INSTRUCTION MANUAL FOR DIGITAL GENSET CONTROLLER DGC-2020 Publication: 9400200990 Revision: K 01/09
INTRODUCTION This instruction manual provides information about the operation and installation of the DGC-2020 Digital Genset Controller.
First Printing: November 2006 Printed in USA © 2009 Basler Electric, Highland Illinois 62249 USA All Rights Reserved January 2009 CONFIDENTIAL INFORMATION of Basler Electric, Highland Illinois, USA. It is loaned for confidential use, subject to return on request, and with the mutual understanding that it will not be used in any manner detrimental to the interest of Basler Electric.
REVISION HISTORY The following information provides a historical summary of the changes made to this instruction manual (9400200990), BESTCOMSPlus software, firmware package, and hardware of the DGC-2020. Manual Revision and Date K, 01/09 Change J, 08/08 Updated manual to support firmware version 1.08.01 changes and BESTCOMSPlus version 2.03.00 changes. (See firmware and BESTCOMSPlus history below for details.
BESTCOMSPlus Version and Date 2.03.00, 01/09 Change Added Export to File feature. Added settings for Phase Toggle and Initializing Messages on General Settings, Front Panel HMI screen. Re-arranged CANbus Setup screen and added ECU Setup screen under Communications. Added settings for 51-3 element under Generator Protection, Current. Added setting for Off Mode Cooldown on System Parameters, System Settings screen. Added Remote Module Setup screen under System Parameters.
Firmware Package Version and Date 1.08.01, 01/09 Change Changed time dial range of 51 element fixed time curve from 0-30 s to 0-7,200 s. Added Phase Toggle Delay setting for front panel HMI. Added Off Mode Cooldown feature. Added 51-3 element. Added Var/PF control. Added LSM Input settings. Added Checksum Fail and CEM Hardware Mismatch pre-alarms. Added kVar A, B, C, and Total metering. Added several MTU items to metering.
DGC-2020 Hardware Version and Date vi Change P, 01/09 Release firmware package 1.08.01 and BESTCOMSPlus 2.03.00. N, 09/08 Release firmware package 1.07.02. M, 07/08 Release firmware package 1.06.00 and BESTCOMSPlus 2.01.00. L, 04/08 Release firmware package 1.05.00 and BESTCOMSPlus 2.00.01. K, 01/08 Added definition of emergency stop input terminals. J, 12/07 Release firmware package 1.04.00 and BESTCOMSPlus 1.04.01.
CONTENTS SECTION 1 GENERAL INFORMATION ................................................................................................ 1-1 SECTION 2 HUMAN-MACHINE INTERFACE ....................................................................................... 2-1 SECTION 3 FUNCTIONAL DESCRIPTION ........................................................................................... 3-1 SECTION 4 BESTCOMSPlus SOFTWARE .............................................................................
This page intentionally left blank.
SECTION 1 GENERAL INFORMATION TABLE OF CONTENTS SECTION 1 GENERAL INFORMATION ................................................................................................ 1-1 DESCRIPTION....................................................................................................................................... 1-1 FEATURES ............................................................................................................................................ 1-1 FUNCTIONS ..............
Underfrequency (81U) and Overfrequency (81O) .......................................................................... 1-8 Reverse Power (32)........................................................................................................................ 1-8 Loss of Excitation (40Q) ................................................................................................................. 1-8 Overcurrent (51) (Optional)...........................................................................
SECTION 1 GENERAL INFORMATION DESCRIPTION The DGC-2020 Digital Genset Controller provides integrated engine-genset control, protection, and metering in a single package. Microprocessor based technology allows for exact measurement, setpoint adjustment, and timing functions. Front panel controls and indicators enable quick and simple DGC-2020 operation. Basler Electric communication software (BESTCOMSPlus) allows units to be easily customized for each application.
Contact Inputs and Output Contacts DGC-2020 controllers have one, dedicated emergency stop contact input and 16 programmable contact inputs. All contact inputs recognize dry contacts. The programmable inputs can be configured to initiate a pre-alarm or alarm. A programmable input can be programmed to receive an input from an automatic transfer switch or override DGC-2020 alarms and protection functions.
AEM-2020 (ANALOG EXPANSION MODULE) The optional AEM-2020 provides eight remote analog inputs, eight remote RTD inputs, two remote thermocouple inputs, and four remote analog outputs to the DGC-2020. The AEM-2020 communicates with the DGC-2020 through a CANbus interface. Refer to Section 10, AEM-2020 (Analog Expansion Module), for more information. CEM-2020 (CONTACT EXPANSION MODULE) The optional CEM-2020 provides 10 additional contact inputs and 24 additional output contacts to the DGC-2020.
Part Numbers A ten-digit part number specifies the electrical characteristics and operational features of special-order DGC-2020 controllers. Table 1-1 lists the special-order DGC-2020 controllers available along with descriptions of their operating features. Table 1-1. Special-Order DGC-2020 Controllers Part Number Style Number 9400200105 51ANBNSNH001 9400200106 11ANBNSNH001 Special Features cURus recognized for use in hazardous locations.
Contact Sensing Contact sensing inputs include 1 emergency stop input and 16 programmable inputs. The emergency stop input accepts normally closed, dry contacts. All programmable inputs accept normally open, dry contacts.
Programmable Relays (12) Rating: 2 Adc at 30 Vdc—make, break, and carry Terminals† Output 1: 52, 51 (common) Output 2: 53, 51 (common) Output 3: 54, 51 (common) Output 4: 56, 55 (common) Output 5: 57, 55 (common) Output 6: 58, 55 (common) Output 7: 60, 59 (common) Output 8: 61, 59 (common) Output 9: 62, 59 (common) Output 10: 64, 63 (common) Output 11: 65, 63 (common) Output 12: 66, 63 (common) Contact rating is reduced to 3 A for part numbers 9400200105 and 9400200106 when used in a hazardous location.
Apparent Power Indicates total kVA and individual line kVA (4-wire, line-to-neutral or 3-wire, line-to-line).
Maintenance Timer Maintenance timer indicates the time remaining until genset service is due. Value is retained in nonvolatile memory. Metering Range: 0 to 5,000 h Update Interval: 6 min Accuracy: 1% or actual indication or 12 min Display Resolution: 1/10 hour Fuel Level Metering Range: Accuracy: Display Resolution: 0 to 100% 2% (subject to accuracy of sender) 1.
Logic Timers Range: Increment: Accuracy: 0 to 10 s 0.1 s 15 ms Communication Interface USB Specification Compatibility: Data Transfer Speed: Connector Type: USB 2.0 9600 baud Mini-B jack RS-485 (Optional) Baud: Data Bits: Parity: Stop Bits: Terminals: 9600 8 None 1 14 (A), 13 (B), and 12 (shield) CANbus Differential Bus Voltage: Maximum Voltage: Communication Rate: Terminals: 1.5 to 3 Vdc –32 to +32 Vdc with respect to negative battery terminal 250 kb/s 48 (low), 49 (high), and 50 (shield) NOTES 1.
CAUTION Replacement of the backup battery for the real-time clock should be performed only by qualified personnel. Do not short-circuit the battery, reverse battery polarity, or attempt to recharge the battery. Observe polarity markings on the battery socket while inserting a new battery. The battery polarity must be correct in order to provide backup for the real-time clock. It is recommended that the battery be removed if the DGC-2020 is to be operated in a salt-fog environment.
UL/CSA Approval “cURus” recognized to UL Standard 508 & CSA Standard C22.2 No. 14. CSA certified to CSA C22.2 No. 14. CAUTION To follow UL guidelines, replacement of the backup battery for the real-time clock should be performed only by qualified personnel.
This page intentionally left blank.
SECTION 2 HUMAN-MACHINE INTERFACE TABLE OF CONTENTS SECTION 2 HUMAN-MACHINE INTERFACE ....................................................................................... 2-1 INTRODUCTION.................................................................................................................................... 2-1 FRONT PANEL ...................................................................................................................................... 2-1 DISPLAY OPERATION.............
This page intentionally left blank.
SECTION 2 HUMAN-MACHINE INTERFACE INTRODUCTION This section describes the components of the DGC-2020 human-machine interface (HMI). DGC-2020 HMI components are located on the front panel (controls and indicators) and the rear panel (terminals and connectors). FRONT PANEL Figure 2-1 illustrates the front panel HMI of the DGC-2020. Table 2-1 lists the call-outs of Figure 2-1 along with a description of each HMI component. Figure 2-1.
Table 2-1. Front Panel HMI Descriptions Locator Description A Liquid Crystal Display. The backlit, 64 by 128 pixel LCD serves as the local information source for metering, alarms, pre-alarms, and protective functions. Display operation is maintained at -40C. B Not in Auto Indicator. This red LED lights when the DGC-2020 is not operating in Auto mode. C Alarm Indicator. This red LED lights continuously during alarm conditions and flashes during pre-alarm conditions. D Supplying Load Indicator.
Permissions If communications access is active through the modem or USB, the front panel will display REMOTE COMMS, FRONT PANEL IS READ ONLY and the summary screen. This informs the user that the front panel can only be used for viewing metering data and settings information. Remote access must be ended before modifying settings through the front panel. Summary Screen and Configurable Metering The summary screen can be set to standard or scrolling.
Changing a Setting To change a setting, navigate to the setting you want to change and press the Edit key. If you are not already logged in, you will be asked to enter your password at this time. Use the Up/Down arrows to raise or lower the value. Press the Edit key again when finished. Front Panel Display Structure The front panel display begins with the SUMMARY SCREEN. Pressing the Right arrow key will open the MAIN MENU screen. The MAIN MENU screen consists of METERING and SETTINGS.
BUS V BUS FREQ SYNCHRONIZER POWER kW A kW B kW C kW TOTAL kVA A kVA B kVA C kVA TOTAL kVar A kVar B kVar C kVar TOTAL PF RUN STATISTICS CUMULATIVE o CUMULATIVE START # STARTS HRS TO MAINT KW-HRS o TOTAL RUN TIME HOURS MINUTES o LOADED RUN TIME HOURS MINUTES o UNLOADED RUN TIME HOURS MINUTES SESSION o SESSION START KW-HRS o TOTAL RUN TIME HOURS MINUTES o LOADED RUN TIME HOURS MINUTES o UNLOADED RUN TIME HOURS MINUTES 9400200990 Re
ALARMS-STATUS 2-6 ALARMS PRE-ALARMS MTU FAULT CODES (Visible when ECU is configured for MTU MDEC, MTU ADEC, or MTU ECU7.) MTU STATUS (Visible when ECU is configured for MTU MDEC, MTU ADEC, or MTU ECU7.) STATUS o EPS SUPP.
SETTINGS GENERAL SETTINGS GENERAL SETTINGS COMMUNICATIONS SYSTEM PARAMS PROGRAMMABLE INPUTS PROGRAMMABLE OUTPUTS ALARM CONFIGURATION GENERATOR PROTECTION BREAKER MANAGEMENT BIAS CONTROL MULTIGEN MANAGEMENT ENTER PASSWORD COMMUNICATIONS SYSTEM PARAMS P0053-51 PROGRAMMABLE INPUTS PROGRAMMABLE OUTPUTS (Available when Analog Expansion Module is enabled.) ALARM CONFIGURATION GENERATOR PROTECTION BREAKER MANAGEMENT BIAS CONTROL MULTIGEN MANAGEMENT (Available when Load Sharing Module is enabled.
o UTC OFFSET o DST ENABLED VIEW DATE/TIME VERSION INFO o FIRMWARE VERSION o BOOT CODE VERSION o SERIAL NUMBER o PART NUMBER o MODEL NUMBER o LANGUAGE VERSION o LANGUAGE PART NUM COMMUNICATIONS CANBUS SETUP o CANBUS SETUP CANBUS ENABLE DTC ENABLE (Visible when CANBUS is enabled.) CANBUS ADDR (Visible when CANBUS is enabled.) ECU OPT SLCT (Visible when CANBUS is enabled.) ECU PULSING (Visible when CANBUS is enabled.) ENG SHTDN TM (Visible when CANBUS is enabled.
RATED FREQ RATED RPM COOLDWN TIME OFF MODE COOLDN EPS EPS THRESHLD LOW LINE OVERRIDE SCALE FACTOR o FUEL LVL TYP o SYSTEM UNITS o BATTERY VOLT o FLYWHL TEETH o SPEED SOURCE o MAINT RESET o NFPA LEVEL o HORN o 1 PHASE O-RIDE (Visible when 1 PHASE O-RIDE INPUT is selected.) o RATED PF o POWER UP DELAY o RELAY CONTROL START RUN PRESTART REMOTE MODULE SETUP o LSM SETUP LSM ENABLE CANBUS ADDRESS (Visible when LSM-2020 is enabled.) VERSION INFO (Visible when LSM-2020 is enabled.
AEM SETUP ENABLE CANBUS ADDR (Visible when AEM-2020 is enabled.) VERSION INFO (Visible when AEM-2020 is enabled.) FIRMWARE VERSION BOOT CODE VERSION SERIAL NUMBER PART NUMBER MODEL NUMBER BUILD DATE AEM DEBUG MENU (Visible when AEM-2020 is enabled.
PROGRAMMABLE INPUTS CONFIGURABLE INPUTS o INPUT X (X = 1 to 26) ALARM CONFIG ACTIVATN DLY RECOGNITION PROG FUNCTIONS o AUTO XFER SWITCH INPUT RECOGNITION (Visible when an INPUT is selected.) o GRND DELTA O-RIDE INPUT RECOGNITION (Visible when an INPUT is selected.) o BATTLE OVERRIDE INPUT RECOGNITION (Visible when an INPUT is selected.) o LOW LINE OVERRIDE INPUT RECOGNITION (Visible when an INPUT is selected.
o OVER 2 THRESHOLD ALARM CONFIG UNDER 1 THRESHOLD ALARM CONFIG UNDER 2 THRESHOLD ALARM CONFIG ARMING DELAY THR1 ACT DLY THR2 ACT DLY HYSTERESIS OOR ALM CFG THRM_CPL_X (X = 1 to 2) OVER 1 THRESHOLD ALARM CONFIG OVER 2 THRESHOLD ALARM CONFIG UNDER 1 THRESHOLD ALARM CONFIG UNDER 2 THRESHOLD ALARM CONFIG ARMING DELAY THR1 ACT DLY THR2 ACT DLY HYSTERESIS OOR ALM CFG PROGRAMMABLE OUTPUTS (Visible when AEM-2020 is enabled) ANALOG OUTPUTS o ANALOG
MAINTENANCE INTERVAL ENABLE THRESHOLD o BATTERY OVERVOLTAGE ENABLE THRESHOLD o LOW BATTERY VOLTAGE ENABLE THRESHOLD ACTIVATN DLY o WEAK BATTERY VOLTAGE ENABLE THRESHOLD ACTIVATN DLY o HIGH FUEL LEVEL ENABLE THRESHOLD ACTIVATN DLY o CHECKSUM FAIL ENABLE o ACTIVE DTC (Visible when DTC is enabled.) ENABLE o ECU COMMS FAIL (Visible when CANBUS is enabled.) ENABLE o COOLANT LEVEL (Visible when CANBUS is enabled.
NOTE The HIGH COOLANT TEMP and LOW OIL PRESSURE alarms have an ARMING DLY setting that disables the alarm for the specified time after engine startup.
CURVE ALARM CONFIG 32 REVERSE POWER o 3 / 1 PHASE SETTINGS PICKUP HYSTERESIS TIME DELAY ALARM CONFIG 40 LOSS OF EXCITATION o 3 / 1 PHASE SETTINGS PICKUP HYSTERESIS TIME DELAY ALARM CONFIG BREAKER MANAGEMENT BREAKER HARDWARE o MAINS FAIL TRANSFER ENABLE RETURN DELAY TRANSFER DELAY MAX TRANSFER TIME o CLOSE WAIT TIME TIME o GEN BREAKER CONTINUOUS CLOSING TIME DEAD BUS CL ENBL o MAINS BREAKER CONFIGURED CONTINUOUS (Visible when Configured.
o o o o o REGUL OFFSET CLOSING ANGLE VG>VB TIME DELAY FAIL DELAY BIAS CONTROL AVR BIAS CONTROL o CONTACT (Visible when LSM-2020 is disabled or when LSM-2020 is enabled and OUTPUT TYPE = CONTACT.) TYPE CORRECTION PULSE (Visible when OUTPUT TYPE = CONTACT and CONTACT TYPE = PROPORTIONAL.) WIDTH INTERVAL o VAR CTRL DROOP DROOP GAIN VAR CTRL ENABLE (Visible when LSM-2020 is enabled.) VAR CTRL MODE (Visible when LSM-2020 is enabled.) KP (Visible when LSM-2020 is enabled.
