Specifications

Electrical Output 20kW/25kVa
Voltage Amperes Cycles Phase kW kVa pf
120/240 70* 60 1 20 20 1.0
120/208 69 60 3 20 25 0.8
120/240 60 60 3 20 25 0.8
277/480 30 60 3 20 25 0.8
* Available amperage at terminal block connection - additional amperage available at receptacle panel for single phase output.
4LE1
2.2 Liter
Naturally Aspirated
Powered by
STANDARD FEATURES
ISUZU 2.2 Liter 1800 RPM Engine
- Meets EPA / CARB Tier 2 Emissions
- Mechanical Governor
- Fuel/Water Separator
- Oil Drain Extension with Valve
BASLER DGC-2020 Digital Controller with Automatic Safety
Shutdowns and Digital Readouts for Low Oil Pressure, High Water
Temp, Engine Overcrank and Engine Overspeed, Low Fuel Level
Shutdown, Battery Disconnect Switch
Brushless Alternator / Class H Insulation
Standby Output: 20kW (25kVA)
Prime Output: 18kW (22.5kVA)
Motor Starting Capability: 7.5 h.p. Code G
Voltage Regulation: 1.5% / < 5% Total Harmonic Distortion
SWITCHABLE 4-Position Voltage Selector Switch with
Automatic Safety Shutdown and Safety Lock Out
AC Voltages - 3 Phase: 208, 220, 240, 416, 440, 460, 480V
AC Voltages - 1 Phase: 120, 139, 208, 220, 240V
Amps: - Single Phase 240V: 70A (at terminal block)
- Three Phase 208V: 69A
- Three Phase 240V: 60A
- Three Phase 480V: 30A
Illuminated Instrumentation Panel and Connection Box
Receptacle Package:
- 2-50amp 120/240V Twistlock Receptacles
- 2-20amp 120V GFCI Duplex Receptacles
- 1-Terminal Block for Full Connection with Safety Shut Off
Shore Power Inlet for Easy Connection to Block Heater
and Battery Charger
Pre-wired for Remote Emergency Stop (Optional Button Available)
Two Wire Remote Start Capability
Selectable High or Low Voltage Mainline Circuit Breakers
for Main Power Connection
Circuit Breakers for Single Phase Receptacles
14-gauge Galvanneal Steel Sound Attenuated Enclosure
with Critical Muffler
Sound Level: 65.9 dB(A) @ 7 Meters, Full Load
Durable Powder Coat Paint Finish / Stainless Steel Fasteners
Large Lockable Doors for Maintenance Access
Single Point Lifting Eye
Full Fluid Containment System with Drains
Lockable Fuel Access Door
Six Bolts to Remove Generator Assembly from Trailer
DOT Approved Trailer & Tank, 3,500 lb. Capacity,
Electric Brakes with Break-Away Kit, Single Axle,
Torsion Bar Suspension, Front Leveling Jack, Rear
Stabilization Jacks, Running Lights, Lighted License Plate Bracket
45-gallon, 7-gauge Steel Fuel Tank
Fuel Consumption: Run Time:
Full Load..........1.8 gal/hr Full Load.......25 hours
75% Load.........1.4 gal/hr 75% Load......32 hours
50% Load..........9 gal/hr 50% Load......50 hours
Removable and Adjustable Hitch
3” Pintle Hitch and 2 5/16” Ball Hitch both come Standard
Large Front Lockable Storage Compartment
Dimensions: Generator with Trailer - 135” x 58” x 73”
Weight: Generator with Dry Fuel Tank and Trailer - 2820 lbs
Warranty: Complete Unit - 1 Year; Engine - 2 Year Limited