PACKAGED STANDBY SYSTEM INSTALLATION AND OPERATORS MANUAL PSS15B4W/D
SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries. PROPER USE AND INSTALLATION You must be sure your new engine generator set is: Read and understand all instructions in the manual before starting and operating the generator set. USING THIS MANUAL Congratulations on your choice of a Winco generator set.
SAFETY INFORMATION This engine generator set has been designed and manufactured to allow safe, reliable performance. Poor maintenance, improper or careless use can result in potential deadly hazards; from electrical shock, exhaust gas asphyxiation, or fire. Please read all safety instructions carefully before installation or use. Keep these instructions handy for future reference. Take special note and follow all warnings on the unit labels and in the manuals.
TESTING POLICY: UL Automatic Transfer Switch Sizes UNIT LINE SIDE CONTACTOR Before any generator is shipped from the factory, it is fully checked for performance. The generator is loaded to its full capacity, and the voltage, current, and frequency are carefully checked. PSS15B4W Rated output of generators is based on engineering tests of typical units, and is subject to, and limited by, the temperature, altitude, fuel, and other conditions specified by the manufacturer of the applicable engines.
L.P. TANK SIZING Required L.P. Tank size for L.P. Vapor withdrawal operating at various outside temperatures given in degrees Fahrenheit (Celsius) TANK TEMPERATURE MODEL 60 f(16 c) 32 f(0 c) 0 f(-18 c) -20 f(-29 c) PSS15B4W 150 Gal. 250 Gal. 500 Gal. 1000 Gal. ENGINE SPECIFICATIONS: Refer to engine operating and maintenance instructions. of delivery by the carrier, but which is discovered later. The carrier or carriers are responsible for merchandise lost or damaged in transit.
ENGINE GENERATOR SET MOUNTING WARNING - Personal Injury The enclosures on these units can become very hot adjacent to the exhaust areas. Special care must be taken when installing these units to insure that the risk of contact by people is minimized. The unit’s main frame should be bolted solid to a four to six inch thick cement pad. The engine-generator is mounted on a sub-frame which is isolated with special shock mounts on the main frame.
************* ***** WARNING **** ************* PERSONAL DANGER - Do not use galvanized pipe in fuel line runs. The galvanized coating can become eroded and flake off, causing possible obstructions in the regulator or fuel valve. The results could range from inoperative engine start to hazardous fuel leaks.
If you are going to operate on LPG you will need to move the fuel line from the NG port to the LPG port on the fuel outlet tee. These two ports have different orifice inserts installed in them, which provide proper engine operation with no further adjustments. When moving the fuel line from one port to the other be sure not to kink or bend the line. Use as large a sweeping curve as possible and never shorten the fuel line. For proper operation the fuel line must stay the same length as it was shipped.
BATTERY CHARGING Units equipped with electric start have a small flywheel charger built into the engine flywheel assembly for recharging the starting battery. This flywheel charger generates a small AC current that passes through a rectifier/regulator assembly on the engine to produce a DC charging current. This circuit is not designed to be used as a battery charging circuit to recharge dead batteries.
CUSTOMER AC AND DC CONNECTION POINTS TORQUE SPECIFICATIONS FOR CONNECTIONS 7340-20 PAGE 8 60706-185
Generator Connections Minimum Conductor Sizes between the Generator and the ATS. Based on wire type and temperature rating. Wire has been derated for 40o C ambient temperatures. C/B kW Amp 15 60 CU Conductor AL Conductor Wire Temperature Rating 90 0C 75 0C 90 0C 75 0C #4 AWG #6 AWG #3 AWG #4 AWG To gain access to the customer connections remove the end panel opposite the hot air discharge end.
switch’s rated capability. Optional Connections If only specific circuits are to be powered under emergency power failure conditions, an additional distribution panel designated “emergency distribution panel” must be installed. All selected emergency circuits are removed from main distribution panels and reinstalled in the emergency distribution panel. Suggested circuits: freezer, refrigerator, furnace, emergency lights, sump pump, emergency outlet circuits, etc.
PROCEDURE Transfer Switch & Engine Generator Engine Generator Set only This procedure checks the electrical operation of the automatic transfer switch. If the actual operation does not follow this procedure, consult the troubleshooting section in the transfer switch manual. Move the right hand toggle switch from stop to the normal position. The alarm light should go out. Next move the left hand toggle switch from the auto to the run position. You should hear the fuel solenoid engage at this time.
the toggle switch to the stop position. In the stop position the alarm light will come on and the engine generator set will not start or run. TROUBLESHOOTING TABLES GENERATOR EXERCISER CIRCUIT The automatic generator exerciser is configured to automatically exercise to generator for 20 minutes once every fourteen days . In order to set and test the exercise circuit the right hand toggle switch on the generator control panel must be in the normal position.
ENGINE STARTS AND THEN STOPS. 1. 2. PREVENTIVE MAINTENANCE Engine is low on oil. Faulty oil lpressure switch on engine. ENGINE WILL NOT COME UP TO SPEED AFTER IT STARTS. 1. 2. 3. 4. Insufficient fuel volume getting to the unit. a. Fuel line too small. b. Low fuel pressure. AC short circuit. Wiring to the A.T.S. panel crossed or shorted. Unit is overloaded, check load amperage. ATS PANEL WILL NOT TRANSFER TO EMERGENCY SUPPLY (GENERATOR). 1. 2. 3. No AC generator output from generator.
AC AND DC GENERATOR WIRING DIAGRAM 7340-20 PAGE 14 60706-185
WINCO UL ATS Complete installation instructions for WINCO UL Automatic Transfer Switches are contained in the operator manual with each switch. Read the complete instructions before installing. CUSTOMER DC CONNECTION POINT All control wires (18-12 AWG) must be torqued to 19 in-lbs.
GENERATOR LAYOUT PSS15B4W 7340-20 PAGE 16 60706-185
12 MONTH LIMITED WARRANTY WINCO, Incorporated warrants to the original purchaser for 12 months or 1000 hours which ever occurs first, that goods manufactured or supplied by it will be free from defects in workmanship and material, provided such goods are installed, operated and maintained in accordance with WINCO written instructions. WINCO’s sole liability, and Purchaser’s sole remedy for a failure under this warranty, shall be limited to the repair of the product.
MAINTENANCE LOG DATE P/N 60706-185 7340-20 ITEM WORK PERFORMED 225 SOUTH CORDOVA AVE LE CENTER MN 56057 Phone: 507-357-6831 www.wincogen.