PACKAGE STANDBY SYSTEMS PSS20000LS PSS35000 PSS70000 INSTALLATION AND OPERATIONS MANUAL Engine Generator Set Automatic Transfer Switch 225 SOUTH CORDOVA AVE LE CENTER MN 56057 507-357-6831
Read and understand all instructions in the manual before starting and operating the generator set. USING THIS MANUAL Congratulations on your choice of a Winco generator set. You have selected a high-quality, precision-engineered generator set designed and tested to give you years of satisfactory portable service. To get the best performance from your new engine generator set, it is important that you carefully read and follow the operating instructions in this manual.
2. SAFETY INFORMATION This engine generator set has been designed and manufactured to allow safe, reliable performance. Poor maintenance, improper or careless use can result in potential deadly hazards; from electrical shock, exhaust gas asphyxiation, or fire. Please read all safety instructions carefully before installation or use. Keep these instructions handy for future reference. Take special note and follow all warnings on the unit labels and in the manuals. FIRE HAZARD - Natural gas and L.P.
a line side contactor and a generator side contactor. The contactors are both electrically and mechanically interlocked. An automatic taper battery trickle charger (40 MA max) and a seven day electronic exerciser clock are installed in the A.T.S. as standard equipment. The A.T.S. also contains the power failure sensing circuitry necessary to send a start/stop signal to the engine generator set. TESTING POLICY: Before any generator is shipped from the factory, it is fully checked for performance.
The engine manufacturer has established an excellent world-wide engine service organization; engine service is available from a nearby authorized dealer or distributor; check the yellow pages of the telephone directory under “engines,” or ask the dealer from whom you purchased the power plant. The rated power of each engine-generator is limited by the temperature, altitude and all other ambient conditions specified by the engine manufacturer. Engine power will decrease 3-1/2% for each 1000 ft.
INSTALLATION inform you of the engine’s requirements and assist in making you aware of the decisions you must make. In no case should the instructions or information provided be interpreted to conflict with any local, state or national codes. If in doubt, always consult your local fire marshal or gas supplier. General Information ************* ***** WARNING **** ************* PERSONAL INJURY - Before proceeding with the installation, be sure the operation selector switch is in the "stop" position.
Two (2) Regulator System (L.P. Vapor only) Size of pipe normally required for generators operating on NATURAL/LP gas. up to 25 feet* over 25 feet* PSS20000 1" pipe not recommended PSS35000 1" pipe use a PSS70000 2" pipe two regulator system * Allow an additional 3 feet for each standard elbow.
**** CAUTION **** ************* ***** WARNING ***** ************* EQUIPMENT DAMAGE - In the following battery installation procedure, check to be sure the selector switch remains in the “stop” position. FIRE HAZARD - All wiring must be done by a licensed electrician, and must conform to the national electrical code and comply with all state and local codes and regulations.
Three Phase FIGURE 5 The standby generator terminals in the A.T.S. are marked “GENERATOR - G1, G2, G3 and G-N. The “hot” leads G1 G2 and G3 wire directly to the generator side contactor, terminals G1, G2 and G3. The G-N connection is made to the lug on the standoff just to the right of the generator side contactor. The line terminals in the A.T.S. are marked “LINE - L1, L2, L3 and L-N”. The “hot” leads L1, L2 and L3 will wire directly to the top lugs on the line side contactor.
Because of the many different types of service, feeder, and distribution equipment, no specific wiring instructions can be provided. It is recommended that only copper wire be used. In all cases it is essential that while the load is connected to the generator, there can be absolutely no feedback from the generator to the power line or the power line to the generator. When properly installed, the normal A.T.S. Control and safety systems will eliminate all paths for feedback.
engine generator set. This stop signal will activate the 3 minute timer circuit and shutdown the unit 3 minutes later. PROCEDURE Move the selector switch on the engine generator to the “RUN” position. The engine-generator will crank and start automatically. If the engine fails to start, return selector switch to the “stop” position and correct the trouble before proceeding. This completes your installation and unit testing. ALWAYS leave the system in standby mode unless servicing the unit.
8. With the "Hour" and "Minute" buttons, select the time you want the engine to stop. It is recommended you let the engine run at least 15 minutes during any exercise period. 3. 4. 5. 6. 7. 8. 9. 10. 11. 9. Position the top right hand (RUN) slide switch to the center (RUN) position. CLOCK NOTES: This seven day exerciser clock has seven additional program cycles available. Always keep in mind the odd number turns the unit on and the even number shuts the unit off. (i.e. (3 on, 4 off) (5 on, 6 off) etc.
4. See your engine manual for governor adjustment procedures. NO AC OUTPUT FROM GENERATOR 1. 2. 3. 4. 5. 6. 7. 8. 9. Defective rectifier. Defective surge suppressor. Defective voltage regulator. Defective rotor. Defective stator. Defective excitor rotor. Defective excitor stator. AC short in the output leads. Defective field circuit breaker. **** CAUTION **** EQUIPMENT DAMAGE - Under full load do not adjust the Hz above 60.
PROPANE VAPOR TO NATURAL GAS 1. Turn off fuel supply. 2. Remove the fuel line from the carburetor at the demand regulator. 3. Invert the regulator so the column is in the upright position. Remove the cap on the upright column of the regulator. This will expose the pressure spring adjusting screw. Turn the screw all the way out (CCW) and then back in (CW) about 8 turns. The plug should be approximately half way down for initial starting. 5. Reconnect the fuel line at the regulator. 6.
CONTROL PANEL 60706-124 Page 13 60541
THREE PHASE AC WIRING HIGH AND LOW WYE 60706-124 Page 14 60541
60706-124 Page 15 60541 THREE PHASE AC WIRING - DELTA SINGLE PHASE AC WIRING
VOLTAGE REGULATOR WIRING THREE PHASE AND SINGLE PHASE 60541 Page 16 60706-124
60706-124 Page 17 60541
60541 Page 18 60706-124
60706-124 Page 19 60541
60541 Page 20 60706-124
60706-124 Page 21 60541
60541 Page 22 60706-124
60706-124 Page 23 60541
12 MONTH LIMITED WARRANTY WINCO, Incorporated warrants to the original purchaser for 12 months that goods manufactured or supplied by it will be free from defects in workmanship and material, provided such goods are installed, operated and maintained in accordance with Winco written instructions. WINCO’s sole liability, and Purchaser’s sole remedy for a failure under this warranty, shall be limited to the repair of the product.