BL ALG MAX (Visible when LSM-2020 is enabled.) BL ALG MIN (Visible when LSM-2020 is enabled.) BRKR OPEN PT (Visible when LSM-2020 is enabled.) o OUTPUT (Visible when LSM-2020 is enabled.) TYPE CONTROL DEBUG (Visible when LSM-2020 in enabled.) MULTIGEN MANAGEMENT (Visible when LSM-2020 is enabled.
REAR PANEL All DGC-2020 terminals and connectors are located on the rear panel. Rear panel terminals and connectors are illustrated in Figure 2-4. (To show the terminals and connectors, Figure 2-4 shows the DGC-2020 with the rear cover removed.) Table 2-2 lists the call-outs of Figure 2-4 along with a description of each connector type.
Table 2-2. Rear Panel HMI Descriptions Locator Description A, D The majority of external, DGC-2020 wiring is terminated at 15-position connectors with compression terminals. These connectors plug into headers on the DGC-2020. The connectors and headers have a dovetailed edge that ensures proper connector orientation. Each connector and header is uniquely keyed to ensure that a connector mates only with the correct header. Connector screw terminals accept a maximum wire size of 12 AWG.
This page intentionally left blank.
SECTION 3 FUNCTIONAL DESCRIPTION TABLE OF CONTENTS SECTION 3 FUNCTIONAL DESCRIPTION ........................................................................................... 3-1 INTRODUCTION.................................................................................................................................... 3-1 DGC-2020 FUNCTION BLOCKS........................................................................................................... 3-1 Power Supply ..............................
AUTO Mode (Running) ................................................................................................................. 3-11 Breaker Operation ............................................................................................................................ 3-11 Determining if it is Acceptable to Close a Breaker ....................................................................... 3-11 Changing the Breaker State ......................................................................
SECTION 3 FUNCTIONAL DESCRIPTION INTRODUCTION This section describes how the DGC-2020 functions. A detailed description of each function block is provided in the paragraphs under the heading of DGC-2020 Function Blocks. DGC-2020 operating and metering features are described in Section 4, BESTCOMSPlus Software. DGC-2020 FUNCTION BLOCKS To ease understanding, DGC-2020 functions are illustrated in the block diagram of Figure 3-1. The following paragraphs describe each function in detail.
Zero Crossing Detection The zero crossing of A-phase to B-phase or A-phase to C-phase (user-selectable) line voltage is detected and used to calculate the generator frequency. The zero crossing of A-phase to B-phase bus voltage is used to calculate the bus frequency. Analog-to-Digital Converter Scaled and conditioned signals representing the sensing voltage, sensing current, coolant temperature, fuel level, oil pressure, and battery voltage are digitized by the microprocessor’s analog-to-digital converter.
Coolant temperature sender connections are made at terminals 10 and 11 (sender common). Fuel Level A current is provided to the fuel level sender. The developed voltage is measured and scaled for use by the internal circuitry. An open circuit or short circuit across the fuel level sender terminals will cause the DGC-2020 to indicate a failed sender. Fuel level senders that are compatible with the DGC-2020 include Isspro model R8925. Other senders may be used.
Connections for the programmable inputs are provided at terminals 15 (Input 16) through 30 (Input 1). The negative side of the battery voltage (terminal 2) serves as the return connection for the programmable inputs. Front Panel HMI The front panel HMI provides a convenient interface for viewing system parameters and for controlling the DGC-2020/generator set. Front panel HMI components include an LCD (liquid crystal display), LED (light emitting diodes) indicators, and pushbuttons.
USB The rear-panel, mini-B USB socket enables local communication with a PC running BESTCOMSPlus software. The DGC-2020 is connected to a PC using a standard USB cable. BESTCOMSPlus is a Windows® based communication software package that is supplied with the DGC-2020. A detailed description of BESTCOMSPlus is provided in Section 4, BESTCOMSPlus Software.
ECU Parameter Total fuel used Trip fuel Metric Units liters liters English Units gallons gallons Update Rate requested 1.5 s requested 1.5 s Decimal Place none none SPN 250 182 SPN is suspect parameter number. Table 3-2.
Table 3-3. Diagnostic Information Obtained Over the CANbus Interface Parameter Transmission Repetition Rate Active diagnostic trouble code 1s Lamp status 1s Previously active diagnostic trouble code On request Request to clear active DTCs On request Request to clear previously active DTCs On request MTU Fault Codes A DGC-2020 connected to a genset equipped with an MTU engine ECU tracks and displays the active fault codes issued by the MTU engine ECU.
265, SD BANK 2 TEST 266, SD SPD DEMAND AN 267, SD SPDMTEST BNCH 269, SD LOAD PLS ANLG 270, SD SPD DEMAND 271, SD T-EXTERN 1 272, SD T-EXTERN 2 273, SD P-EXTERN 1 274, SD P-EXTERN 2 275, MD EXT.
input is open (emergency stop condition), the Pre-Start, Crank, and Fuel outputs open. When the Emergency Stop input is closed, all output contacts operate normally. DGC-2020 output contacts include Pre-Start, Crank, Fuel, and up to 12 standard programmable outputs. Additional output contacts can be accommodated with a CEM-2020 (Contact Expansion Module). Pre-Start This output closes to energize the engine glow plugs. The Pre-Start output can be programmed to close up to 30 seconds prior to engine cranking.
Generator Exerciser The unit will start at the designated time and will run for the specified duration. The breaker will be closed if “Run with Load” is checked in the generator exerciser settings. This mode is independent of the other self-starting modes. Mains Fail Transfer Functionality If mains fail transfer is enabled, the unit will run when the utility is determined to be bad, and will not stop until the utility has been determined to be good and the load has been transitioned to the utility.
The type of response given for a local request depends on the operating mode of the DGC-2020. RUN Mode When in RUN mode, the generator and mains breakers can be closed manually using contact inputs or the breaker buttons on the BESTCOMSPlus Control screen. OFF or AUTO Mode (Not Running) If operating in the OFF mode or AUTO and not running, the generator breaker cannot be closed because the generator will not be stable.
Breaker close sources are: The DGC-2020 itself when the automatic transfer (ATS) feature is enabled The DGC-2020 itself when the Run with Load logic element receives a Start pulse in the programmable logic. The DGC-2020 itself when started from a Demand Start as part of demand start/stop and sequencing. The DGC-2020 itself when started from the Exercise Timer and the Run with Load box is checked in the Generator Exerciser Settings.
Table 3-4.
Event String Event Description Event Type ATS INPUT CLOSED ATS Input Status AUTO RESTART Automatic Restart in Progress Status AUTO RESTART FAIL A Automatic Restart Fail Alarm BATT CHRG FAIL A Battery Charger Fail Alarm BATT CHRG FAIL P Battery Charger Fail Pre-Alarm BATT OVERVOLT P Battery Overvoltage Pre-Alarm BATTLE OVERRIDE Battle Override Status CEM COMM FAIL P CEM-2020 Communications Failure Pre-Alarm CEM HW MISMATCH P Connected CEM-2020 is wrong type Pre-Alarm CHECKSUM FA
Event String Event Description Event Type GN BKR OP FL P Generator Breaker Fail to Open Pre-Alarm GN BKR SYN FL P Generator Breaker Synchronization Fail Pre-Alarm HI COOLANT TMP A High Coolant Temp Alarm HI COOLANT TMP P High Coolant Temp Pre-Alarm HI DAY TANK LEVEL P High Day Tank Level Pre-Alarm HI PRESSURE IN 1 P High Pressure Input 1 Pre-Alarm HI PRESSURE IN 2 P High Pressure Input 2 Pre-Alarm HI ECU VOLTS A High ECU Supply Voltage Alarm HI EXHAUST A T P High Exhaust Temp A
Event String Event Description Event Type LOST ECU COMM P Loss of ECU Communication Pre-Alarm LOW BATT VOLT P Low Battery Voltage Pre-Alarm LOW CHARGE AIR PRESS P Low Charge Air Pressure Pre-Alarm LOW COOL LEVEL A Low Coolant Level Alarm LOW COOL LEVEL P Low Coolant Level Pre-Alarm LOW COOL TMP A Low Coolant Temperature Alarm LOW COOL TMP P Low Coolant Temperature Pre-Alarm LOW COOLANT LEVEL P Low Coolant Level Pre-Alarm LOW FUEL DELIV PRESS P Low Fuel Delivery Pressure Pre-Alar
Event String Event Description Event Type RTD_IN_X_O2 A (X = 1 to 8) User Configurable Analog Input X Over 1 (X = 1 to 8) Alarm RTD_IN_X_O2 P (X = 1 to 8) User Configurable Analog Input X Over 1 (X = 1 to 8) Pre-Alarm RTD_IN_X_OOR (X = 1 to 8) User Configurable RTD Input X Out of Range (X = 1 to 8) Status RTD_IN_X_OOR A (X = 1 to 8) User Configurable Analog Input X Out of Range (X = 1 to 8) Alarm RTD_IN_X_OOR P (X = 1 to 8) User Configurable Analog Input X Out of Range (X = 1 to 8) Pre-Alar
This page intentionally left blank.
SECTION 4 BESTCOMSPlus SOFTWARE TABLE OF CONTENTS TTSECTION 4 BESTCOMSPlus SOFTWARE....................................................................................... 4-1 INTRODUCTION.................................................................................................................................... 4-1 INSTALLATION...................................................................................................................................... 4-1 Installing BESTCOMSPlus .........
Frequency Protection (81O/U) ......................................................................................................... 4-47 Reverse Power Protection (32) ........................................................................................................ 4-48 Loss of Excitation Protection (40Q).................................................................................................. 4-48 Overcurrent Protection (51-1, 51-2, 51-3) ...................................................
Figure 4-17. ECU Setup .......................................................................................................................... 4-18 Figure 4-18. Modem Setup...................................................................................................................... 4-20 Figure 4-19. RS-485 Setup...................................................................................................................... 4-21 Figure 4-20. System Settings ...................................
Figure 4-78. Metering, Inputs, Remote Thermocouple Inputs................................................................. 4-78 Figure 4-79. Metering, Inputs, Remote Analog Input Values .................................................................. 4-79 Figure 4-80. Analog Input Temperature Calibration ................................................................................ 4-79 Figure 4-81. Metering, Outputs, Contact Outputs ......................................................................
SECTION 4 BESTCOMSPlus SOFTWARE INTRODUCTION BESTCOMSPlus is a Windows®-based, PC application that provides a user-friendly, graphical user interface (GUI) for use with Basler Electric communicating products. The name BESTCOMSPlus is an acronym that stands for Basler Electric Software Tool for Communications, Operations, Maintenance, and Settings. BESTCOMSPlus provides the user with a point-and-click means to set and monitor the DGC-2020.
Table 4-1. System Requirements for BESTCOMSPlus and the .NET Framework Component Requirement Processor 400 MHz RAM 128 MB Hard Drive 25 MB (if .NET Framework is already installed on PC.) 250 MB (if .NET Framework is not already installed on PC.) In order to install and run BESTCOMSPlus, a Windows user must have administrator rights. A Windows user with limited rights may not be permitted to save files in certain folders.
The BESTCOMSPlus splash screen is shown for a brief time. See Figure 4-3. Figure 4-3. Splash Screen The BESTCOMSPlus platform window opens. If a DGC-2020 is connected, select New Connection from the Communication pull-down menu and select DGC-2020. See Figure 4-4. The DGC-2020 plug-in is automatically activated after connecting to a DGC-2020. Figure 4-4. Communication Pull-Down Menu If a DGC-2020 is not connected, select New from the File pull-down and select DGC-2020.
Click on the Activate button when you are ready to enter the activation key you received from Basler Electric. The Device Needs Activated pop-up will appear. Refer to Figure 4-5. Entering an Activation Key Select the device from the Device pull-down menu. Enter your Email Address and Activation Key provided by Basler Electric. If you received an email containing the Activation Key, you can select all of the text in the email and copy it to the Windows clipboard using normal Windows techniques.
Figure 4-7. DGC-2020 Connection USB Communication If connecting to the DGC-2020 through a USB cable, select USB via Serial RS232, USB, and enter COM Port. The USB drivers are installed automatically during the BESTCOMSPlus installation process. To select the correct COM Port, open Windows Device Manager and expand the Ports (COM & LPT) branch. Locate the device named CP2101 USB to UART Bridge Controller (COMx). The COM Port number will be displayed in parenthesis (COMx).
Modem Communication If connecting to the DGC-2020 through a telephone line, select USB via Serial RS232, Modem, and enter Phone Number. To select the correct COM Port, open Windows Device Manager and expand the Modems branch. Right-click on the modem name and choose Properties. Open the Advanced tab to view the COM port. Ethernet Communication Communication with the DGC-2020 can be made through an optional LSM-2020 (Load Share Module).
10.0.0.0 - 10.255.255.255 172.16.0.0 - 172.31.255.255 192.168.0.0 - 192.168.255.255 If the LSM-2020 is operating on an isolated network, the Subnet Mask may be left at 0.0.0.0 and the Default Gateway can be chosen as any valid IP address from the same range as the LSM-2020 IP address. 3. Click the Send to Device button located on the Configure Ethernet Port screen. A confirmation popup will be displayed notifying the user that the LSM-2020 will reboot after settings are sent.
Figure 4-10. Processing, Please Wait… MENU BARS The menu bars are located near the top of the BESTCOMSPlus screen (see Figure 4-1). The upper menu bar has five pull down menus. With the upper menu bar, it is possible to manage settings files, setup communications, upload and download settings/security files, and compare settings files. The lower menu bar consists of clickable icons.
Help About ............................................................. View general, detailed build, and system information Lower Menu Bar (DGC-2020 Plug-In) View This clickable icon allows you to view the Metering Panel, Settings Panel, or Show Settings Information. Open File This clickable icon is used to open a saved settings file. Connect/Disconnect When clicked, the DGC-2020 Connection screen opens allowing the user to connect via USB or a modem.
GENERAL SETTINGS General DGC-2020 settings consist of settings controlling the HMI display and indicators. Additional general settings include style number configuration, DGC-2020 identification, DGC-2020 version information, and device security setup. Front Panel HMI The contrast A of the front panel LCD (liquid crystal display) can be adjusted to suit the viewing angle used or compensate for environmental conditions.
Style Number When a PC operating BESTCOMSPlus is communicating with a DGC-2020, the style number of the DGC-2020 is automatically displayed on the BESTCOMSPlus Style Number tab. When configuring DGC-2020 settings off-line, the style number for the unit to be configured can be entered into BESTCOMSPlus to enable configuration of the required settings. BESTCOMSPlus style number selections and definitions are illustrated in Figure 4-12. Figure 4-12.
When on-line, read-only information includes the application versionY, boot code versionZ, application buildAA, serial numberBB, application part numberCC, and model numberDD. The Refresh buttonEE is used to update the screen after connecting an optional AEM-2020. BESTCOMSPlus device information values and settings are illustrated in Figure 4-13. Figure 4-13.
C Boot Code Version: Read-only value obtained when BESTCOMSPlus is communicating with the DGC2020. D Application Build: Read-only value obtained when BESTCOMSPlus is communicating with the DGC2020. E Serial Number: Read-only value obtained when BESTCOMSPlus is communicating with the DGC2020. F Application Part Number: Read-only value obtained when BESTCOMSPlus is communicating with the DGC-2020. G Model Number: Read-only value obtained when BESTCOMSPlus is communicating with the DGC2020.
OEM Access. This password level allows access to all settings. The default, OEM-access password is OEM. Settings Access. This password level allows all except uploading of firmware and clearing of device event log. The default, settings-access password is SET. Operator Access. The default, operator-access password is OP.
