DSECONTROL ® DSE7000 Quick Start Guide 057-101 Author : John Ruddock
DSE Model 7000 Series Quick Start Guide Deep Sea Electronics Plc Highfield House Hunmanby North Yorkshire YO14 0PH ENGLAND Sales Tel: +44 (0) 1723 890099 Sales Fax: +44 (0) 1723 893303 E-mail: sales@deepseaplc.com Website: www.deepseaplc.com DSE Model 7000 series Control and Instrumentation System Operators Manual © Deep Sea Electronics Plc All rights reserved.
DSE Model 7000 Series Quick Start Guide TABLE OF CONTENTS Section Page 1 BIBLIOGRAPHY........................................................................................... 4 2 INTRODUCTION........................................................................................... 4 3 DESCRIPTION OF CONTROLS .................................................................... 5 3.1 DSE7210 / DSE7310 AUTOSTART CONTROL MODULE ............................................. 5 3.
DSE Model 7000 Series Quick Start Guide 1 BIBLIOGRAPHY This document refers to and is referred to by the following DSE publications which can be obtained from the DSE website www.deepseaplc.
DSE Model 7000 Series Quick Start Guide 3 DESCRIPTION OF CONTROLS The following section details the function and meaning of the various controls on the module. 3.1 DSE7210 / DSE7310 AUTOSTART CONTROL MODULE Main status and instrumentation display Menu navigation buttons Four configurable LEDs Close generator (manual mode only) Open generator (manual mode only) Start engine (when in manual mode) Select Stop mode Select Manual mode Select Auto mode Mute alarm / Lamp test Part No.
DSE Model 7000 Series Quick Start Guide Close Generator LED. On When The Generator Is Required To Be On Load. Generator Available LED. On when the generator is within limits and able to take load. NOTE:- “Generator on load” LED has two modes of operation depending upon the configuration of the controllers digital inputs. 1) Digital input configured for “Generator closed auxiliary” – The LED illuminates when the generator closed auxiliary input is active – The LED shows the state of the auxiliary contact.
DSE Model 7000 Series Quick Start Guide 3.2 DSE7220 / DSE7320 AMF CONTROL MODULE Main status and instrumentation display Menu navigation buttons Four configurable LEDs Transfer to generator (manual mode only) Transfer to mains (manual mode only) Start engine (when in manual mode) Select Stop mode Continued overleaf…. Mute alarm / Lamp test Select Manual mode Select Test on load mode Select Auto mode Part No.
DSE Model 7000 Series Quick Start Guide Mains Available LED. On when the mains is within limits and able to take load. Close Mains LED. On When The Generator Is Required To Be On Load. Close Generator LED. On When The Generator Is Required To Be On Load. Generator Available LED. On when the generator is within limits and able to take load. NOTE:- “Generator on load” LED has two modes of operation depending upon the configuration of the controllers digital inputs.
DSE Model 7000 Series Quick Start Guide 3.3 QUICKSTART GUIDE This section provides a quick start guide to the module’s operation. 3.3.1 STARTING THE ENGINE First, select manual mode… …then press the Start button to crank the engine. NOTE:- For further details, see the section entitled ‘OPERATION’ elsewhere in this manual. 3.3.2 STOPPING THE ENGINE Select Stop/Reset mode. The generator is stopped. NOTE:- For further details, see the section entitled ‘OPERATION’ elsewhere in this manual. Part No.
DSE Model 7000 Series Quick Start Guide 3.4 VIEWING THE INSTRUMENTS It is possible to scroll to display the different pages of information by repeatedly operating the next page button. Once selected the page will remain on the LCD display until the user selects a different page or after an extended period of inactivity, the module will revert to the status display.
DSE Model 7000 Series Quick Start Guide 3.4.
DSE Model 7000 Series Quick Start Guide 3.4.2 CAN ERROR MESSAGES When connected to a suitable CAN engine the 7000 series controller displays alarm status messages from the ECU. Alarm ECU Warning Type of alarm as reported by the ECU Warning Type of alarm that is triggered in the DSE module (ie Warning or Shutdown) Press to access the list of current active Engine DTCs (Diagnostic Trouble Codes).
DSE Model 7000 Series Quick Start Guide 3.5 VIEWING THE EVENT LOG Event log 1/50 Oil Pressure Low Shutdown 12 Sep 2007, 08:25:46 Number of present alarms. This is event 1 of a total of 50 logged events. The 7000 series modules maintains a log of the last 50 shutdown alarms (7200 series logs 30 shutdown alarms) to enable the operator or engineer to view the past alarms history. The event log only includes shutdown and electrical trip alarms logged; The event log does not contain Warning alarms.
DSE Model 7000 Series Quick Start Guide 4 OPERATION The following description details the sequences followed by a module containing the standard ‘factory configuration’. Remember that if you have purchased a completed generator set or control panel from your supplier, the module’s configuration will probably have been changed by them to suit their particular requirements. Always refer to your configuration source for the exact sequences and timers observed by any particular module in the field. 4.
DSE Model 7000 Series Quick Start Guide 4.2 AUTOMATIC MODE OF OPERATION NOTE:- If a digital input configured to panel lock is active, changing module modes will not be possible. Viewing the instruments and event logs is NOT affected by panel lock. Activate auto mode be pressing the pushbutton. An LED indicator beside the button confirms this action. Auto mode will allow the generator to operate fully automatically, starting and stopping as required with no user intervention. 4.2.
DSE Model 7000 Series Quick Start Guide 4.2.3 ENGINE RUNNING Once the engine is running, the Warm Up timer, if selected, begins, allowing the engine to stabilise before accepting the load. DSE7210/DSE7310 - The generator will be placed on load. DSE7220/DSE7320 - Load will be transferred from the mains supply to the generator NOTE:-The load transfer signal remains inactive until the Oil Pressure has risen. This prevents excessive wear on the engine.
DSE Model 7000 Series Quick Start Guide 4.3 MANUAL OPERATION NOTE:- If a digital input configured to panel lock is active, changing module modes will not be possible. Viewing the instruments and event logs is NOT affected by panel lock. Activate Manual mode be pressing the pushbutton. An LED indicator beside the button confirms this action. Manual mode allows the operator to start and stop the set manually, and if required change the state of the load switching devices. 4.3.
DSE Model 7000 Series Quick Start Guide 4.3.3 ENGINE RUNNING In manual mode, the load is not transferred to the generator unless a ‘loading request’ is made. A loading request can come from a number of sources. • • • • Pressing the transfer to generator button Mains supply out of limits (DSE7220/DSE7320 only) Activation of an auxiliary input that has been configured to remote start on load Activation of the inbuilt exercise scheduler if configured for ‘on load’ runs.
DSE Model 7000 Series Quick Start Guide 4.4 TEST MODE OF OPERATION NOTE:- Test Mode is only applicable to DSE7220/DSE7320 controllers. NOTE:- If a digital input configured to panel lock is active, changing module modes will not be possible. Viewing the instruments and event logs is NOT affected by panel lock. Activate test mode be pressing the pushbutton. An LED indicator beside the button confirms this action.
DSE Model 7000 Series Quick Start Guide 4.4.3 ENGINE RUNNING Once the engine is running, the Warm Up timer, if selected, begins, allowing the engine to stabilise before accepting the load. Load will be automatically transferred from the mains supply to the generator. NOTE:-The load transfer signal remains inactive until the Oil Pressure has risen. This prevents excessive wear on the engine.
DSE Model 7000 Series Quick Start Guide Part No.