PACKAGE STANDBY SYSTEMS INSTALLATION AND OPERATIONS MANUAL PSS80/A Natural Gas Only Engine Generator Set
SAVE THESE INSTRUCTIONS TABLE OF CONTENTS This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries.
IMPORTANT SAFETY INSTRUCTIONS 2. FIRE HAZARD - Natural gas and L.P. present a hazard of possible explosion and/or fire. a. SAVE THESE INSTRUCTION This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries. b. 3. Read and understand all instructions in the manual before starting and operating the generator set. This engine generator set has been designed and manufactured to allow safe, reliable performance.
2) ENGINE/GENERATOR TESTING POLICY: Before any generator is shipped from the factory, it is fully checked for performance. The generator is loaded to its full capacity, and the voltage, current, and frequency are carefully checked. Rated output of generators is based on engineering tests of typical units, and is subject to, and limited by, the temperature, altitude, fuel, and other conditions specified by the manufacturer of the applicable engines.
FUNCTIONS DGC-2020 Digital Genset Controllers perform the following functions: temperature, battery voltage, speed, engine load, coolant level (from ECU), ECU specific parameters, and run-time statistics. Generator Protection and Metering Generator protection guards against over voltage, under voltage, under frequency, and over frequency. Over current and phase imbalance protection is available as an option at the time of manufacture.
J - Reset Push-button. This button is pressed to cancel a settings editing session and discard any settings changes. When pressed, this button also resets the Breaker Management PreAlarms K - Arrow Push-buttons. These four buttons are used to navigate through the front panel display menus and modify settings. The left- and right-arrow buttons are used to navigate through the menu levels.
The engine manufacturer has established an excellent worldwide engine service organization; engine service is available from a nearby authorized dealer or distributor; check the Yellow Pages of the telephone directory under “engines,” or ask the dealer from whom you purchased the power plant. The rated power of each engine-generator is limited by the temperature, altitude and all other ambient conditions specified by the engine manufacturer. Engine power will decrease 3-1/2% for each 1000 ft.
Connect the fuel supply to the inlet of the fuel solenoid (see table for recommended line size). The pressure at the secondary demand regulator must be four to six ounces psi (per square inch) or 7 to 11 inches W.C. (Water column) for vapor withdrawal units. On units equipped with liquid withdrawal fuel systems full tank pressure is plumbed to the fuellock strainer mounted on the generator rails. The fuel converter mounted on the unit will handle both vaporization of the fuel and pressure reduction.
Notice the preceding tables give two (2) different units of measuring fuel pressure. The first is with a pressure gauge calibrated in ounces per square inch. The second and most accurate is the use of a simple water manometer. A manometer is calibrated in inches of water column. When installing or replacing batteries, use the proper group/size starting battery. The battery should be a Maintenance Free lead acid design. Deep cycle batteries will not work for this application.
Never fill the battery above the fill line. Over filling above the upper level line may cause the electrolyte to overflow, resulting in corrosion to the engine or nearby parts. Immediately wash off any spilled electrolyte following the procedure above. NOTE: Always make sure that a new battery is fully charged before installing it on a generator set. Failure to do so can cause damage to the engine control module in the generator set. All connections must be clean and tight.
B - Generator Circuit Breaker, This circuit breaker provides overload protection for the generator. Your power feeds from the transfer switch will connect to the bottom lugs on the circuit breaker. The generator power feeds have already been wired into the upper lugs. The load current carrying wires (L) and (T) must be sized to handle the maximum load current without excessive voltage drop.
All DC connections are completed in the small box just below the engine control cabinet. In addition there are two small fuses mounted on the top of the engine control cabinet that protect both the engine control and all the other DC connections. See the display on the pervious page for call outs.. CONTROL PANEL LAYOUT A - DGC-2020 Digital Gen-Set Control. See Explanation on page 3. NOTE: This feature must be turned on at the time the manufacture.
ASCO 300 UL SWITCH Your DC connection points in the ASCO 300 ATS are terminals “14” and “15”. Depending on the size of the switch they are located in different locations. See next page: PROCEDURE Depress the “RUN” push-button on the front of the DGC. The engine-generator will crank and start automatically. If the engine fails to start, depress the “stop” push-button and correct the trouble before proceeding. With the engine running smoothly check the no load voltage and frequency on the digital display.
TROUBLESHOOTING TABLES ATS PANEL WILL NOT TRANSFER TO EMERGENCY SUPPLY (GENERATOR) UNIT WILL NOT CRANK WHEN THE POWER FAILS. 1. 2. 3. 4. 5. 6. 7. 8. 9. 1. 2. 3. 4. Digital Genset Controller not in "AUTO". Transfer control switch not in "AUTOMATIC" position. Incorrect wiring between transfer switch and generator. Blown fuses on Digital Genset Controller. Defective Digital Genset Controller. Loose or dirty battery terminals. Defective auto start controller in the transfer switch. Defective starter.
60706-193 Page 13 9315-00 PSS60LS & 80LS OUTLINE DRAWING AND WIRING ENTRANCE
THREE PHASE-LOW WYE 120/208 VOLTS THREE PHASE AC WIRING HIGH AND LOW WYE THREE PHASE-HIGH WYE 277/480 VOLTS 60706-193 Page 14 9315-00
60706-193 Page 15 9315-00 SINGLE PHASE 120/240 VOLTS THREE PHASE -DELTA 120/240 VOLTS THREE PHASE AC WIRING - DELTA SINGLE PHASE AC WIRING
VOLTAGE REGULATOR WIRING THREE PHASE AND SINGLE PHASE 9315-00 Page 16 60706-193
DC SCHEMATIC 60706-193 Page 17 9315-00
12 MONTH LIMITED WARRANTY WINCO, Incorporated warrants to the original purchaser for 12 months or 1000 hours which ever occurs first, that goods manufactured or supplied by it will be free from defects in workmanship and material, provided such goods are installed, operated and maintained in accordance with WINCO written instructions. WINCO’s sole liability, and Purchaser’s sole remedy for a failure under this warranty, shall be limited to the repair of the product.