Figure 4-15. Clock Setup A UTC Offset (min): Adjustable from -1,440 to 1,440 minutes in increments of 1. DST Configuration: Disabled, Fixed, or Floating. C Start Day: Fixed DST Configuration Month (January to December), Day of Month (1 to 31 in increments of 1), Hour (0 to 23 in increments of 1), Minute (0 to 59 in increments of 1).
selected, the Fuel Solenoid output will still close during cranking and genset operation to provide a separate indication that the genset is running. For applications where pulsing of the ECU is not desired, this pulsing featureE may be disabled. ECU Limitations For some ECUs, an external source cannot stop the engine without removing power from the ECU. Turning off power to the ECU is the only way to remove fuel from the engine and shut it down.
secondary base speed is 1,800 rpm. The Accelerator Position settingC is expressed as a percentage and tells the Volvo Penta ECU where to set the engine speed (trim) relative to the base speed. The range of the setting is the base speed 120 rpm. A setting of 0% will cause the engine to run at 120 rpm below the base speed, a setting of 50% will cause the engine to run at the base speed, and a setting of 100% will cause the engine to run at 120 rpm above the base speed.
Figure 4-17. ECU Setup A ECU Type: Standard, Volvo Penta, MTU MDEC, MTU ADEC, or MTU ECU7. Speed Select: Primary or Secondary. C Accelerator Position: Adjustable from 0 to 100% in 1% increments. D MDEC Module Type: CAN Module 201, 302, 303, or 304. E Speed Demand Switch: Analog CAN, Up Down ECU, Up Down CAN, Analog ECU, Frequency, No CAN Demand. F Engine RPM: Adjustable from 1,400 to 2,000 in increments of 1. G Overspeed Test: Off or On. H Governor Param Switch Over: Off or On. I Trip Reset: Press to set.
81O Trip Alarm 81U Trip Alarm 27-1 Trip Pre-Alarm 27-2 Trip Pre-Alarm 32 Trip Pre-Alarm 40 Trip Pre-Alarm 47 Trip Pre-Alarm 51-1 Trip Pre-Alarm 51-2 Trip Pre-Alarm 51-3 Trip Pre-Alarm 59-1 Trip Pre-Alarm 59-2 Trip Pre-Alarm 81O Trip Pre-Alarm 81U Trip Pre-Alarm AEM Comm Failure Auto Restart Failure Alarm Auxiliary Input X Closed (X = 1 to 16) AVR Output Limit Battery Charger Fail Status Battery Overvoltage Pre-Alarm CEM Comm Failure Config Element X Status (X = 1
Overspeed Alarm Scheduled Maintenance Pre-Alarm Switch Not in Auto Transfer Fail Alarm Virtual Output X Status (X = 1 to 8) Weak Battery Voltage Pre-Alarm Dial-Out The DGC-2020 uses telelocator alphanumeric protocol (TAP) version 1.7 when communicating with paging companies. This data formatD specifies seven data bits with even parity. If required, eight data bits with no parity may be specified.
Figure 4-19. RS-485 Setup A Baud Rate: A value of 1200, 2400, 4800, or 9600 may be selected. Parity: No Parity, Odd Parity, or Even Parity. C Modbus Address: A value of 1 to 247 may be entered in increments of 1. B SYSTEM PARAMETERS System parameters configure the DGC-2020 for operation with a specific application and are divided into three categories: system, engine cranking, and sensing transformers.
immediately. Furthermore, if an Off Mode Cooldown is in progress and the OFF button is pressed, the unit will immediately shut down. If the unit was in RUN mode when the OFF button was pressed, it remains in RUN for the remainder of the cooldown cycle. If the machine was in the AUTO mode when the OFF button was pressed, it remains in AUTO mode until the cooldown and shutdown cycle are completed, or until the OFF button is pressed a second time forcing the unit to OFF mode.
Single-Phase Override The DGC-2020 will switch to single-phase voltage sensingQ when a contact input (programmed as a single-phase override input) is received. Either A-to-B or A-to-C sensing can be selected. Fuel Level Function This settingR allows the selection of four fuel types: Fuel Lvl, Natural Gas, Liquid Propane, or Disabled.
Figure 4-20. System Settings A Generator Connection: Delta, Wye, 1-Phase A-B, 1-Phase A-C, or Grounded Delta. Genset kW Rating: Adjustable from 5 to 9,999 kW in 1 kW increments. C Rated Volts: Adjustable from 1 to 999 Vac in 1 Vac increments. D Rated Power Factor: Adjustable from –1 to +1 in increments of 0.001. E Speed Signal Source: MPU, Gen Freq, or MPU Freq. F Rated Frequency: 50/60 or 400 Hz. G Rated Engine RPM: Adjustable from 750 to 3,600 rpm in 1 rpm increments.
Contact Expansion Module A J1939 AddressC must be entered when the optional CEM-2020 is enabledD. Select number of CEM2020 outputsE. Analog Expansion Module A J1939 AddressF must be entered when the optional AEM-2020 is enabledG. BESTCOMSPlus system settings (DGC-2020, System Parameters, Remote Module Setup) are illustrated in Figure 4-21. Figure 4-21. Remote Module Setup A LSM J1939 Address: Adjustable from 1 to 253 in increments of 1. Load Share Module: Enable or Disable.
Figure 4-22. Engine Crank Settings A Cranking Style: Cycle or Continuous. Number of Crank Cycles: Adjustable from 1 to 7 cycles in 1 cycle increments. Controllers configured for NFPA compliance have a 1 to 3-cycle range. C Cycle Crank Time: Adjustable over the range of 5 to 15 seconds in 1 second increments. D Continuous Crank Time: Adjustable from 5 to 60 seconds in 1 second increments. Controllers configured for NFPA compliance have a 1 to 45 second range.
Exercise Timer The exercise timer is used to start the genset at a predetermined time and run for the user-defined period. The modeA defines how often the genset will run. If monthly is selected, you must select the day of the monthB to start. If weekly is selected, you must select the day of the weekC to start. Settings for Start HourD and Start MinutesE may also be defined. The Run Period HoursF and MinutesG define how long the genset will run each time.
Bus Transformer Settings Primary and secondary bus transformer ratings are used by the automatic transfer switch function, which monitors a single-phase bus input to detect mains failure. Controllers equipped with an automatic synchronizer (style number xxxxxxxAx) also use the primary and secondary bus transformer ratings. The primary settingD establishes the nominal voltage present at phases A and C of the bus.
Figure 4-26. Contact Inputs Settings A Alarm Configuration: None, Alarm, or Pre-Alarm. Activation Delay: Adjustable from 0 to 300 s in 1 s increments. C Label Text: An alphanumeric character string with a maximum of 16 characters. D Contact Recognition: Always or While Engine Running Only.
Figure 4-27. Programmable Functions Settings A Auto Transfer Switch Input: Select Input (None, 1-16) and Contact Recognition (Always or While Engine Running Only). B Grounded Delta Override: Select Input (None, 1-16) and Contact Recognition (Always or While Engine Running Only). C Battle Override: Select Input (None, 1-16) and Contact Recognition (Always or While Engine Running Only). D Low Line Override: Select Input (None, 1-16) and Contact Recognition (Always or While Engine Running Only).
Figure 4-28. Remote LSM InputsSettings A Input Type: Voltage or Current. Min/Max Input Voltage: Adjustable from 0 to 10 volts in 0.1 V increments. C Min/Max Input Current: Adjustable from 4 to 20 mA in 0.1 mA increments. B Remote Contact Inputs An optional CEM-2020 (Contact Expansion Module) provides 10 contact inputs. Each of the 10 contact inputs can be independently configured to annunciate an alarm or pre-alarmA when the input senses a contact closure.
Select the input typeB and amount of hysteresisC. A user-adjustable arming delayD disables analog input recognition during engine startup. When enabled, an out of range alarmE alerts the user of an open or damaged analog input wire. Ranges must be set for the selected input type. Param MinF correlates to Min Input CurrentG or Min Input VoltageH and Param MaxI correlates to Max Input CurrentJ or Max Input VoltageK.
K Max Input Voltage: Adjustable from 0 to 10 V in 1 V increments. Alarm Configuration: None, Alarm, Pre-Alarm, or Status Only. M Threshold: –9999.0 to +9999.0 in increments of 0.1. N Activation Delay: Adjustable from 0 to 300 s in 1 s increments. L Remote RTD Inputs An optional AEM-2020 (Analog Expansion Module) provides eight RTD inputs. To make identifying the RTD inputs easier, a user-assigned nameA can be given to each input. Select the amount of hysteresisB and RTD typeC.
Remote Thermocouple Inputs An optional AEM-2020 (Analog Expansion Module) provides two thermocouple inputs. To make identifying the thermocouple inputs easier, a user-assigned nameA can be given to each input. Select the amount of hysteresisB. A user-adjustable arming delayC disables thermocouple input recognition during engine startup. Each thermocouple input can be independently configured to annunciate an alarm, pre-alarm, or status onlyD when the thermocouple input signal falls beyond the thresholdE.
Figure 4-33. Contact Outputs Settings A Label Text: An alphanumeric character string with a maximum of 16 characters. Configurable Elements Each of the 8 elements can be independently configured to annunciate an alarm or pre-alarmA. A useradjustable time delayB can be set to delay recognition of an element. By default, all elements are configured so that they do not trigger an alarm or pre-alarm. To make identifying the element easier, each of the elements can be given a user-assigned nameC.
BESTCOMSPlus settings for remote contact inputs (DGC-2020, Programmable Outputs, Remote Contact Outputs) are illustrated in Figure 4-35. Figure 4-35. Remote Contact Outputs Settings A Label Text: An alphanumeric character string with a maximum of 16 characters. Remote Analog Outputs An optional AEM-2020 (Analog Expansion Module) provides four analog outputs. Make a parameter selectionA and select the output typeB.
E Param Min: –9999.0 to +9999.0 in increments of 0.1. Min Output Current: Adjustable from 4 to 20 mA in 0.1 mA increments. G Min Output Voltage: Adjustable from 0 to 10 V in 1 V increments. H Parm Max: –9999.0 to +9999.0 in increments of 0.1. I Max Output Current: Adjustable from 4 to 20 mA in 0.1 mA increments. J Max Output Voltage: Adjustable from 0 to 10 V in 1 V increments.
E Alarm Configuration: None, Alarm, Pre-Alarm, or Status Only. Threshold: -99,999,900 to 99,999,900 in increments of 1. G Activation Delay: Adjustable from 0 to 300 s in 1 s increments. F ALARM CONFIGURATION DGC-2020 alarms and pre-alarms can be used to annunciate system, genset, and engine sender conditions.
down to zero from the threshold time setting. The maintenance interval pre-alarm can be reset through the DGC-2020 front panel or by using BESTCOMSPlus. To reset the maintenance interval pre-alarm through the DGC-2020 front panel, navigate to the SETTINGS->SYSTEM SETTINGS->MAINT RESET screen. Operator, Settings, or OEM access level is required to reset the maintenance interval pre-alarm. If the maintenance interval pre-alarm is not enabled, the MAINT RESET parameter is not visible on the front panel.
GOV Bias Output Limit GOV bias output limit settingsO consist of an enable/disable setting and an activation delay setting. If enabled, a GOV bias output limit pre-alarm is annunciated when the GOV bias output limit has been met and the activation delay has expired. This setting only applies when using the optional LSM-2020. Intergenset Comm Failure Intergenset communication failure pre-alarm settingsP consist of a single enable/disable setting.
Figure 4-38. Pre-Alarms Configuration A High Fuel Level: Enable or Disable, threshold is adjustable from 0 to 150% in 1 % increments. Low Battery Voltage: Enable or Disable, threshold is adjustable from 6 to 12 Vdc (12 Vdc battery) or 12 to 24 Vdc (24 Vdc battery) in 0.1 Vdc increments. Activation delay is adjustable from 1 to 10 s in 1 s increments. C Weak Battery Voltage: Enable or Disable, threshold is adjustable from 4 to 8 Vdc (12 Vdc battery) or 8 to 16 Vdc (24 Vdc battery) in 0.1 Vdc increments.
F Engine kW Overload: Enable or Disable, threshold is adjustable from 95 to 140% of Genset kW Rating in 1% increments. G Low Fuel Level: Enable or Disable, threshold is adjustable from 10 to 100% in 1 % increments. H High Coolant Temp: Enable or Disable, threshold is adjustable from 100 to 280F or 38 to 138C in 1 increments. Activation time delay is fixed at 60 s. I Low Coolant Temp: Enable or Disable, threshold is adjustable from 35 to 150F or 2 to 65C in 1 increments.
Note: ECU Support must be enabled on the Communications, CANbus Setup screen before this alarm can be configured. Figure 4-39. Alarms Configuration A High Coolant Temp: Enable or Disable, threshold is adjustable from 100 to 280F or 38 to 138C in 1 increments. Arming time delay is adjustable from 0 to 150 in 1 s increments. B Low Oil Pressure: Enable or Disable, threshold is adjustable from 3 to 150 psi or 21 to 1,034 kPa in 7 psi or 1 kPa increments.
Figure 4-40. Sender Fail Configuration A Coolant Temp Sender Fail: None, Alarm, or Pre-Alarm, time delay adjustable from 5 to 30 min in 1 min increments. B Oil Pressure Sender Fail: None, Alarm or Pre-Alarm, time delay adjustable from 0 to 300 s in 1 s increments. C Fuel Level Sender Fail: None, Alarm, or Pre-Alarm, time delay adjustable from 0 to 300 s in 1 s increments. D Voltage Sensing Fail: None, Alarm, or Pre-Alarm, time delay adjustable from 0 to 300 s in 1 s increments.
The hysteresis settingD functions as an undervoltage dropout by preventing rapid switching of the pickup output. A frequency-based inhibit settingE prevents a 27 trip from occurring during an undervoltage condition associated with system startup. A low-line scale factor settingF is used to automatically adjust the undervoltage pickup settings in applications that may utilize more than one type of genset connections.
settings. For example, if a scale factor contact input is received by the DGC-2020 and the scale factor setting is 2.000, the pickup setting will be doubled (2.000 PU). The element is disabled when Alarm Configuration is set to “None”. Element status is available in BESTlogic+ Programmable Logic when “Status Only” is selected. BESTCOMSPlus voltage protection settings (DGC-2020, Generator Protection, Voltage, Overvoltage) are illustrated in Figure 4-42. The 59-1 element is shown. Figure 4-42.
A Pickup: Adjustable from 5 to 100 Vac in 1 Vac increments. Activation Delay: Adjustable from 0 to 30 s in 0.1 s increments. C Alarm Configuration: None, Alarm, Pre-Alarm, or Status Only. D Hysteresis: Adjustable from 1 to 5 Vac in 1 Vac increments. B Frequency Protection (81O/U) Two sets of frequency protection settings are provided: one for underfrequency (81U) and one for overfrequency (81O).
H I Overfrequency Alarm Configuration: None, Alarm, Pre-Alarm, or Status Only. Hysteresis: Adjustable from 0.1 to 40 Hz in 0.1 Hz increments. Reverse Power Protection (32) Two sets of reverse power settings are provided: one for three-phase generator connections and one for single-phase generator connections. The pickup setting entered is based on the CT secondary side (DGC-2020).
Figure 4-46. Generator Capability Curve vs. 40Q Response If reactive power is within the 40Q tripping region for the duration of the 40Q activation delay settingB, a loss of excitation condition is annunciated. A loss of excitation annunciation can be user-selected to trigger a pre-alarmC (warning) or alarmC (shutdown). A loss of excitation annunciation can also be userconfigured to close a programmable output.
Overcurrent Protection (51-1, 51-2, 51-3) Two sets of overcurrent settings are provided for each element: one for three-phase generator connections and one for single-phase generator connections. The pickup setting entered is based on the CT secondary side (DGC-2020). When a single-phase override contact input is received by the DGC2020, the overcurrent protection settings automatically switch from the three-phase settings to the singlephase overcurrent protection settings.
Figure 4-48. Overcurrent Protection Settings A Pickup: Adjustable from 0.9 to 7.75 Aac for 5 Aac current sensing (style number 5xxxxxxxx) or 0.18 to 1.18 Aac for 1 Aac current sensing (style number 1xxxxxxxx). B Alarm Configuration: None, Alarm, Pre-Alarm, or Status Only. C Time Dial: Adjustable from 0 to 7,200 s for F (fixed) curve, 0 to 9.9 for all other curve selections. D Curve: A, B, C, D, E1, E2, F, G, I1, I2, L1, L2, M, S1, S2, V1, or V2. E Overcurrent Pickup Curve.
