HPS6000HE/I INSTALLATION AND OPERATORS MANUAL BI-FUEL GENERATOR
SAVE THESE INSTRUCTIONS PROPER USE AND INSTALLATION This manual contains important instructions that should be followed during installation and maintenance of the generator and battery. Read and understand all instructions in the manual before starting and operating the generator set. You must be sure your new engine generator set is: * Properly serviced before starting. * Operated in a well ventilated area. * Properly exhausted and gases safely dispersed. * Operated only for its designed purposes.
SAFETY INFORMATION b. c. d. e. f. This engine generator set has been designed and manufactured to allow safe, reliable performance. Poor maintenance, improper or careless use can result in potentially deadly hazards; from electrical shock, exhaust gas asphyxiation, or fire. Please read all safety instructions carefully before installation or use. Keep these instructions handy for future reference. Take special note and follow all warnings on the unit labels and in the manuals. 3.
TESTING POLICY UNIT CAPABILITIES Before any generator is shipped from the factory, it is fully checked for performance. The generator is loaded to its full capacity, and the voltage, current and frequency are carefully checked. GENERATOR CONNECTIONS Rated output of generator is based on engineering tests of typical units, and is subject to and limited by, the temperature, altitude, fuel, and other conditions specified by the manufacturer of the applicable engines.
rests with you when a generator set is sent F.O.B. shipping point. Only you can legally file a claim. load, such as an air compressor, it will require more starting current. If it is connected to a light load, or no load such as a power saw, it will require less starting current. The exact requirement will also vary with the brand or design of the motor. 2.
ay reach flames g no more than addition, nhibitors. Use of than shown oblems. It may e fuel system. ult from using a ter than shown Oil is a major factor affecting performance and service life. Use 4-stroke automotive detergent oil. Recommended Oil Use 4-stroke motor oil that meets or exceeds the requirements for API service classification SJ or later (or equivalent). Always check the API service label on the oil container to be sure it includes the letters SJ or later (or equivalent). e, and you ueling.
FUEL PRESSURE A positive fuel shut-off device must be installed in the fuel line close to the engine generator set. This manual shut-off valve is require by code even if the 12 volt fuel solenoid kit is installed. This optional 12 volt DC valve is available through your local Winco dealer and can be used to shut the fuel off during normal periods of operation without having to shut off the manual valve. Correct fuel pressure cannot be stressed enough.
CHANGING FUEL TYPES These engine generator sets are designed to run on two different fuels; gasoline, and natural gas. They may be easily changed from one fuel to another. FROM GASOLINE TO NG 1. With the engine running turn off the gasoline fuel valve. 2. Run the engine until it runs out of fuel. 3. Remove the plastic insert from the demand regulator. 4. Install a locally approved flexible fuel line. 5. Connect the NG vapor fuel line to the flexible fuel line.
INITIAL START UP WARNING: PERSONAL INJURY Lead acid batteries produce explosive hydrogen The throttle control on these generators is preset and gas when charging. Keep sparks, flames, and locked to operate at 3600 RPM (nominal) with no load burning cigarettes away from the battery. Ventilate speed set at 3690 RPM. Only a trained service techthe area when charging or using the battery in an nician should be allowed to adjust this speed setting. enclosed space.
me engine applications use a remote-mounted throttle control er than the engine-mounted throttle lever shown here. Refer to instructions provided by the equipment manufacturer. urn the engine switch to the ON position. XCEPT ELECTRIC4 TARTER TYPES Turn the ELECTRIC off/on engine switch STARTER TYPESto the on position. ON ON position. 3. Move the choke lever to the “CLOSED” ON To restart a warm engine, leave the choke lever in OFF the “OPEN” position 2.
ELECTRIC STARTING (NG only) 2. Hot weather a. Use the proper oil for the temperature expected. b. Use only summer blended gasoline. Using gasoline left over from winter may cause the unit to vapor lock. When operating on NG, you will have to always use the electric start to get the unit running. Because of the engine vacuum need to activate the fuel system 3. Move the throttle lever away from the MIN. position, about 1/3 it is almost to manual start the unit using of the way toward the MAX.
OPERATING SPEED The engine-generator must be run at the correct speed in order to produce the proper electrical voltage and frequency. CAUTION: EQUIPMENT DAMAGE The output voltage should be checked to ensure the generator is working properly prior to connecting a load to the generator. Failure to do so could result in damage to equipment plugged into the unit and possible injury to the individual. All engines have a tendency to slow down when a load is applied.
and generator ratings. The nameplate rating can be obtained through a single receptacle as long as the receptacle amperage rating is not exceeded. GROUNDING All units must be grounded. Drive a 3/4 or 1” copper pipe or rod into the ground close to the enginegenerator set. The pipe must penetrate moist earth. Connect an approved ground clamp to the pipe. Run a no. 10 Awg wire from clamp to the generator ground lug on the receptacle panel. Do not connect to a water pipe or to a ground used by a radio system.
ENGINE CARE MAINTENANCE SCHEDULE REGULAR SERVICE PERIOD (3) cal and trouble- Each Use Perform at every First Every 3 Every 6 Every Month Months Months Year or indicated month or or or or Refer to Page e. Replace filler plug. f Start the engine up and warm it up. h. After warming up the engine, recheck the oil level and refill as necessary to bring it to the proper level. 20 Hrs 50 Hrs 100 Hrs 300 Hrs operating hour interval, whichever comes first.
r replace dirty filter elements. Always replace damaged ements. If equipped with an oil-bath air cleaner, also check evel. o pages 10 − 11 for instructions that apply to the air cleaner er for your engine type. a. Bearing - The bearing used in these generators is a heavy duty double sealed ball bearing. They require no maintenance or lubrication. b. Receptacles - Quality receptacles have been utilized. If a receptacle should become cracked or otherwise damaged, replace it.
TROUBLESHOOTING SPECIFICATIONS PROBLEM (SYMPTOMS) POSSIBLE SPECIFICATIONS HPS6000HE/I CAUSES ——————————————————————— Won’t Start *Low Oil Level. *Fouled spark plug. *Out of fuel. *Start switch in Off position. *Fuel valve turn off. *Plugged fuel filter. *Blown fuse in key switch ——————————————————————— Voltage too low *Engine speed is too low. *Generator overloaded. *Defective stator. *Defective rotor (field). *Defective Capacitor.
WIRING DIAGRAM 3180-00 17 60706-238
24 MONTH LIMITED WARRANTY WINCO, Inc. warrants to the original purchaser for 24 months* that goods manufactured or supplied by it will be free from defects in workmanship and material, provided such goods are installed, operated and maintained in accordance with WINCO’s written instructions. * NOTE: Units used for rental, demonstration, commercial or prime power (off grid) application such as construction or utility, are warranted for 90 day Units that are resold are not covered under this warranty.
CALIFORNIA EVAPORATIVE EMISSION CONTROL WARRANTY STATEMENT YOUR WARRANTY RIGHTS AND OBLIGATIONS The California Air Resources Board is pleased to explain the evaporative emission control system’s warranty on your model 2013 or later generator. In California, new equipment that uses small off-road engines must be designed, built, and equipped to meet the State’s stringent anti-smog standards.