Specifications

Nominal voltage 120/240 V 60 Hz, single phase.
Listed to UL1008 Transfer Switch Equipment and CSA Certified to CSA 22.2 No. 178-1978 Automatic
Transfer Switches.
Meets National Electrical Code (NEC) and National Fire Protection Association (NFPA) requirements.
True double-throw contacts (no intentional off position), with inherent mechanical interlocking to
prevent connection of generator and utility source.
Convenient terminals to connect neutral and ground conductors from service and load feeders.
Available in Type 1 (indoor) and Type 3R (outdoor) enclosures.
Available from stock.
Product Features
Time Delay Functions
The 165 Automatic Transfer Switch has a unique built-in automatic digital diagnostic monitoring system, which
provides status on potential system problems such as: generator failed to start; generator over frequency;
transfer switch did not transfer; and more. It’s one more way you can count on ASCO to provide continuous
power protection ...anytime.
Control Panel
Diagnostic Indicators
3-second time delay to override momentary utility source.
15-second transfer to emergency time delay to allow engine generator to stabilize after starting.
15-second time delay after transfer to the standby source to ignore momentary voltage dips on the generator
during initial loading.
5-minute time delay on retransfer to allow utility source to stabilize prior to transferring the load back to utility
1-minute unloading running time delay for engine generator cool-down before shutdown.
Residential/Light Commercial
Automatic Transfer Switches
User-friendly control panel with
easy to understand symbols
and all the necessary visual
indicators to inform the operator
of transfer switch and power
source status.