During synchronization of the generator with the bus (Anticipatory mode only), the DGC-2020 uses the breaker closing timeJ to calculate the optimum time to close the breaker. When a close command is issued, the DGC-2020 monitors the breaker status and annunciates a breaker failure if the breaker does not close within the time defined by the breaker-close wait-time delayK. Typically, this parameter is set to be longer than twice the breaker closing time.
E Mains Fail Return Delay: Adjustable from 0 to 1,800 s in 1 s increments. This specifies the delay between detection of restored (stable) mains and initiation of the return from the generator back to the mains. F Mains Fail Max Transfer Time: Adjustable from 10 to 120 s in 1 s increments. This specifies the maximum time that is allowed for a transfer from failed mains to generator power.
Figure 4-50. Bus Condition Detection Settings A Dead Bus Threshold: Adjustable from 0 to 4,800 Vac in 1 Vac increments. Dead Bus Time Delay: Adjustable from 0.1 to 600 s in 0.1 s increments. C Gen and Bus Stable Overvoltage Pickup and Dropout: Adjustable from 10 to 1,200 Vac in 1 Vac increments. D Gen and Bus Stable Undervoltage Pickup and Dropout: Adjustable from 10 to 12,000 Vac in 1 Vac increments. E Gen and Bus Stable Overfrequency Pickup and Dropout: Adjustable from 46 to 64 Hz in 0.
that is required to compensate for the breaker closure time by monitoring the frequency difference between the generator and the bus. BESTCOMSPlus automatic synchronizer settings (DGC-2020, Breaker Management, Synchronizer) are illustrated in Figure 4-51. Frequency Correction Generator frequency correction is defined by the slip frequency setting and further refined by the breaker closing angle setting.
D Breaker Closing Angle: Adjustable from 3 to 20 in 1 increments. If Phase Lock Loop synchronization is selected, this specifies the maximum acceptable slip angle under which a breaker close command can be issued. E Sync Activation Delay: Adjustable from 0.1 to 0.8 seconds in 0.1s increments. F Regulation Offset: Adjustable from 2 to 15% of nominal generator voltage in 0.5% increments. This specifies the voltage acceptance window for the synchronization function. G Vgen>Vbus: Enable or Disable.
droop is also the mode when the generator breaker is closed if kW load sharing is disabled. If it is desired to disable voltage droop, set the droop percentage to 0. The voltage droop gain settingZ determines the gain factor applied to the voltage droop percentage to compensate for governor differences and achieve desired droop performance. In order to test the operation of droop, the unit must be loaded to full load and the resulting generator voltage should be compared to the desired droop.
P PF Setpoint Source: User Setting, LSM Analog Input 1, or Analog Inputs 1-8. PF Setpoint: Adjustable from –0.60 to 0.60 in increments of 0.01. R PF Analog Max: Adjustable from –0.60 to 0.60 in increments of 0.01. S PF Analog Min: Adjustable from –0.60 to 0.60 in increments of 0.01. T Proportional Gain (Kp): Adjustable from 0 to 1,000 in increments of 0.001. U Integral Gain (Ki): Adjustable from 0 to 1,000 in increments of 0.001. V Derivative Gain (Kd): Adjustable from 0 to 1,000 in increments of 0.001.
Expected rpm reduction in droop - (actual load/machine capacity) (droop percentage/100) rated speed. If the actual rpm drop does not match the expected value, calculate the error by dividing the expected drop by the actual drop, and putting the result in as the droop gain. Ramp rateT is defined as the rate, in percentage of machine capacity, at which the machine will ramp up its real power when loading or coming online. The machine also uses this rate to unload prior to cooling down.
P Derivative Filter Constant (Td): Adjustable from 0 to 1 in increments of 0.001. Loop Gain (Kg): Adjustable from 1 to 1,000 in increments of 0.001. R Droop Percentage: Adjustable from 0 to 10 percent in 0.001 % increments. S Speed Droop Gain: Adjustable from 0 to 1,000 in increments of 0.001. T Ramp Rate: Adjustable from 0 to 100 percent/second in 0.1 %/s increments. U Base Load Level Source: User Setting, LSM Analog Input 1, or Analog Inputs 1-8.
Figure 4-55. Governor Output Settings A Output Type: Voltage or Current. Response: Increasing or Decreasing. C Min Output Current: Adjustable from 4 to 20 mA in 0.1 mA increments. D Max Output Current: Adjustable from 4 to 20 mA in 0.1 mA increments. E Min Output Voltage: Adjustable from –10 to +10 V in 0.1 V increments. F Max Output Voltage: Adjustable from –10 to +10 V in 0.1 V increments.
Figure 4-57. Demand Start/Stop A Demand Start Stop Enable: Enable or Disable. Delayed Start Level: Adjustable from 0 to 1 in increments of 0.001. C Start Level Timeout: Adjustable from 0 to 600 seconds in 0.1 s increments. D Delayed Stop Level: Adjustable from 0 to 1 in increments of 0.001. E Stop Timeout: Adjustable from 0 to 600 seconds in 0.1 s increments.
Balanced Service Time If this mode is selected, units will seek to sort the start priority of all non-disabled networked units in ascending order of service hours remaining. In this configuration, a network of units will respond to a demand start request by starting the unit with the greatest number of service hours remaining first. In the event that two or more units have matching service hours remaining, the unit with the lowest sequencing ID is assigned highest start priority.
BESTCOMSPlus network configuration settings Configuration) are illustrated in Figure 4-59. (DGC-2020, Multigen Management, Network Figure 4-59. Network Configuration Settings A Expected Seq Id: Adjustable from 0 to 255. PROGRAMMABLE SENDERS The sender inputs of the DGC-2020 can be customized to obtain maximum accuracy from the coolant temperature, oil pressure, and fuel level senders. The characteristic curve of each sender input can be configured with up to 11 pointsA.
Figure 4-60. Programmable Senders Settings A Sender Points: Accepts up to 11 user-defined sender resistance points. Sender Slope: Positive or Negative causes sender points to be sorted and displayed accordingly. C Sender Point Curve: Automatic plot of sender points data. D Print This Graph: Click to print sender point curve. E Save Cool. Data: Click to save file containing sender point data. F Load Cool. Settings File: Click to clear all user-defined sender data and revert to the factory-default values.
Opening a Settings File To open a new instance of a settings file into BESTCOMSPlus, pull down the File menu and choose Open. The Open dialog box appears. This dialog box allows you to use normal Windows techniques to select the file that you want to open. Select the file and open it and the file settings have been brought into a new instance in BESTCOMSPlus. You may also open a file, by clicking on the Open File icon on the lower menu bar.
A dialog box will appear and notify you if any differences were found. The BESTCOMSPlus Settings Compare dialog box (Figure 4-62) is displayed where you can view all settings (Show All Settings), view only the differences (Show Settings Differences), view all logic (Show All Logic Paths), or view only logic differences (Show Logic Path Differences). Select Close when finished. Figure 4-62.
CAUTION The order in which the components are upgraded is critical. Assuming a system of a DGC-2020 and expansion modules is in a state where the DGC-2020 is communicating with all of the system expansion modules, the expansion modules must be upgraded before the DGC-2020. This is required because the DGC-2020 must be able to communicate to the expansion module before the DGC-2020 can send firmware to it.
8. Click on the Upload button and the Proceed with Device Upload screen will appear. Select Yes or No. 9. After selecting Yes, the DGC-2020 Selection screen will appear. Select the communication port to begin upload. Firmware updating is only possible locally through the USB port. Refer to Figure 4-64. Figure 4-64. DGC-2020 Selection 10. The Processing, Please Wait… screen is displayed as file(s) are uploaded. See Figure 4-65. Figure 4-65. Processing, Please Wait… 11.
f. Click the Upload button and follow the instructions that appear to begin the upgrade process. g. After the upload is complete, disconnect communication to the DGC-2020. NOTE If the front panel HMI becomes blank and all LEDs are flashing, cycle power to the DGC-2020 and restart the upgrade procedure starting with step A.1.c. You will not be asked to save settings this time. 2. Modify the Application Version in the desired settings file to be compatible with the DGC-2020 Application Version. a.
5. Load the new settings file into the DGC-2020. a. Disconnect communication from the DGC-2020. b. Close all settings files. c. From the File pull-down menu, select New, DGC-2020. d. Connect to the DGC-2020. e. Once all settings have been read from the DGC-2020, open the new settings file by selecting the file with File, Open File in the BESTCOMSPlus menu. f. When BESTCOMSPlus asks if you wish to upload settings and logic to the device, click Yes. g.
METERING EXPLORER The Metering Explorer is a convenient tool within BESTCOMSPlus used to navigate through the following metering screens of the DGC-2020 plug-in.
B A C E P0042-15 09-20-06 D Figure 4-66. Metering, Docking Options Table 4-2. Explanation of Call-Outs on Figure 4-66 CallOut Symbol Explanation A Holding the left mouse button down on a metering tab and dragging it to one of the four arrow boxes will place it inside the selected window on the location selected. To place the metering tab as a tab inside the selected window, drop it on the tabs button in the center of the arrow buttons.
Engine This screen provides information and metering of engine components. Refer to Figure 4-67. Figure 4-67. Metering, Engine Generator This screen provides metering of generator voltages and currents. Refer to Figure 4-68. Figure 4-68. Metering, Generator Power This screen provides metering of generator power and power factor. Refer to Figure 4-69. 4-74 Figure 4-69.
Bias Control This screen provides Var/PF mode status and operating levels. Refer to Figure 4-70. Figure 4-70. Metering, Bias Control Run Statistics This screen provides Cumulative Run Statistics, Session Run Statistics, and Commission Date. Refer to Figure 4-71. The maintenance interval can be reset through this screen. Figure 4-71. Metering, Run Statistics Status This screen indicates status of breakers, modes, and switches. The status is TRUE when the corresponding LED is red. Refer to Figure 4-72.
Figure 4-72. Metering, Status Inputs Contact Inputs This screen indicates the status of contact inputs, contact input alarms, and contact input pre-alarms. The status is TRUE when the corresponding LED is red. Refer to Figure 4-73. Figure 4-73.
Remote LSM Inputs When an optional LSM-2020 (Load Share Module) is connected, the value of the analog inputs is displayed on this screen. Voltage is displayed when the input is configured for voltage and current is displayed when the input is configured for current. Refer to Figure 4-74. Figure 4-74.
Remote RTD Inputs When an optional AEM-2020 (Analog Expansion Module) is connected, the status of the remote RTD inputs, remote RTD input alarms, and remote RTD input pre-alarms are shown on this screen. The status is TRUE when the corresponding LED is red. Refer to Figure 4-77. Remote RTD Input #1 is shown. Figure 4-77.
Figure 4-79. Metering, Inputs, Remote Analog Input Values The Calibrate button shown in Figure 4-79 opens the Analog Input Temperature Calibration screen shown in Figure 4-80. This screen is used to calibrate RTD inputs 1 through 8 and thermocouple inputs 1 and 2. Figure 4-80.
Outputs Contact Outputs This screen indicates the status of contact outputs. The status is TRUE when the corresponding LED is green. Refer to Figure 4-81. Figure 4-81. Metering, Outputs, Contact Outputs Configurable Elements This screen indicates the status of configurable elements. It also indicates alarms and pre-alarms of configurable elements. The status is TRUE when the corresponding LED is green. Refer to Figure 4-82. Figure 4-82.
Figure 4-83. Metering, Outputs, Remote Contact Outputs Remote Analog Outputs When an optional AEM-2020 (Analog Expansion Module) is connected, the status of the remote analog outputs, scaled analog output values, and raw analog output values are shown on this screen. The status is TRUE when the corresponding LED is red. Refer to Figure 4-84. Figure 4-84. Metering, Outputs, Remote Analog Outputs Alarms This screen indicates the status of Alarms, Pre-Alarms, Sender Fail, and Generator Protection.
Figure 4-85. Metering, Alarms Event Log The event log provides a historical record of event occurrences detected by the DGC-2020. It is saved in nonvolatile memory so that is will not be affected if power is removed. Thirty event records are retained and each record contains a time stamp of the first and last event occurrence, and the number of occurrences for each event. In addition, each record contains details of the time, date, and engine hours for the most recent 30 occurrences of the event.
Figure 4-86. Metering, Event Log, Sorted by Date When viewed with BESTCOMSPlus, the event log can be sorted by Event ID, Description, Occurrence, Date, or Engine Hours. Selecting event log sorted by Date yields a list of all event occurrences in sequential order. This is a view that one would see in a typical “sequence of events” type of event log. Figure 4-86 shows the sequential list resulting from sorting by Date.
Figure 4-88. Metering, ECU Data Engine Configuration This screen displays Engine Configuration. Refer to Figure 4-89. Figure 4-89. Metering, Engine Configuration Active DTC and Previously Active DTC This screen is used for viewing, downloading, and clearing DTC (Diagnostic Trouble Codes). Refer to Figure 4-90.
Figure 4-90. Metering, Download DTC MTU The MTU reports operating information to the DGC-2020 through the CANbus interface when the ECU is configured for MTU. Operating parameters and diagnostic information, if supported by the MTU, are decoded and displayed on these screens. MTU Alarms MTU Alarms and MTU Pre-Alarms are reported on this screen. The status is TRUE when the corresponding LED is red. Refer to Figure 4-91. Figure 4-91.
MTU Status MTU Status is reported on this screen. The status is TRUE when the corresponding LED is red. Refer to Figure 4-93. Figure 4-93. Metering, MTU Status MTU Engine Status MTU Engine Status is reported on this screen. The status is TRUE when the corresponding LED is red. Refer to Figure 4-95. Figure 4-94.
Summary This screen displays a metering summary. Refer to Figure 4-95. Figure 4-95.
Control Controls for stopping/starting the engine, controls for opening/closing breakers, and controls for opening/closing switches are accessed through the Control branch. The following controls are available by using the Metering Explorer in BESTCOMSPlus to open the Control branch. Refer to Figure 4-96. A. The user has control to stop the generator in case of emergency by clicking on the Emergency Stop button. B. The engine can be started and stopped by clicking on the Start and Stop buttons. C.
Generator Network Status This screen (Figure 4-98) displays the detected sequencing IDs of the LSM-2020’s on the network. This can only be accomplished when an optional LSM-2020 (Load Share Module) is connected to the DGC2020 and actively communicating to the generator network. The Options button is used to copy or save the list of sequencing IDs. The Download button refreshes the list of sequencing IDs. Figure 4-98.
This page intentionally left blank.
SECTION 5 BESTlogic+ PROGRAMMABLE LOGIC TABLE OF CONTENTS SECTION 5 BESTlogic+ PROGRAMMABLE LOGIC............................................................................. 5-1 INTRODUCTION.................................................................................................................................... 5-1 OVERVIEW OF BESTlogic+.................................................................................................................. 5-1 BESTlogic+ Composition ................
This page intentionally left blank.
SECTION 5 BESTlogic+ PROGRAMMABLE LOGIC INTRODUCTION BESTlogic+ Programmable Logic is a programming method used for managing the input, output, protection, control, monitoring, and reporting capabilities of Basler Electric's DGC-2020 Digital Genset Controller. Each DGC-2020 has multiple, self-contained logic blocks that have all of the inputs and outputs of its discrete component counterpart.
BESTlogic+ Composition There are three main groups of objects used for programming BESTlogic+. These groups are I/O, Components, and Elements. For details on how these objects are used to program BESTlogic+, see the paragraphs on Programming BESTlogic+. I/O This group contains Input Objects, Output Objects, Alarms, Pre-Alarms, and Senders. Table 5-1 lists the names and descriptions of the objects in the I/O group. Table 5-1.
Name Description Status Input Auto Restart TRUE when the Automatic Restart function is active. Status Input Battery Charger Fail TRUE when the Battery Charger Fail input is TRUE. Status Input Battle Override TRUE when the Battle Override input is TRUE. Status Input Bus Dead TRUE when the Bus Dead condition settings have been exceeded. Status Input Bus Fail TRUE when the Bus Fail condition settings have been exceeded.
