Mobile Diesel Systems OWNERS MANUAL MD25K/C INSTALLATION AND OPERATION INSTRUCTIONS 60706-101
Read and understand all instructions in the manual before starting and operating the generator set. USING THIS MANUAL Congratulations on your choice of a Winco generator set. You have selected a high-quality, precision-engineered generator set designed and tested to give you years of satisfactory portable service. To get the best performance from your new engine generator set, it is important that you carefully read and follow the operating instructions in this manual.
GUIDE TO PRODUCT SAFETY This engine generator set has been designed and manufactured to insure your personal safety. Improper use can result in potential deadly hazards, from electrical shock, exhaust gas asphyxiation, or fire. Please read all safety instructions carefully before installation or use.Keep these instructions handy for future reference.Take special note and follow all warnings on the unit and in the manuals.
SPECIFICATIONS UNPACKING GENERATOR SPECIFICATIONS When unpacking the unit, be sure to inspect it carefully for freight loss or damage. Check the nameplate to be sure it is what you ordered (proper KW, voltage, fuel, etc.). If you have questions, contact your local authorized dealer. If you see evidence of loss or damage at the time of delivery, have the driver sign and describe the loss or damage in the memo of loss or damage section on the freight bill.
COOLANT REQUIREMENTS OPERATIONS Antifreeze should be used during all seasons to protect the engine cooling system from corrosion as well as freezing damage. DESCRIPTION AND IDENTIFICATION The cooling system of the engine has been filled at the factory with a 50% water and 50% ethylene-glycol antifreeze mixture. This mixture provides protection to 34 degrees F. Never exceed a 50/50 antifreeze/water mix ratio and never use 100% antifreeze for makeup coolant. COOLANT QUANTITY MD25 US Gal 2.14 Liters 8.
coolant temperature gauge indicates engine coolant temperature. The gauge serves a dual function. In addition to displaying the water temperature it also provides the shutdown signal to the engine control module if the water temperature gets too high. The shutdown signal is preset to operate at 225 f (407 k) c. Battery Voltage Meter - This DC voltmeter monitors the VOLTAGE of the battery under static (at rest) conditions, and under cranking and charging conditions.
drop cords plugged into this receptacle may be split into 120 volt receptacles at a distribution box. This receptacle is protected by a two pole 50 amp circuit breaker mounted just above it. THIS RECEPTACLE UTILIZES A SPECIAL HUBBELL PLUG.(HUBBELL PART NUMBER CS 6365.) B. Full Power Load Connections and Breakers This Mobile Diesel Power System is equipped with both high voltage (480) and low voltage (208/240) main line breakers.
normally. If frequency has not returned at the end of this time period, the engine oil pressure status is observed to determine whether the engine is actually running or stopped. If the engine has stopped (i.e.- air in fuel, (etc), the unit is shut down with an overspeed indication and alarm. b. Overspeed indicator light can mean a loss of control signal during the previous run period (i.e.- bat. charging alternator belt broken).
*This selector position is also used for single phase 120/ 240 output, using only the L1 and L2 leads. The L3 three phase output lead is the wild leg in the delta configuration and is used only for three phase loads. 9. Check hoses and clamps for leakage. 10. Check the air cleaner indicator. Service only when indicated. Do not over-service. 11. Clean out dust cup on the air cleaner. 2.
THE ENGINE CONTROL MODULE. switch to be in for automatic start operation. 5. For most installations sixteen gauge wire is sufficient to handle the control signal. On extremely long runs increase wire size to minimize voltage drop. 18. Use the test switch on the transfer switch or shut off the incoming power to test the complete system. The MD25 should start up and the transfer switch should transfer the load to the generator. 6.
F. UNIT STORAGE Certain precautions must be taken if a mobile Diesel Generator set is to be stored for a long period of time. The unit must be stored in a dry location to prevent the generator winding from drawing moisture. The unit should also be thoroughly cleaned prior to storage. For engine storage procedures consult your local Kubota engine dealer. They have certain procedures that must be followed in order to prevent engine damage, i.e. cylinder rust and injector deterioration.
WINCO, INC. 12 Month Limited Warranty WINCO, Incorporated warrants to the original purchaser for 12 months that goods manufactured or supplied by it will be free from defects in workmanship and material, provided such goods are installed, operated and maintained in accordance with Winco written instructions. WINCOs sole liability, and Purchasers sole remedy for a failure under this warranty, shall be limited to the repair of the product.