PACKAGE STANDBY SYSTEMS PSS50LS/C PSS75LS/A INSTALLATION AND OPERATIONS MANUAL for UNITS EQUIPPED WTH BASLER DIGITAL GENSET CONTROLS Engine Generator Set 225 SOUTH CORDOVA AVE LE CENTER MN 56057 507-357-6831
Read and understand all instructions in the manual before starting and operating the generator set. USING THIS MANUAL Congratulations on your choice of a Winco generator set. You have selected a high-quality, precision-engineered generator set designed and tested to give you years of satisfactory standby service. To get the best performance from your new engine generator set, it is important that you carefully read and follow the operating instructions in this manual.
2. SAFETY INFORMATION This engine generator set has been designed and manufactured to allow safe, reliable performance. Poor maintenance, improper or careless use can result in potential deadly hazards; from electrical shock, exhaust gas asphyxiation, or fire. Please read all safety instructions carefully before installation or use. Keep these instructions handy for future reference. Take special note and follow all warnings on the unit labels and in the manuals. FIRE HAZARD - Natural gas and L.P.
TESTING POLICY: 2) ENGINE/GENERATOR Before any generator is shipped from the factory, it is fully checked for performance. The generator is loaded to its full capacity, and the voltage, current, and frequency are carefully checked. PSS50LS- The engine generator set consists of a GM 5.7L V-8 industrial, liquid cooled engine equipped to run on L.P./N.G. fuel. The engine operates at 1800 rpm and frequency regulation is maintained by the electronic governor within .
Battery Overvoltage 15 VDC Low Battery Voltage 10 VDC Weak Battery Voltage 7.5 VDC Coolant Temperature Sender Failure Oil Pressure Sender Failure Magnetic Pickup Failure N/A N/A N/A Enabled Enabled Enabled SPECIFICATIONS GENERATOR MODEL During normal operation the DGC will continuously display the engine oil pressure, coolant temperature and the battery voltage reading.
***** CAUTION **** UNPACKING INSTRUCTIONS ** NOTICE ** When unpacking the generator set, be sure to inspect it carefully for freight loss or damage. If loss or damage is noted at the time of delivery, require that the person making the delivery make note of the loss or damage on the freight bill, or affix his signature under the consignees’s memo of the loss or damage. Contact the carrier for claim procedures.
INSTALLING THE FUEL LINE FUEL PRESSURE (vapor system) ** NOTICE ** Correct fuel pressure cannot be stressed enough. The most common cause for inoperative systems is an inadequate or incorrect fuel pressure. Performance of the engine is in direct relation to the correctness of the fuel system. Shown below is a block diagram of a typical L.P. or N.G. Installation.
Notice the preceding tables give two (2) different units of measuring fuel pressure. The first is with a pressure gauge calibrated in ounces per square inch. The second and most accurate is the use of a simple water manometer. A manometer is calibrated in inches of water column. NOTE: Always make sure that a new battery is fully charged before installing it on a generator set. Failure to do so can cause damage to the engine control module in the generator set.
not be able to transfer the complete electrical system. In this case it will be necessary to install a secondary emergency distribution panel or purchase a larger transfer switch. .1/74- # ************* ***** WARNING ***** ************* Service Entrance PERSONAL INJURY - Be certain the operation selector switch on the front of the A.T.S. Control is in the “stop” position and the main power switch “off”.
All the neutral leads (G-N, L-N and T-N) must be carried through the A.T.S. These leads are all bonded together within the A.T.S. and are bonded to GROUND at one common point. If your system requires an isolated neutral, this neutral to ground bond can be isolated by removing the copper strap located between the LINE terminal L-N and the ground lug in the panel.
There is no neutral connection point in these switches so all three neutral leads (line neutral, generator neutral and load neutral) should be connected together and taped up. See the prints enclosed with UL-ATS panel for additional information. ************* ***** WARNING ***** ************* EQUIPMENT DAMAGE - The UL-ATS panels are voltage sensitive. Do not attempt to use a 240 volt ATS on a 208 volt system. Doing so will cause damage to the control circuits in the ATS panel.
clean 'break before make' action in the transfer switch. The restoration of line power also sends a stop signal to the engine generator set. This stop signal will activate the 5 minute timer circuit and shut down the unit 5 minutes later. This completes your installation and unit testing. ALWAYS leave the system in standby mode unless servicing the unit. For standby operation, keep both the generator set and transfer selector switches in the “AUTOMATIC” position. 8.
ENGINE CRANKS BUT WILL NOT START 1. 2. 3. 4. 5. 6. 7. 8. 9. Improper fuel pressure being delivered to unit. Fuel supply shut off. Fuel tank empty. Defective spark plug. Defective engine ignition module. Dirty air cleaner filter. Defective fuel solenoid valve. Low battery. Defective fuel regulator ATS PANEL WILL NOT RETRANSFER TO NORMAL POWER 1. 2. 3. 4. NO AC OUTPUT FROM GENERATOR 1. 2. 3. 4. 5. 6. 7. 8. ENGINE STARTS AND THEN STOPS AND ALARM LIGHT COMES ON 1. 2. 3. 4. 5. Engine is low on oil.
THREE PHASE AC WIRING HIGH AND LOW WYE V1 - T2 V2 - T5 V5 - T8 V6- T11 U1 - T1 U2 - T4 U5 - T7 U6 - T10 Lead Cross Ref. U =L1 V =L2 W =L3 N=N W1- T3 W2 - T6 W5 - T9 W6 - T12 V1 - T2 V2 - T5 V5 - T8 V6- T11 THREE PHASE-LOW WYE 120/208 VOLTS Lead Cross Ref.
60706-156 Page 13 3113-00 U1 - T1 U2 - T2 U5 - T3 U6- T4 Lead Cross Ref. U1 =L1 U6 =L3 N=N SINGLE PHASE 120/240 VOLTS V1 - T2 V2 - T5 V5 - T8 V6- T11 W1- T3 W2 - T6 W5 - T9 W6 - T12 Lead Cross Ref.
VOLTAGE REGULATOR WIRING THREE PHASE AND SINGLE PHASE 3113-00 Page 14 60706-156
DC SCHEMATIC 60706-156 Page 15 3113-00
PSS50 & 75LS OUTLINE DRAWING AND WIRING ENTRANCE 60706-156 Page 16 3113-00
12 MONTH LIMITED WARRANTY WINCO, Incorporated warrants to the original purchaser for 12 months that goods manufactured or supplied by it will be free from defects in workmanship and material, provided such goods are installed, operated and maintained in accordance with WINCO written instructions. WINCO’s sole liability, and Purchaser’s sole remedy for a failure under this warranty, shall be limited to the repair of the product.
60706-156-3113-00 225 SOUTH CORDOVA AVE LE CENTER MN 56057 Phone - 507-357-6831 Fax - 507-357-4857 Website www:wincogen.