Name Description Status Input Front Panel Buttons TRUE while the EDIT front panel button is pressed. Status Input Front Panel Buttons TRUE while the LAMP TEST front panel button is pressed. Status Input Front Panel Buttons TRUE while the LEFT front panel button is pressed. Status Input Front Panel Buttons TRUE while the OFF front panel button is pressed. Status Input Front Panel Buttons TRUE while the RESET front panel button is pressed.
Name Description Symbol Status Input Load Share Module Load Share Module Connected. TRUE when an optional LSM-2020 is connected to the DGC-2020. Status Input Load Share Module Load Share Module Governor Output Limit. TRUE when the LSM-2020 Governor Output Limit settings have been exceeded. Status Input Low Line Override TRUE when the Low Line Override input is TRUE. Status Input Off Mode TRUE when the DGC-2020 is in Off Mode. Status Input PF Mode Active TRUE when PF mode is active.
Name Description Symbol Alarms Analog Expansion Module Remote Analog Inputs 1-8 TRUE when Over 1, Over 2, Under 1, Under 2, or Out of Range is configured as an Alarm and the threshold has been exceeded. (Over 1 shown.) Analog Expansion Module Remote Analog Outputs 1-4 TRUE when the analog output connection is open and the Out of Range Alarm Configuration is set to Alarm.
Name Description Symbol Hi Coolant Temp TRUE when the High Coolant Temp Alarm settings have been exceeded. Low Coolant Level TRUE when the Low Coolant Level function is configured as an Alarm and the activation delay has expired. In addition, TRUE when CANbus is enabled and the Low Coolant Level Alarm threshold has been exceeded. Low Fuel Level TRUE when the Low Fuel Level Alarm settings have been exceeded. Low Oil Pressure TRUE when the Low Oil Pressure Alarm settings have been exceeded.
Name Description Battery Charger Fail TRUE when the Battery Charger Fail function is configured as a Pre-Alarm and the activation delay has expired. Battery Overvoltage TRUE when the Battery Overvoltage Pre-Alarm threshold has been exceeded. Checksum Failure TRUE when some of the user settings or firmware code has been corrupted. Refer to Section 4, BESTCOMSPlus Software, Alarm Configuration, Pre-Alarms, for more details.
Name Description Hi Coolant Temp TRUE when the High Coolant Temp Pre-Alarm threshold has been exceeded. High Fuel Level TRUE when the High Fuel Level Pre-Alarm settings have been exceeded. Intergenset Comm Fail TRUE when an individual generator detects that it had been connected to a generator network, but has lost the connection. Load Share Module Load Share Module Comm Fail TRUE when communication from the LSM-2020 to the DGC-2020 has been lost.
Name Description Symbol Senders Coolant Temp Sender Fail TRUE when the Coolant Temp Sender Fail is configured as either a Pre-Alarm or Alarm and the activation delay has expired. Fuel Level Sender Fail TRUE when the Fuel Level Sender Fail is configured as either a Pre-Alarm or Alarm and the activation delay has expired. Oil Pressure Sender Fail TRUE when the Oil Pressure Sender Fail is configured as either a Pre-Alarm or Alarm and the activation delay has expired.
Name Description XOR Input 0 0 0 1 1 0 1 1 Output 0 1 1 0 XNOR Input 0 0 0 1 1 0 1 1 Output 1 0 0 1 NOT (INVERTER) Input 0 1 Output 1 0 Symbol Pickup and Dropout Timers Drop Out Timer Used to set a delay in the logic. Pickup Up Timer Used to set a delay in the logic. Latches Reset Priority Latch A positive going edge on the Set input sets the latch, as long as the Reset input is false. A positive edge on the Reset input will clear the latch.
Table 5-3. Elements Group, Names and Descriptions Name Description Symbol Protection 27-1TRIP TRUE when the 27-1 undervoltage is in a TRIP condition. Connect to another logic block input. 27-2TRIP TRUE when the 27-2 undervoltage is in a TRIP condition. Connect to another logic block input. 32TRIP TRUE when the 32 reverse power is in a TRIP condition. Connect to another logic block input. 40TRIP TRUE when the 40Q loss of excitation is in a TRIP condition. Connect to another logic block input.
Name Description Symbol Other ATS When this logic element is TRUE, and the DGC-2020 is in AUTO mode, the generator will run. This can be used in place of the ATS programmable function if it is desired to generate the ATS signal as a combination of programmable logic rather than a simple contact input. If either the ATS logic element is TRUE or the contact mapped to the ATS programmable function is TRUE, and the DGC is in AUTO mode, the generator will run.
Name Description COOLDOWNREQ RUN Mode Symbol If the unit is in RUN mode when the Cool Down Request is received, the unit is forced to unload and open its breaker and then go into a cooldown cycle. While in the cool down cycle, the unit will display “COOLDOWN REQ” in addition to displaying the cooldown timer. After the cooldown timer expires, the unit will remain running in RUN mode. The Cool Down Request must be removed before the breaker can be closed again; this element blocks breaker closures.
Name Description GENBRK This element is used to connect the breaker open and close output signals from the DGC-2020 to physical output contacts to open and close the generator breaker, and map breaker status feedback to a contact input. In addition, contact inputs can be mapped to allow switches to be implemented to manually initiate breaker open and close requests. Inputs Status: This input allows a contact input to be mapped that will provide breaker status feedback to the DGC-2020.
Name Description MAINSBRK This element is used to connect the breaker open and close output signals from the DGC-2020 to physical output contacts to open and close the mains breaker and map breaker status feedback to a contact input. In addition, contact inputs can be mapped to allow switches to be implemented to manually initiate breaker open and close requests.
Name Description PARTOMAINS Setting this logic element to TRUE indicates to the DGC-2020 that it is paralleled to a utility. When paralleled to the utility, the Kw controller will regulate the machine’s KW output at the Base Load Level (%) that is set on the Governor Bias Control Settings screen, where the Base Load Level is in percent of machines rated KW. Otherwise, the KW controller will implement KW load sharing when part of a load sharing system.
Name Description Symbol STARTOUTPUT This element is used to drive the start output relay from logic when the Start Output Relay configuration is set to “Programmable”. When the Start Output Relay configuration is set to “Programmable”, the start relay will not close unless logic is used to drive this element. When the Start Output Relay configuration is set to “Predefined”, the start relay is closed according to the predefined start functionality of the DGC-2020.
CAUTION Modifying a logic scheme in BESTCOMSPlus does not automatically make that scheme active in the DGC-2020. The modified scheme must be uploaded into the DGC-2020. See the paragraphs on Sending and Retrieving Logic Schemes later in this section. PROGRAMMING BESTlogic+ BESTCOMSPlus is used to program BESTlogic+. Using BESTCOMSPlus is analogous to physically attaching wire between discrete DGC-2020 terminals.
Pickup and Dropout Timers A pickup timer produces a TRUE output when the elapsed time is greater than or equal to the Pickup Time setting after a FALSE to TRUE transition occurs on the Initiate input from the connected logic. Whenever the Initiate input status transitions to FALSE, the output transitions to FALSE immediately.
Opening a BESTlogic+ File To open a saved BESTlogic+ file, click on the Logic Library drop-down button on the BESTlogic+ Programmable Logic toolbar and select Open Logic Library File. Use normal windows techniques to browse to the folder where the file is located. Protecting a BESTlogic+ File Objects in a logic diagram can be locked so that when the logic document is protected these objects cannot be changed. Locking and protecting is useful when sending logic files to other personnel to be modified.
Example 2 - AND Gate Connections Figure 5-5 illustrates a typical AND gate connection. In this example, Output 11 will become active when the Low Fuel alarm AND the Low Oil Pressure alarm are TRUE. Figure 5-5. Example 2 - AND Gate Connections Example 3 - Multiple Logic Connections In this example, there are two comment boxes, which may be placed on the logic diagram. Double-click a comment box to modify the inside text. Output 5 will become TRUE when the 27TRIP is TRUE.
SECTION 6 INSTALLATION TABLE OF CONTENTS SECTION 6 INSTALLATION .................................................................................................................. 6-1 GENERAL .............................................................................................................................................. 6-1 PRODUCT REGISTRATION ................................................................................................................. 6-1 HARDWARE ......................
Figure 6-16. Single-Phase A-B Connections for MTU MDEC ECU Applications.................................... 6-22 Figure 6-17. Single-Phase A-C Connections for MTU MDEC ECU Applications.................................... 6-23 Figure 6-18. DGC-2020, AEM-2020, CEM-2020, LSM-2020 CANbus Connections .............................. 6-24 Tables Table 6-1. Operating Power Terminals...................................................................................................... 6-3 Table 6-2.
SECTION 6 INSTALLATION GENERAL DGC-2020 controllers are delivered in sturdy cartons to prevent shipping damage. Upon receipt of a system, check the part number against the requisition and packing list for agreement. Inspect for damage, and if there is evidence of such, immediately file a claim with the carrier and notify the Basler Electric regional sales office, your sales representative, or a sales representative at Basler Electric, Highland, Illinois USA.
Figure 6-2.
CONNECTIONS DGC-2020 connections are dependent on the application. Incorrect wiring may result in damage to the controller. NOTE Be sure that the DGC-2020 is hard-wired to earth ground with no smaller than 12 AWG copper wire attached to the chassis ground terminal (terminal 1) on the rear of the controller. Operating power from the battery must be of the correct polarity. Although reverse polarity will not cause damage, the DGC-2020 will not operate.
Table 6-2. Generator Current Sensing Terminals Terminal Description 68 (IA–) A-phase current sensing input 69 (IA+) 71 (IB–) B-phase current sensing input 72 (IB+) 74 (IC–) C-phase current sensing input 75 (IC+) NOTE Unused current sensing inputs should be shorted to minimize noise pickup. Generator Voltage Sensing The DGC-2020 accepts either line-to-line or line-to-neutral generator sensing voltage over the range of 12 to 576 volts, rms line-to-line.
Table 6-5. Sender Input Terminals Terminal Description 8 (OIL) Oil pressure sender input 9 (FUEL) Fuel level sender input 10 (COOLANT) Coolant temperature sender input 11 (SENDER COM) Sender return terminal Emergency Stop Input The emergency stop input is intended for use with a normally closed switch and recognizes an emergency stop input when the short-circuit across the input is removed. The ESTOP can be up to 75 ft away from the DGC-2020 using a maximum wire length of 150 ft.
Magnetic Pickup Input The magnetic pickup input accepts a speed signal over the range of 3 to 35 volts peak and 32 to 10,000 hertz. Magnetic pickup input terminals are listed in Table 6-7. Table 6-7. Magnetic Pickup Input Terminals Terminal Description 31 (MPU+) Magnetic pickup positive input 32 (MPU–) Magnetic pickup return input Contact Sensing Inputs Contact sensing inputs consist of 1 emergency stop input and 16 programmable inputs. The programmable inputs accept normally open, dry contacts.
Table 6-9.
NOTES 1.) If the DGC-2020 is providing one end of the J1939 bus, a 120 terminating resistor should be installed across terminals 48 (CANL) and 49 (CANH). 2.) If the DGC-2020 is not part of the J1939 bus, the stub connecting the DGC2020 to the bus should not exceed 914 mm (3 ft) in length. 3.) The maximum bus length, not including stubs, is 40 m (131 ft). 4.) The J1939 drain (shield) should be grounded at one point only. If grounded elsewhere, do not connect the drain to the DGC-2020.
Dial-Out Modem DGC-2020 controllers with style number xxxxxMxxx have an internal modem with dial-in, dial-out capability. The DGC-2020 connects to a standard-device telephone line through a USOC RJ-11C jack. RDP-110 Connections Terminals are provided for connection with the optional RDP-110 remote display panel. These terminals provide dc operating power to the RDP-110 and enable communication between the DGC-2020 and RDP-110.
3-Phase Wye Connections for Typical Applications Figure 6-6.
3-Phase Delta Connections for Typical Applications Figure 6-7.
Single-Phase A-B Connections for Typical Applications Figure 6-8.
Single-Phase A-C Connections for Typical Applications Figure 6-9.
Connections for Volvo Penta EDC III Applications Engines equipped with Volvo Penta EDC III controllers can receive engine control commands (such as start and stop) from the DGC-2020 through the SAE J1939 communication interface. To invoke this feature, the EDC III must receive a J1939 message containing engine control information within one second of waking (exiting sleep mode).
3-Phase Wye Connections for Volvo Penta EDC III Applications Figure 6-10.
3-Phase Delta Connections for Volvo Penta EDC III Applications Figure 6-11.
Single-Phase A-B Connections for Volvo Penta EDC III Applications Figure 6-12.
Single-Phase A-C Connections for Volvo Penta EDC III Applications Figure 6-13.
Connections for MTU MDEC ECU Applications MTU MDEC ECUs, supplied on some Detroit Diesel engines, can receive engine control commands from the DGC-2020 and transmit engine operating status information to the DGC-2020 through the SAE J1939 communication interface. In order for the DGC-2020 to communicate with the MTU MDEC ECU, ECU support must be enabled on the CANbus Setup screen of BESTCOMSPlus and “MTU MDEC” must be selected as the engine configuration.
3-Phase Wye Connections for MTU MDEC ECU Applications Figure 6-14.
3-Phase Delta Connections for MTU MDEC ECU Applications Figure 6-15.
Single-Phase A-B Connections for MTU MDEC ECU Applications Figure 6-16.
Single-Phase A-C Connections for MTU MDEC ECU Applications Figure 6-17.
Connections with AEM-2020, CEM-2020, and LSM-2020 The AEM-2020 (Analog Expansion Module), CEM-2020 (Contact Expansion Module), and LSM-2020 (Load Share Module) are optional modules that may be installed with the DGC-2020. These modules interface to the DGC-2020 via CANbus, thus the CANBUS terminals are the only common connections (Figure 6-18) between the DGC-2020, AEM-2020, CEM-2020, and LSM-2020. Refer to Section 8, LSM2020 (Load Share Module), for independent LSM-2020 connections.
SECTION 7 MAINTENANCE AND TROUBLESHOOTING TABLE OF CONTENTS SECTION 7 MAINTENANCE AND TROUBLESHOOTING.................................................................... 7-1 MAINTENANCE ..................................................................................................................................... 7-1 Backup Battery for the Real Time Clock ............................................................................................ 7-1 TROUBLESHOOTING.................................
This page intentionally left blank.
SECTION 7 MAINTENANCE AND TROUBLESHOOTING MAINTENANCE Preventative maintenance consists of periodic replacement of the backup battery (optional) and periodically checking that the connections between the DGC-2020 and the system are clean and tight. DGC-2020 units are manufactured using state-of-the-art, surface-mount technology. As such, Basler Electric recommends that no repair procedures be attempted by anyone other than Basler Electric personnel.
Step 3. Verify that all Ethernet devices comply with IEC 61000-4 series of specifications for Industrial Ethernet Devices. Commercial devices are not recommended and may result in erratic network communications. USB Port Does Not Operate Properly Step 1. Verify that the proper port of your computer is being used. For more information, refer to Section 4, BESTCOMSPlus Software, Communication.
Step 2. Ensure that the proper current is present at the DGC-2020 current sensing inputs (68/69, 71/72, and 74/75. Step 3. Verify that the current sensing transformer ratios are correct. Step 4. Confirm that the current sensing transformers are correct and properly installed. Incorrect Display of Engine RPM Step 1. Verify that all wiring is properly connected. Refer to Section 6, Installation, Connections. Step 2. Verify that the flywheel teeth setting is correct. Step 3.
the logic output that would normally be the breaker close output. Map another virtual switch to the logic output that would normally be the breaker close output. Connect with BESTCOMSPlus, and exercise the virtual switches using the Control panel located in the Metering Explorer. Never turn open and close on at the same time. This could damage the breaker and/or motor operator. If everything is working as expected, restore the logic to its original diagram.
Synchronizer Determining if the Synchronizer is Active Step 1: Disable the speed trim function. Step 2: Initiate a breaker close request by one of the methods listed in Section 3, Functional Description, Breaker Management. Step 3: Check for raise and/or lower pulses coming from the DGC-2020 if the governor or AVR bias control output type is contact.
