1800 1800 1800 1800 *Unity Power Factor - Derate 3.5% per 1000 feet elevation above sea level. **Power Factor .8 - Derate 3.5% per 1000 feet elevation above sea level.
INSTALLING THE FUEL LINE **** CAUTION **** EQUIPMENT DAMAGE - These units must be mounted on a solid concrete pad to prevent air from exiting under the unit. Allowing air to exit under the unit may cause the unit to overheat from lack of proper air flow.
Supply Primary Secondary Tank Regulator Regulator 1 2 3 TWO (2) REGULATOR FUEL SYSTEM LP LIQUID WITHDRAWAL SYSTEMS Generator Set 4 Supply Primary Generator Tank Regulator Set 1 2 4 SINGLE REGULATOR FUEL SYSTEM Reference numbers 1 through 3 in the block diagrams above are fuel lines supplied by customer. Reference number 4 is the engine generator set. Below is a table of the fuel pressure readings at each reference in the system. Single Regulator (L.P. Vapor only) 1 TANK PSI 2 7-11 in 4-6 oz.
CAUTION – PERSONAL DANGER CAUTION - NEVER dispose of a battery in a fire. The battery is capable of exploding. CAUTION - DO NOT open or mutilate the battery. Released electrolyte is known to be harmful to the skin and eyes and to be very toxic. These engine generator sets are all NEGATIVE ground. Be very careful not to connect the battery in reverse polarity, as this may short circuit the battery charging system on the engine.
To wire the automatic transfer switch into the existing wiring, first determine which circuits will be on the emergency load circuit. If the entire load is to be transferred, the transfer switch can be wired in directly after the watt-hour meter and the service entrance, providing the service entrance ampere rating is within the transfer switch’s rated capability.
See the manual shipped with the Automatic Transfer Switch for connection locations in the switch. Connections in each switch will vary depending on the type of switch and the manufacturer. GROUNDING A grounding lug has been provided on the engine generator set to grounded to earth ground if required. Check with your local codes. Generally a 6 foot copper rod driven into the earth will provide a proper earth ground. D.C.
ASCO 165 UL SWITCH Your DC connection points in the ASCO 165 ATS are terminals “4” and “5 on the interface terminal block. ASCO 300 UL SWITCH Your DC connection points in the ASCO 300 ATS are terminals “14” and “15”. Depending on the size of the switch they are located in different locations. See next page: D. AC INTERFACE CONNECTOR - This connector is used to interface with the AC generator end. It provides the controller with the voltage, amperage and frequency reading for the display. E.
A J F. START – This button is active only in the MANUAL or STOP/ RESET mode. Pressing this button in the MANUAL mode will start the engine locally for testing. The engine will continue to run until either the STOP/RESET or the AUTO button is pressed.
panel. The voltage should also be checked between the hot terminals (G1 and G3) and the G-N to be certain of a balanced voltage output and a solid neutral connection. The voltage between G1 and G-N should be about 120 volts AC (277 on 480 units). The same approximate voltage should be found between terminals G3 and G-N (120 volts AC).
TROUBLESHOOTING TABLES ENGINE WILL NOT COME UP TO SPEED AFTER IT STARTS UNIT WILL NOT CRANK WHEN THE POWER FAILS 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. DSE Controller not in "AUTO". Transfer control switch not in "AUTOMATIC" position. Incorrect wiring between transfer switch and generator. Blown fuses on engine control box. Defective DSE Control. Loose or dirty battery terminals. Defective auto start controller in the transfer switch. Defective starter. Defective start solenoid. Defective ECU on engine. 1. 2.
VOLTAGE REGULATOR WIRING THREE PHASE AND SINGLE PHASE 60706-197 Page 13 0210-10 REV B
THREE PHASE-LOW WYE 120/208 VOLTS THREE PHASE AC WIRING HIGH AND LOW WYE THREE PHASE-HIGH WYE 277/480 VOLTS 60706-197 Page 14 0210-10 REV B
60706-197 Page 15 0210-10 REV B SINGLE PHASE 120/240 VOLTS THREE PHASE -DELTA 120/240 VOLTS THREE PHASE AC WIRING - DELTA SINGLE PHASE AC WIRING
ENGINE CONTROL SCHEMATIC 0210-10 REV B Page 16 60706-197
60706-197 Page 17 0210-10 REV B DIMENSIONS ARE SUBJECT TO CHANGE. ALWAYS OBTAIN A CERTIFIED DRAWING FOR CONSTRUCTION PURPOSES.
MODE ICONS AUTO RUN ICONS INSTRUMENTATION ICONS 0210-10 REV B Page 18 60706-197
WARNING ALARMS 60706-197 Page 19 0210-10 REV B
SHUTDOWN ALARMS 0210-10 REV B Page 20 60706-197
ACCESSING THE FRONT PANEL CONFIGURATION EDITING A PARAMETER 60706-197 Page 21 0210-10 REV B
12 MONTH LIMITED WARRANTY WINCO, Incorporated warrants to the original purchaser for 12 months or 1000 hours which ever occurs first, that goods manufactured or supplied by it will be free from defects in workmanship and material, provided such goods are installed, operated and maintained in accordance with WINCO written instructions. WINCO’s sole liability, and Purchaser’s sole remedy for a failure under this warranty, shall be limited to the repair of the product.