If the speed still does not change when varying the bias: Verify that the governor or ECU is equipped and configured to accept bias inputs. Check connections to verify the wiring to the governor bias is correct. If you have an engine with an ECU, check ECU programming to verify it is set up to accept a speed bias input. Engine Speed Decreases When Speed Bias is Increased Step 1: Navigate to the SETTINGS->MULTIGEN MANAGEMENT->GOV ANALOG OUTPUT screen and set SPD RESPONSE to DECREASING.
SECTION 8 LSM-2020 (LOAD SHARE MODULE) TABLE OF CONTENTS TTSECTION 8 LSM-2020 (LOAD SHARE MODULE)............................................................................ 8-1 GENERAL INFORMATION.................................................................................................................... 8-1 FEATURES ............................................................................................................................................ 8-1 SPECIFICATIONS .....................
Figures UUFigure 8-1. Device Info Screen............................................................................................................. 8-5 Figure 8-2. Device Security Setup Screen ................................................................................................ 8-6 Figure 8-3. LSM-2020 Overall Dimensions ............................................................................................... 8-7 Figure 8-4. CANbus Interface with LSM-2020 providing One End of the Bus ....
SECTION 8 LSM-2020 (LOAD SHARE MODULE) GENERAL INFORMATION The LSM-2020 is a remote auxiliary device that interfaces to the DGC-2020 and provides analog outputs to the power system in the form of analog bias signals to the voltage regulator and speed governor. When the breaker is closed and Load Sharing is enabled, the LSM-2020 will share real power load proportionally with the other generators on the Analog Load Share Line.
Communication Interface CANbus Differential Bus Voltage: Maximum Voltage: Communication Rate: Terminals: 1.5 to 3 Vdc –32 to +32 Vdc with respect to negative battery terminal 250 kb/s P2-12 (low), P2-11 (high), and P2-10 (shield) Ethernet Rear-panel RJ-45 connector provides remote communications via BESTCOMSPlus to the LSM-2020 and to the DGC-2020 that the module is connected to. Type: 10/100BASE-T Industrial Ethernet devices designed to comply with IEC 61000-4 series of specifications are recommended.
CE Compliance This product complies with the requirements of the following EC Directives: Low Voltage Directive (LVD) - 73/23/EEC as amended by 93/68/EEC Electromagnetic Compatibility (EMC) - 89/336/EEC as amended by 92/31/EEC and 93/68/EEC This product conforms to the following Harmonized Standards: EN 50178:1997 - Electronic Equipment for use in Power Installations EN 61000-6-4:2001 - Electromagnetic Compatibility (EMC), Generic Standards, Emission Standard for Industrial Environments EN 61000-6
Generator Sequencing Machines can be added or removed from the power system based on load demand. The following criteria should be considered before adding or removing a machine: Machine Priority Engine Run Time Machine Size kW% of the load/demand Out of Service machines Communications The LSM-2020 communication ports include CAN terminals and an Ethernet port. CANbus A Control Area Network (CAN) is a standard interface that enables communication between the LSM2020 and the DGC-2020.
Figure 8-1. Device Info Screen A Application Version: When configuring Load Share Module settings off-line, the application version for the unit to be configured must be selected. B Application Version: Read-only value obtained when BESTCOMSPlus is communicating with the Load Share Module. C Boot Code Version: Read-only value obtained when BESTCOMSPlus is communicating with the Load Share Module. D Application Build: Read-only value obtained when BESTCOMSPlus is communicating with the Load Share Module.
Figure 8-2. Device Security Setup Screen A Access Level/Password: Read-only value obtained when BESTCOMSPlus is communicating with the Load Share Module. B Password: Accepts an alphanumeric character string of up to 16 characters. C Save Password: Clicking this button will save the password changes in BESTCOMSPlus memory. INSTALLATION LSM-2020’s are delivered in sturdy cartons to prevent shipping damage.
1.39 [35.3] 6.38 [162.0] 5.50 [139.7] J3 P2 1 2 3 4 5 6 7 8 7.50 [190.5] 9 8.38 [212.8] 10 11 12 13 14 15 16 17 18 P0052-36 Figure 8-3. LSM-2020 Overall Dimensions Connections LSM-2020 connections are dependent on the application. Incorrect wiring may result in damage to the module. NOTE Operating power from the battery must be of the correct polarity. Although reverse polarity will not cause damage, the LSM-2020 will not operate.
Operating Power The LSM-2020 operating power input accepts either 12 Vdc or 24 Vdc and tolerates voltage over the range of 6 to 32 Vdc. Operating power must be of the correct polarity. Although reverse polarity will not cause damage, the LSM-2020 will not operate. Operating power terminals are listed in Table 8-1. It is recommended that a fuse be added for additional protection for the wiring to the battery input of the LSM-2020. A Bussmann ABC-7 fuse or equivalent is recommended. Table 8-1.
CANbus Interface These terminals provide communication using the SAE J1939 protocol and provide high-speed communication between the LSM-2020 and the DGC-2020. Connections between the LSM-2020 and DGC-2020 should be made with twisted-pair, shielded cable. CANbus interface terminals are listed in Table 8-4. Refer to Figure 8-4 and Figure 8-5. Table 8-4.
AEM-2020 (Optional) LSM-2020 Bus Stub CAN-H DGC-2020 Engine CAN-L P0053-59 120 ohm Termination Other Devices CEM-2020 (Optional) 120 ohm Termination Figure 8-5. CANbus Interface with DGC-2020 providing One End of the Bus Ethernet Port The LSM-2020 has Ethernet capability. The LSM-2020 connects to a PC through a RJ-45 jack (J3). Industrial Ethernet devices designed to comply with IEC 61000-4 series of specifications are recommended.
48 49 50 GEN ENGINE 12 11 10 CANL CANH GND DGC-2020 AVR GOV CANL CANH GND Ethernet To Other LSM-2020's 5 6 LSLS+ LSM-2020 AVRAVR+ 14 15 GOVGOV+ 17 18 L O A D DGC-2020 48 49 50 GEN ENGINE 12 11 10 AVR GOV CANL CANH GND Ethernet CANL CANH GND Industrial Ethernet Switch 5 6 LSLS+ LSM-2020 AVRAVR+ 14 15 GOVGOV+ 17 18 Up to 16 LSM-2020's are supported on the network.
Connections using AVR’, GOV’, and LS’ Additional terminals provide a landing point to add series resistance to the GOV, AVR, and LS analog outputs. These terminals are not internally connected to the LSM-2020. Figure 8-8 illustrates connections using the additional AVR’ terminal as a landing point.
To System Load Share Line 12 or 24 Vdc SHIELD DGC-2020 CANH CANL External Device Governor Analog Aux Output + 1 GND 2 B+ 3 4 B- 5 6 LSLS+ 7 I+ 8 9 V+ Ethernet LS’ IN- 10 11 12 GND 13 14 GOV’ 15 16 GOV+ LSM-2020 CANH CANL GOV- AVR’ 17 AVR- 18 AVR+ Analog Aux Input + P0056-92 Figure 8-9.
This page intentionally left blank.
SECTION 9 CEM-2020 (CONTACT EXPANSION MODULE) TABLE OF CONTENTS SECTION 9 CEM-2020 (CONTACT EXPANSION MODULE) ............................................................... 9-1 GENERAL INFORMATION.................................................................................................................... 9-1 FEATURES ............................................................................................................................................ 9-1 SPECIFICATIONS .....................
This page intentionally left blank.
SECTION 9 CEM-2020 (CONTACT EXPANSION MODULE) GENERAL INFORMATION The optional CEM-2020 is a remote auxiliary device that provides additional DGC-2020 contact inputs and outputs.
HALT (Highly Accelerated Life Testing) HALT is used by Basler Electric to prove that our products will provide the user with many years of reliable service. HALT subjects the device to extremes in temperature, shock, and vibration to simulate years of operation, but in a much shorter period span. HALT allows Basler Electric to evaluate all possible design elements that will add to the life of this device.
BESTCOMSPlus SOFTWARE BESTCOMSPlus provides the user with a point-and-click means to set and monitor the Contact Expansion Module. Installation and operation of BESTCOMSPlus is described in Section 4, BESTCOMSPlus Software. INSTALLATION Contact Expansion Modules are delivered in sturdy cartons to prevent shipping damage. Upon receipt of a module, check the part number against the requisition and packing list for agreement.
Connections Contact Expansion Module connections are dependent on the application. Incorrect wiring may result in damage to the module. NOTE Operating power from the battery must be of the correct polarity. Although reverse polarity will not cause damage, the CEM-2020 will not operate. Be sure that the CEM-2020 is hard-wired to earth ground with no smaller than 12 AWG copper wire attached to the chassis ground terminal on the module.
Figure 9-2. CEM-2020 Input Contact and Output Contact Terminals CANbus Interface These terminals provide communication using the SAE J1939 protocol and provide high-speed communication between the Contact Expansion Module and the DGC-2020. Connections between the CEM-2020 and DGC-2020 should be made with twisted-pair, shielded cable. CANbus interface terminals are listed in Table 9-2. Refer to Figure 9-3 and Figure 9-4. Table 9-2.
NOTES 1.) If the CEM-2020 is providing one end of the J1939 bus, a 120 terminating resistor should be installed across terminals P1- LO (CANL) and P1- HI (CANH). 2.) If the CEM-2020 is not part of the J1939 bus, the stub connecting the CEM2020 to the bus should not exceed 914 mm (3 ft) in length. 3.) The maximum bus length, not including stubs, is 40 m (131 ft). 4.) The J1939 drain (shield) should be grounded at one point only. If grounded elsewhere, do not connect the drain to the CEM-2020.
SECTION 10 AEM-2020 (ANALOG EXPANSION MODULE) TABLE OF CONTENTS SECTION 10 AEM-2020 (ANALOG EXPANSION MODULE).............................................................. 10-1 GENERAL INFORMATION.................................................................................................................. 10-1 FEATURES .......................................................................................................................................... 10-1 SPECIFICATIONS ........................
This page intentionally left blank.
SECTION 10 AEM-2020 (ANALOG EXPANSION MODULE) GENERAL INFORMATION The optional AEM-2020 is a remote auxiliary device that provides additional DGC-2020 analog inputs and outputs.
Type Tests Shock 15 G in 3 perpendicular planes Vibration Swept over the following ranges for 12 sweeps in each of three mutually perpendicular planes with each 15-minute sweep consisting of the following: 5 to 29 to 5 Hz: 1.5 G peak for 5 min. 29 to 52 to 29 Hz: 0.036” Double Amplitude for 2.5 min. 52 to 500 to 52 Hz: 5 G peak for 7.5 min. Ignition System Tested in closed proximity to an unshielded, unsuppressed Altronic DISN 800 ignition system.
FUNCTIONAL DESCRIPTION A functional description of the AEM-2020’s inputs and outputs is provided below. Analog Inputs The AEM-2020 provides eight analog inputs that are user-selectable for 4 to 20 mA or 0 to 10 Vdc. Each analog input has under/over thresholds that can be configured as status only, alarm, or pre-alarm. When enabled, an out of range alarm alerts the user of an open or damaged analog input wire. The label text of each analog input is customizable.
Mounting Analog Expansion Modules are contained in an encapsulated plastic case and may be mounted in any convenient position. The construction of a Analog Expansion Module is durable enough to mount directly on a genset using UNF ¼-20 or equivalent hardware. Hardware selection should be based on any expected shipping/transportation and operating conditions. The torque applied to the mounting hardware should not exceed 65 in-lb (7.34 N•m). See Figure 10-1 for AEM-2020 overall dimensions.
is mounted permanently to the board. Connector screw terminals accept a maximum wire size of 12 AWG. Thermocouple connectors accept a maximum thermocouple wire diameter of 0.177 inches (4.5 mm). Maximum screw torque is 5 inch-pounds (0.56 Nm). Operating Power The Analog Expansion Module operating power input accepts either 12 Vdc or 24 Vdc and tolerates voltage over the range of 6 to 32 Vdc. Operating power must be of the correct polarity.
Table 10-2. Input and Output Terminals Connector Description P1 Operating Power and CANbus P2 RTD Inputs 1 - 8 P3 Analog Inputs 1 - 8 and Analog Outputs 1 - 4 P4 Thermocouple 1 Input P5 Thermocouple 2 Input External RTD Input Connections External 2-wire RTD input connections are shown in Figure 10-3. Figure 10-4 shows external 3-wire RTD input connections. RED AEM-2020 RTD1+ RTD1– Jumper RTD1C P0053-64 BLACK Figure 10-3.
Table 10-3. CANbus Interface Terminals Terminal Description P1- HI (CAN H) CAN high connection (yellow wire) P1- LO (CAN L) CAN low connection (green wire) P1- CAN drain connection (SHIELD) NOTES 1. If the AEM-2020 is providing one end of the J1939 bus, a 120 terminating resistor should be installed across terminals P1- LO (CANL) and P1- HI (CANH). 2. If the AEM-2020 is not part of the J1939 bus, the stub connecting the AEM2020 to the bus should not exceed 914 mm (3 ft) in length. 3.
CEM-2020 (Optional) AEM-2020 Bus Stub CAN-H Engine DGC-2020 CAN-L P0053-63 120 ohm Termination Other Devices LSM-2020 (Optional) 120 ohm Termination Figure 10-6. CANbus Interface with DGC-2020 providing One End of the Bus MAINTENANCE Preventive maintenance consists of periodically checking that the connections between the AEM-2020 and the system are clean and tight. Analog Expansion Modules are manufactured using state-of-the-art surface-mount technology.
APPENDIX A TIME OVERCURRENT CHARACTERISTIC CURVES TABLE OF CONTENTS APPENDIX A TIME OVERCURRENT CHARACTERISTIC CURVES...................................................A-1 INTRODUCTION ...................................................................................................................................A-1 CURVE SPECIFICATIONS ...................................................................................................................A-1 TIME OVERCURRENT CHARACTERISTIC CURVE GRAPHS....
This page intentionally left blank.
APPENDIX A TIME OVERCURRENT CHARACTERISTIC CURVES INTRODUCTION The inverse time overcurrent characteristic curves provided by the DGC-2020 (style xxxxxxExx only) closely emulate most of the common electromechanical, induction-disk, overcurrent relays sold in North America. To further improve proper relay coordination, selection of integrated reset or instantaneous reset characteristics is also provided. CURVE SPECIFICATIONS Timing Accuracy: Within ±500 milliseconds of indicated operating point.
Table A-1. 51 Time Characteristic Curve Constants Curve Selection Trip Characteristic Constants Curve Name Reset A B C N K R S1 S, S1, Short Inverse 0.2663 0.03393 1.0000 1.2969 0.0280 0.5000 S2 S2, Short Inverse 0.0286 0.02080 1.0000 0.9844 0.0280 0.0940 L1 L, L1, Long Inverse 5.6143 2.18592 1.0000 1.0000 0.0280 15.750 L2 L2, Long Inverse 2.3955 0.00000 1.0000 0.3125 0.0280 7.8001 D D, Definite Time 0.4797 0.21359 1.0000 1.5625 0.0280 0.
Table A-2.
Table A-3 .Time Dial Setting Cross-Reference Curve Equivalent To Electromechanical Relay Time Dial Setting 0.5 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 Basler Electric Equivalent Time Dial Setting A-4 S, S1 ABB CO-2 0.3 0.8 1.7 2.4 3.4 4.2 5.0 5.8 6.7 7.7 8.6 9.7 L, L1 ABB CO-5 0.4 0.8 1.5 2.3 3.3 4.2 5.0 6.0 7.0 7.8 8.8 9.9 D ABB CO-6 0.5 1.1 2.0 2.9 3.7 4.5 5.0 5.9 7.2 8.0 8.9 10.1 M ABB CO-7 0.4 0.8 1.7 2.5 3.3 4.3 5.3 6.1 7.0 8.
Figure A-1.
Figure A-2.
Figure A-3.
Figure A-4.
Figure A-5.
Figure A-6.
Figure A-7.
Figure A-8.
Figure A-9.
Figure A-10.
Figure A-11.
Figure A-12.
Figure A-13.
Figure A-14.
Figure A-15.
Figure A-16.
APPENDIX B MODBUS COMMUNICATION TABLE OF CONTENTS APPENDIX B Modbus COMMUNICATION .........................................................................................B-1 INTRODUCTION....................................................................................................................................B-1 General Overview...............................................................................................................................
This page intentionally left blank.
APPENDIX B MODBUS COMMUNICATION INTRODUCTION General Overview An optional feature of the DGC-2020 performs Modbus communications by emulating a subset of the Modicon 984 Programmable Controller. This document describes the Modbus communications protocol employed by the DGC-2020 and how to exchange information with the DGC-2020 over a Modbus network. The DGC-2020 maps all parameters into the Modicon 984 Holding Register address space (4XXXX).
Data Block Field The query Data block contains additional information needed by the slave to perform the requested function. The response Data block contains data collected by the slave for the queried function. An error response will substitute an Exception Response Code for the Data Block. The length of this field varies with each query.
Function 08, Subfunction 00 - Diagnostics: Return Query Data Function 16 - Preset Multiple Registers, Non-Broadcast & Broadcast The only Broadcast query supported by the DGC-2020 is the Preset Multiple Registers query. Read Holding Registers Read Holding Registers - General QUERY: This query message requests a register or block of registers to be read. The data block contains the starting register address and the quantity of registers to be read. A register address of N will read Holding Register N+1.
Preset Multiple Registers, Non-Broadcast & Broadcast Preset Multiple Registers - General QUERY: This query message requests a register or block of registers to be written. The data block contains the starting address and the quantity of registers to be written, followed by the Data Block byte count and data. A device address is 0 for a broadcast query. A register address of N will write Holding Register N+1.
There are several instances of registers that are grouped together (signified as DP or TP) to collectively represent a single numerical (vs. ASCII string) DGC-2020 parameter value. A query to write a subset of such a register group will result in an error response with Exception Code “Illegal Data Address”. A query to write an unallowed value (out of range) to a register results in an error response with Exception Code of “Illegal Data Value”.
Long Integer Data Format (INT32) The Modbus long integer data format uses two consecutive holding registers to represent a 32-bit data value. The first register contains the low-order 16 bits and the second register contains the high-order 16 bits. Example: The value 95,800 represented in long integer format is hexadecimal 0x00017638.
The second register contains the low-order 16 bits of double precision data, and is the actual data value modulus 10,000. Triple Precision Data Format (TP) The Modbus Triple Precision data format (TP) uses 3 consecutive registers to represent a data value. The first register contains the high-order 16 bits of triple precision data, and is the actual data value / 100,000,000.
MAPPING - DGC-2020 PARAMETERS INTO MODICON ADDRESS SPACE Table Conventions Table B-3 uses the conventions outlined in this section.
Table B-3.
Holding Register Parameter Range Read/Write Supported 40049 Threshold LOW BATTERY VOLTAGE PRE-ALARM 3-100 RW 40050 Enable 0-1 RW 40051 Threshold 40052 Pre-alarm Activation Time Delay WEAK BATTERY VOLTAGE PRE-ALARM 40053 Enable 40054 Threshold 0-1 40055 Pre-alarm Activation Time Delay 40056-59 RESERVED HIGH COOLANT TEMP ALARM 40060 60-120 (12V) 120-240 (24V) 1-10 Enable 40-80 (12V) 80-160 (24V) 1-10 Data Format Units PSI 0 =Off 1 =On RW .
Holding Register Parameter Range Read/Write Supported Data Format Units R R R R R RW RW b0=High Coolant Temperature b1=Low Coolant Level b2=Low Fuel Level b3=Emergency Stop b4=Sender Failure b5=Over Crank b6=Over Speed b7=Low Oil Pressure Rev. 3.04 Added: b8 = CAN Fail b0=High Coolant Temperature b1=Low Coolant Temperature b2=Weak Battery b3=Low Battery b4=Battery Overvoltage b5=Battery Charger Fail b6=Maintenance Interval b7=Engine Overload Rev. 3.
Holding Register Parameter Range Read/Write Supported Data Format Units 40110 40111 40112 40113 40114 40115 40116 40117 40118 40119 40120 40121 40122 40123 40124 40125 40126 40127 40128 Phase a RMS Current Phase b RMS Current Phase c RMS Current Phase a Apparent Power(a) Phase a Apparent Power(b) Phase b Apparent Power(a) Phase b Apparent Power(b) Phase c Apparent Power(a) Phase c Apparent Power(b) 3 Phase Apparent Power(a) 3 Phase Apparent Power(b) Phase a Power(a) Phase a Power(b) Phase b Power(a)
Holding Register 40287-97 40298 Parameter Range Read/Write Supported Data Format Units RESERVED Read Relay Image of both Main and Aux Output 40299 RESERVED J1939 DIAGNOSTIC TROUBLE CODES Active DTC Number 16 – Lower 40300 Two Bytes Active DTC Number 16 – Upper 40301 Two Bytes Active DTC Number 15 – Lower 40302 Two Bytes Active DTC Number 15 – Upper 40303 Two Bytes Active DTC Number 14 – Lower 40304 Two Bytes Active DTC Number 14 – Upper 40305 Two Bytes Active DTC Number 13 – Lower 40306 Two Bytes A
Holding Register 40322 40323 40324 40325 40326 40327 40328 40329 40330 40331 40332 40333 40334 40335 40336 40337 40338 40339 40340 40341 40342 40343 40344 40345 40346 40347 40348 40349 40350 40351 40352 40353 B-14 Parameter Range Active DTC Number 5 – Lower Two Bytes Active DTC Number 5 – Upper Two Bytes Active DTC Number 4 – Lower Two Bytes Active DTC Number 4 – Upper Two Bytes Active DTC Number 3 – Lower Two Bytes Active DTC Number 3 – Upper Two Bytes Active DTC Number 2 – Lower Two Bytes Active DTC N
Holding Register 40354 40355 40356 40357 40358 40359 40360 40361 40362 40363 40364 40365 40366 40367 Parameter Range Previous DTC Number 12 – Lower Two Bytes Previous DTC Number 12 – Upper Two Bytes Previous DTC Number 13 – Lower Two Bytes Previous DTC Number 13 – Upper Two Bytes Previous DTC Number 14 – Lower Two Bytes Previous DTC Number 14 – Upper Two Bytes Previous DTC Number 15 – Lower Two Bytes Previous DTC Number 15 – Upper Two Bytes Previous DTC Number 16 – Lower Two Bytes Previous DTC Number 16
Holding Register Parameter Range 40372 CAN Communications Diagnostics for use when CAN is enabled. 40373 System Config 40374 40375 40380-81 System Status Read/Write Supported individual bits are 0 or 1 R individual bits are 0 or 1 RW 0 - 10 Used to display Value, NC, NS, NA, and SF R R Units Bit 12 - .Engine Run Time Bit 11 – Data Failure Status. Previous Active DTCs Cleared Bit 10 –Active DTCs Cleared Bit 9 -.Previous Active DTCs Bit 8 -.
Holding Register Parameter Range Read/Write Supported Data Format Units 0 = Not configured; 1 = Volvo Penta EDC3; 2 = MTU MDEC 3 = MTU ADEC milliseconds 40388 CANbus ECU Configuration 0-65535 RW 40395 ECU Settling Time ECU Pulse Cycle Time - The amount of time unit is to wait in OFF between Pulse Cycles. ECU Disconnect Time - The amount of time ECU is kept powered off. ECU Connect Time - The amount of time ECU is powered when connecting (unit tries to run). Also used for the Pulse duration time.
Holding Register Parameter Range Read/Write Supported Data Format Units 40444 Coolant Level 0 to +100 % R 40445 Fuel Rate 0 to +3212.75 L/h R 40446 Barometric Pressure 0 to +125 kPa (0 to +18.1 psi) R Raw ECU Parameter Data 0.4 %/bit gain, 0 % offset Raw ECU Parameter Data 0.05 L/h per bit gain, 0 L/h offset (13.9 x 10-6 L/s per bit) Raw ECU Parameter Data 0.5 kPa/bit gain, 0 kPa offset 40447 Ambient Air Temperature -273 to +1735.0 °C (-459.4 to 3155.0 °F) R Raw ECU Parameter Data 0.
Holding Register Parameter Range Read/Write Supported 40468 Override Speed Point7 0 to 8031.875 rpm R 40469 Override Time Limit 0 s to 25 s R 40470 Speed Lower Limit 0 to 2500 rpm R 40471 Speed Upper Limit 0 to 2500 rpm R 40472 Torque Lower Limit 0 to 125% R 40473 Torque Upper Limit 0 to 125% R 40474 Crankcase Pressure -250 to +251.99 kPa R 40475 Oil Filter Diff. Pressure 0 to 125 kPa R 40476 Fuel Filter Diff.
Holding Register Parameter Range Read/Write Supported Data Format Units 40509-604 RESERVED OVERCURRENT 40605 51 Pick-up – 3-phase 40606 51 Time Dial – 3-phase 40607 40608 51 Curve – 3-phase 51 Alarm Config. – 3-phase 40609 51 Pick-up – 1-phase 40610 51 Time Dial – 1-phase 40611 51 Curve – 1-phase 40612 51 Alarm Config.
Holding Register Parameter Range Read/Write Supported Data Format Units 40640 Gen Protection Pre-Alarms (lower 16 bits) 0-65535 R b0 = overvoltage pre-alarm, b1 = undervoltage pre-alarm, b2 = overfrequency pre-alarm, b3 = underfrequency pre-alarm, b4 = overcurrent pre-alarm, b5 = phase imbalance pre-alarm, b6-b15 UNASSIGNED 40641 Gen Protection Alarms (upper 16 bits) 0-65535 R b16-b31 UNASSIGNED 0-65535 R b0 = overvoltage alarm, b1 = undervoltage alarm, b2 = overfrequency alarm, b3 = under
Holding Register 40761 Parameter Read/Write Supported Range MTU Pre-alarms 0-65535 Data Format Units b0 = High ECU Temp, b1 = High Oil Temp, b2 = High Intercooler Temp, b3 = High Charge Air Temp, b4 = High Coolant Temp, b5 = Shutdown Override, b6 = High Fuel Rail Press, b7 = Low Fuel Rail Press, b8 = Low Coolant Level, b9 = Low Charge Air Pressure, b10 = Low Fuel Deliv Pressure, b11 = Low Oil Pressure, b12 = Combined Yellow, b13-b15 UNASSIGNED R Current Parameter Table The DGC-2020 maps all non-l
Register Description 42052 Mains Breaker Status 42054-60 RESERVED 42062 Dead Bus Close Enable 42064-248 FUTURE USE Scaling Factor R/W Int32 Type N/A Units N/A R 0 = Open 1 = Closed Range Int32 N/A N/A RW 0 = Disable 1 = Enable Bias Control Settings Register Description Type Float Units N/A Scaling Factor N/A R/W RW Range 42250 AVR Kp Proportional Gain 0 - 1000 42252 AVR Ki Integral Gain Float N/A N/A RW 0 - 1000 42254 AVR Kd Derivative Gain Float N/A N/A RW 0 -
Register Description Type Units Scaling Factor R/W Range 42328 kw Integrator Limit Plus Float N/A N/A RW 0 - 1000 42330 kw Integrator Limit Minus Float N/A N/A RW (-1000) - 0 42332 kw Output Upper Limit Float N/A N/A RW 0 - 1000 42334 kw Output Lower Limit Float N/A N/A RW (-1000) - 0 42336 RESERVED 42338 Droop Percent Float Percent N/A RW 0 - 10 42340 Load Control Int32 N/A N/A RW 0 = Disable 1 = Enable 42342 kw Load Rate Int32 N/A Deci RW 0 - 1000
Register Description Type Int32 Units CentiHertz Scaling Factor R/W Range Centi RW 4600 - 6400 42768 Gen Sensing Stable Overfrequency Pickup 42770 Gen Sensing Stable Overfrequency Dropout Int32 CentiHertz Centi RW 4600 - 6400 42772 Gen Sensing Fail Time Delay Int32 Decisecond Deci RW 1 - 6000 42774 Gen Sensing Stable Time Delay Int32 Decisecond Deci RW 1 - 6000 42776 RESERVED 42778 Bus Sensing Dead Bus Pickup Int32 Volt N/A RW 1 - 4800 42780 Bus Sensing Dead Bus Ti
Register Description Type Units Scaling Factor R/W Range 43502 Pre-Start Contact Config Int32 N/A N/A RW 0 = Open After Disconnect 1 = Closed While Running 43504 System Units Int32 N/A N/A RW 0 = English 1 = Metric 43506 Battery Volts Int32 N/A N/A RW 0 = 12V 1 = 24V 43508 Off Mode Status Int32 N/A N/A R 0 = Disable 1 = Enable 43510 Run Mode Status Int32 N/A N/A R 0 = Disable 1 = Enable 43512 Auto Mode Status Int32 N/A N/A R 0 = Disable 1 = Enable 43514 Virt
Register Description Type Units Scaling Factor R/W Range 43574 Speed Signal Source Uint32 N/A N/A RW 1 = MPU 2 = Gen Freq 3 = MPU Freq 43576 NFPA Level Uint32 N/A N/A RW 0 = Zero 1 = One 2 = Two 43578 Horn Enable Int32 N/A N/A RW 0 = Disabled 1 = Enabled 43580 Single Phase Override Sensing Uint32 N/A N/A RW 0 = AB 1 = AC 43582 RESERVED 43584 LCD Contrast Value Uint32 N/A N/A RW 0 - 100 43586 Front Panel Sleep Mode Uint32 N/A N/A RW 0 = Disabled 1 = Enabled
Register Description Type Scaling Factor Units R/W Range 43616 DST End Week of Month Int32 N/A N/A RW 0 = First 1 = Second 2 = Third 3 = Fourth 4 = Last 43618 DST End Day of Week Int32 N/A N/A RW 0 = Sunday 1 = Monday 2 = Tuesday 3 = Wednesday 4 = Thursday 5 = Friday 6 = Saturday 43620 DST End Hour Int32 N/A N/A RW 0 - 23 43622 DST End Minute Int32 N/A N/A RW 0 - 59 43624 EPS Low Line Scale Factor Float N/A N/A RW 0-3 43626 Rated Power Factor Float Power Factor
Register Description Type Units Scaling Factor R/W Range 43776 Virtual Input 1 Open Int32 N/A N/A RW 0 = Disable 1 = Enable 43778 Virtual Input 2 Close Int32 N/A N/A RW 0 = Disable 1 = Enable 43780 Virtual Input 2 Open Int32 N/A N/A RW 0 = Disable 1 = Enable 43782 Virtual Input 3 Close Int32 N/A N/A RW 0 = Disable 1 = Enable 43784 Virtual Input 3 Open Int32 N/A N/A RW 0 = Disable 1 = Enable 43786 Virtual Input 4 Close Int32 N/A N/A RW 0 = Disable 1 = Enable 4
Register Type 44262 1 Phase Overcurrent Curve (511) Uint32 N/A N/A RW 0 = S1 Curve 1 = S2 Curve 2 = L1 Curve 3 = L2 Curve 4 = D Curve 5 = M Curve 6 = I1 Curve 7 = I2 Curve 8 = V1 Curve 9 = V2 Curve 10 = E1 Curve 11 = E2 Curve 12 = A Curve 13 = B Curve 14 = C Curve 15 = G Curve 16 = F Curve 44264 1 Phase Overcurrent Alarm Configuration (51-1) Uint32 N/A N/A RW 0 = None 1 = Alarm 2 = Pre-Alarm 44266 Phase Imbalance Pickup Uint32 Volt N/A RW 5 - 100 44268 Phase Imbalance Activation Dela
Register Type 44306 Underfrequency Alarm Configuration Uint32 N/A 44308 Overfrequency Pickup Uint32 DeciHertz Deci RW 450 - 4400 44310 Overfrequency Activation Delay Uint32 Decisecond Deci RW 0 - 300 44312 Overfrequency Alarm Configuration Uint32 N/A N/A RW 0 = None 1 = Alarm 2 = Pre-Alarm 44314 Overcurrent Low Line Scale Factor (51-1) Float N/A N/A RW 0-3 44316 Overvoltage Low Line Scale Factor (59-1) Float N/A N/A RW 0-3 44318 Undervoltage Low Line Scale Factor (2
Register Scaling Factor Description Type Units 44338 3 Phase Undervoltage Activation Delay (27-2) Uint32 Decisecond Deci RW 0 - 300 44340 3 Phase Undervoltage Inhibit Frequency (27-2) Uint32 Hertz N/A RW 20 - 400 44342 3 Phase Undervoltage Alarm Configuration (27-2) Uint32 N/A N/A RW 0 = None 1 = Alarm 2 = Pre-Alarm 44344 1 Phase Undervoltage Pickup (27-2) Uint32 Volt N/A RW 70 - 576 44346 1 Phase Undervoltage Activation Delay (27-2) Uint32 Decisecond Deci RW 0 - 300
Register Description Type Scaling Factor Units R/W Range 44396 3 Phase Reverse Power Alarm Configuration Uint32 N/A N/A RW 0 = None 1 = Alarm 2 = Pre-Alarm 44398 3 Phase Reverse Power Hysteresis Int32 DeciPercent Deci RW 10 - 100 44400 1 Phase Reverse Power Pickup Uint32 DeciPercent Deci RW (-500) - 50 44402 1 Phase Reverse Power Activation Delay Uint32 Decisecond Deci RW 0 - 300 44404 1 Phase Reverse Power Alarm Configuration Uint32 N/A N/A RW 0 = None 1 = Alarm 2 =
Scaling Factor R/W 44516 Register Overspeed Alarm Enable Uint32 N/A N/A RW 0 = Disable 1 = Enable 44518 Overspeed Alarm Threshold Uint32 Percent N/A RW 105 - 140 44520 Overspeed Alarm Activation Delay Uint32 Millisecond Milli RW 0 - 500 44522 Low Fuel Level Alarm Enable Uint32 N/A N/A RW 0 = Disable 1 = Enable 44524 Low Fuel Level Alarm Threshold Uint32 Percent N/A RW 0 - 100 44526 Low Fuel Level Alarm Activation Delay Int32 Second N/A RW 0 - 30 44528 High Coola
Description Type Scaling Factor R/W 44578 Register Maintenance Interval Pre-Alarm Enable Uint32 N/A N/A RW 0 = Disable 1 = Enable 44580 Maintenance Interval Pre-Alarm Threshold Uint32 Hour N/A RW 0 - 5000 44582 Speed Sender Fail Activation Delay Int32 Second N/A RW 0 - 300 44584 ECU Low Coolant Level Alarm Enable Uint32 N/A N/A RW 0 = Disable 1 = Enable 44586 ECU Low Coolant Level Alarm Threshold Uint32 Percent N/A RW 1 - 99 44588 ECU Low Coolant Level PreAlarm Enabl
Scaling Factor R/W 44634 Register GOV Bias Output Limit Prealarm Activation Delay Description Int32 Type Second Units N/A RW 1 - 15 Range 44636 GOV Bias Output Limit Prealarm Enable Int32 N/A N/A RW 0 = Disable 1 = Enable 44638 ID Missing Pre-alarm Enable Int32 N/A N/A RW 0 = Disable 1 = Enable 44640 ID Repeat Pre-alarm Enable Int32 N/A N/A RW 0 = Disable 1 = Enable 44642 CEM Comm Failure Pre-alarm Enable Int32 N/A N/A RW 0 = Disable 1 = Enable 44644 AEM Comm Failu
Register Description Type Units Scaling Factor R/W Range 44812 Alarm Metering Int32 N/A N/A R Bit 0 = Overspeed Bit 1 = Hi Coolant Temp Bit 2 = Low Oil Pressure Bit 3 = Low Fuel Level Bit 4 = Global Sender Fail Bit 5 = Loss of ECU Comms Bit 6 = Overcrank Bit 7 = Emergency Shutdown Bit 8 = Loss of ECU Shutdown Bit 9 = ECU Low Coolant Level 44814 Pre-Alarm Metering Int32 N/A N/A R Bit 0 = Hi Coolant Temp Bit 1 = Low Oil Pressure Bit 2 = Low Fuel Level Bit 3 = Low Coolant Temp Bit 4 = Low B
Register Description Type Units Scaling Factor R/W Range 44828 Local Input Metering Int32 N/A N/A R Bit 0 = Input 1 Bit 1 = Input 2 Bit 2 = Input 3 Bit 3 = Input 4 Bit 4 = Input 5 Bit 5 = Input 6 Bit 6 = Input 7 Bit 7 = Input 8 Bit 8 = Input 9 Bit 9 = Input 10 Bit 10 = Input 11 Bit 11 = Input 12 Bit 12 = Input 13 Bit 13 = Input 14 Bit 14 = Input 15 Bit 15 = Input 16 44830 Local Output Metering Int32 N/A N/A R Bit 0 = Output 1 Bit 1 = Output 2 Bit 2 = Output 3 Bit 3 = Output 4 Bit 4 = Out
Register Description Type Units Scaling Factor R/W Range 44858 Session Total Engine Run Hrs. Int32 Hour N/A R 0 - 99999 44860 Session Total Engine Run Min. Int32 N/A N/A R 0 - 59 44862 Session Loaded Engine Run Hrs. Int32 Hour N/A R 0 - 99999 44864 Session Loaded Engine Run Min. Int32 N/A N/A R 0 - 59 44866 Session Unloaded Engine Run Hrs. Int32 Hour N/A R 0 - 99999 44868 Session Unloaded Engine Run Min.
Register Description Type Units Scaling Factor R/W Range 44956 Local Configurable Inputs Alarm Bits Int32 N/A N/A R Bit 0 = Input 1 Bit 1 = Input 2 Bit 2 = Input 3 Bit 3 = Input 4 Bit 4 = Input 5 Bit 5 = Input 6 Bit 6 = Input 7 Bit 7 = Input 8 Bit 8 = Input 9 Bit 9 = Input 10 Bit 10 = Input 11 Bit 11 = Input 12 Bit 12 = Input 13 Bit 13 = Input 14 Bit 14 = Input 15 Bit 15 = Input 16 44958 Configurable Elements Status Bits Int32 N/A N/A R Bit 0 = Config Element 1 Bit 1 = Config Element 2 B
Register Description Type Units Scaling Factor R/W Range 44966 Remote Outputs Status Bits Int32 N/A N/A R Bit 0 = Remote Output 13 Bit 1 = Remote Output 14 Bit 2 = Remote Output 15 Bit 3 = Remote Output 16 Bit 4 = Remote Output 17 Bit 5 = Remote Output 18 Bit 6 = Remote Output 19 Bit 7 = Remote Output 20 Bit 8 = Remote Output 21 Bit 9 = Remote Output 22 Bit 10 = Remote Output 23 Bit 11 = Remote Output 24 Bit 12 = Remote Output 25 Bit 13 = Remote Output 26 Bit 14 = Remote Output 27 Bit 15 = Remo
Register Description Type Units Scaling Factor R/W Range 45504 Analog Input 3 Metering Value Int32 DeciUnit Deci R (-99990) - 99990 45506 Analog Input 4 Metering Value Int32 DeciUnit Deci R (-99990) - 99990 45508 Analog Input 5 Metering Value Int32 DeciUnit Deci R (-99990) - 99990 45510 Analog Input 6 Metering Value Int32 DeciUnit Deci R (-99990) - 99990 45512 Analog Input 7 Metering Value Int32 DeciUnit Deci R (-99990) - 99990 45514 Analog Input 8 Metering Value
Register Description Type Units Scaling Factor R/W 45538 AEM Input Threshold Status Bits Reg 2 Uint32 N/A N/A R 45540 AEM Input Threshold Status Bits Reg 3 Uint32 N/A N/A R 45542 AEM Input Threshold Status Bits Reg 4 Uint32 N/A N/A R 9400200990 Rev K DGC-2020 Modbus Communication Range Bit 0 = Analog Input 7 Out of Range Bit 1 = Analog Input 7 Over 1 Bit 2 = Analog Input 7 Over 2 Bit 3 = Analog Input 7 Under 1 Bit 4 = Analog Input 7 Under 2 Bit 5 = Analog Input 8 Out of Range Bit
Register Description Type Units Scaling Factor R/W 45544 AEM Input Threshold Alarm Bits Reg 1 Uint32 N/A N/A R 45546 AEM Input Threshold Alarm Bits Reg 2 Uint32 N/A N/A R B-44 DGC-2020 Modbus Communication Range Bit 0 = Analog Input 1 Out of Range Bit 1 = Analog Input 1 Over 1 Bit 2 = Analog Input 1 Over 2 Bit 3 = Analog Input 1 Under 1 Bit 4 = Analog Input 1 Under 2 Bit 5 = Analog Input 2 Out of Range Bit 6 = Analog Input 2 Over 1 Bit 7 = Analog Input 2 Over 2 Bit 8 = Analog Input 2 Un
Register Description Type Units Scaling Factor R/W 45548 AEM Input Threshold Alarm Bits Reg 3 Uint32 N/A N/A R 45550 AEM Input Threshold Alarm Bits Reg 4 Uint32 N/A N/A R 45552 AEM Input Threshold PreAlarm Bits Reg 1 Uint32 N/A N/A R 9400200990 Rev K DGC-2020 Modbus Communication Range Bit 0 = RTD Input 5 Out of Range Bit 1 = RTD Input 5 Over 1 Bit 2 = RTD Input 5 Over 2 Bit 3 = RTD Input 5 Under 1 Bit 4 = RTD Input 5 Under 2 Bit 5 = RTD Input 6 Out of Range Bit 6 = RTD Input 6 Ov
Register Scaling Factor R/W N/A N/A R Uint32 N/A N/A R AEM Input Threshold PreAlarm Bits Reg 4 Uint32 N/A N/A R Analog Output 1 Metering Value Int32 CentiUnit Centi R Description Type 45554 AEM Input Threshold PreAlarm Bits Reg 2 Uint32 45556 AEM Input Threshold PreAlarm Bits Reg 3 45558 45560 B-46 Units DGC-2020 Modbus Communication Range Bit 0 = Analog Input 7 Out of Range Bit 1 = Analog Input 7 Over 1 Bit 2 = Analog Input 7 Over 2 Bit 3 = Analog Input 7 Under 1 Bit 4 = An
Register Description Type Units Scaling Factor R/W Range 45562 Analog Output 2 Metering Value Int32 CentiUnit Centi R (-999990) - 999990 45564 Analog Output 3 Metering Value Int32 CentiUnit Centi R (-999990) - 999990 45566 Analog Output 4 Metering Value Int32 CentiUnit Centi R (-999990) - 999990 45568 Configurable Protection Threshold Status Bits Uint32 N/A N/A R Bit 0 = Conf Protection 1 Over 1 Bit 1 = Conf Protection 1 Over 2 Bit 2 = Conf Protection 1 Under 1 Bit 3 = Conf
Register Description Type Units Scaling Factor R/W 45570 Configurable Protection Alarm Bits Uint32 N/A N/A R 45572 Configurable Protection Pre-Alarm Bits Uint32 N/A N/A R 45574 Gen Kvar A Int32 KiloVAr N/A R B-48 DGC-2020 Modbus Communication Range Bit 0 = Conf Protection 1 Over 1 Bit 1 = Conf Protection 1 Over 2 Bit 2 = Conf Protection 1 Under 1 Bit 3 = Conf Protection 1 Under 2 Bit 4 = Conf Protection 2 Over 1 Bit 5 = Conf Protection 2 Over 2 Bit 6 = Conf Protection 2 Under 1 Bi
Register Description Type Units Scaling Factor R/W Range 45576 Gen Kvar B Int32 KiloVAr N/A R (-2147483648) - 2147483647 45578 Gen Kvar C Int32 KiloVAr N/A R (-2147483648) - 2147483647 45580 Gen Kvar Total Int32 KiloVAr N/A R (-2147483648) - 2147483647 45582-749 FUTURE USE 45750 Device Address Int32 N/A N/A RW (-128) - 127 45752 pc Emergency Stop Uint32 N/A N/A RW 0 = Stop 1 = Start 45754 pc Relay Closed Uint32 N/A N/A RW 0 = Stop 1 = Start 45756 Test Butt
Register Description Type 46018 J1939-Rated RPM Uint32 46020 J1939-Exhaust Temp A Uint32 Units Scaling Factor Raw ECU Parameter Data R/W Range R 0.125 rpm/bit, 0 offset R −273 to +1735.0 °C (−459.4 to 3155.0 °F) R −273 to +1735.0 °C (−459.4 to 3155.0 °F) R 0.03125 °C/bit gain, −273 °C offset −273 to +1735.0 °C (−459.4 to 3155.0 °F) R No Scale Or Offset R 0.125 rpm/bit, gain 0 offset R 0.125 rpm/bit, gain 0 offset R 0.125 rpm/bit, gain 0 offset R 0.
Register Description Type Units Scaling Factor R/W Range 46052 J1939-ADEC Cylinder Cutout Code Uint32 Raw ECU Parameter Data R No Scale or Offset 46054 J1939-ADEC Start Sequence Bit Field Uint32 Raw ECU Parameter Data R No Scale or Offset 46056 J1939-ADEC P Lube Oil Limit LO Uint32 Raw ECU Parameter Data R 0.01 mbar per bit, 0 offset 46058 J1939-ADEC P Lube Oil Limit LO LO Uint32 Raw ECU Parameter Data R 0.
Register Units Scaling Factor Description Type R/W Range 46104 J1939-ADEC T Intercooler Limit Hi Uint32 Raw ECU Parameter Data R 01 Degree C per bit, 0 offset 46106 J1939-MTU Sps Node Uint32 Raw ECU Parameter Data R No Scale Or Offset 46108 J1939-MTU Sw Type Uint32 Raw ECU Parameter Data R No Scale Or Offset 46110 J1939-MTU Sw Var Uint32 Raw ECU Parameter Data R No Scale Or Offset 46112 J1939-MTU Sw Ed 1 Uint32 Raw ECU Parameter Data R No Scale Or Offset 46114 J1939-MTU
APPENDIX C TUNING PID SETTINGS TABLE OF CONTENTS APPENDIX C TUNING PID SETTINGS .................................................................................................C-1 INTRODUCTION....................................................................................................................................C-1 TUNING PROCEDURES.......................................................................................................................C-2 Voltage Controller Tuning Procedure....
This page intentionally left blank.
APPENDIX C TUNING PID SETTINGS INTRODUCTION The LSM-2020 (Load Share Module) and DGC-2020 utilize three controllers to accomplish synchronization, load sharing, and speed trim functions. The controllers are a speed controller, a voltage controller, and a kW load controller. The voltage and speed controller are in effect when the DGC-2020 is synchronizing the generator to a bus. When synchronizing, these controllers adjust the speed and voltage output of the generator to match that of the bus.
TUNING PROCEDURES Voltage Controller Tuning Procedure The voltage controller is tuned prior to the speed controller. Set all gains in voltage controller, speed controller, and KW load controller to 0. Start the generator and close the breaker onto some load. The voltage controller is only active during synchronization when the DGC-2020 is trying to close the generator breaker. In order to tune it, a variable AC voltage source must be connected across the bus input of the DGC-2020.
Var/PF Controller Tuning Procedure Once desired voltage controller performance is obtained, the Var/PF controller can be tuned. Set all gains in the Var/PF controller to 0, enable the Var /PF controller, and set the control mode to Var control. The generator must be paralleled to the utility (as indicated by the Parallel to Mains element in logic) in any of the tuning steps where the system is being tested for stable operation. KP - Proportional Gain Set an initial value of KP = 1 in the Var/PF Controller.
and the speed it is trying to reach. The important thing is that the generator’s output behaves in a stable manner. If the system is unstable, lower KP and repeat. Repeat this procedure, raising KP until the system is unstable, and then lower it to half the value where instability is first attained. If it is not possible to obtain stable speed operation, it may be necessary to reduce the control gains in the governor that has its analog bias input driven by the LSM-2020.
KD - Derivative Gain If the performance with KP and KI alone is satisfactory, you may stop here. Otherwise, KD, the derivative controller gain, can be used in conjunction with TD, the noise filter constant, to reduce overshoot obtained with the PI control. Setting KD and TD is an iterative process. Start with small values of KD such as 0.1 or half the KI value, whichever is less.
This page intentionally left blank.
ROUTE 143, BOX 269 HIGHLAND, IL 62249 USA http://www.basler.com, info@basler.