INSTRUCTION MANUAL FOR DIGITAL GENSET CONTROLLER DGC-2020 Publication: 9400200990 Revision: U 03/13
INTRODUCTION This instruction manual provides information about the operation and installation of the DGC-2020 Digital Genset Controller.
First Printing: November 2006 Printed in USA Copyright © 2013 Basler Electric, Highland Illinois 62249 USA All Rights Reserved March 2013 CONFIDENTIAL INFORMATION of Basler Electric, Highland Illinois, USA. It is loaned for confidential use, subject to return on request, and with the mutual understanding that it will not be used in any manner detrimental to the interest of Basler Electric.
REVISION HISTORY The following information provides a historical summary of the changes made to this instruction manual (9400200990), BESTCOMSPlus® software, firmware package, and hardware of the DGC-2020. Manual Revision and Date U, 03/13 Change Revised to support firmware package version 1.17.02 (see firmware package version history). Added new breaker hardware and mains fail transfer settings Minor text edits T, 01/13 Revised to support firmware package version 1.17.
Manual Revision and Date M, 11/09 Change L, 05/09 K, 01/09 iv Section 1: Under Specifications, Metering, Power Factor, changed calculation method from “PF = P (3-phase average) / S (3-phase average)” to “PF = Cosine of the Angle between Phase AB voltage (Vab) and Phase A current (Ia)”. Added “Diagnostics” to Figure 2-2, Metering Screen Branches. Section 3: Updated MTU Fault Code list. Added description for Logic Control Relays in Table 5-1.
Manual Revision and Date J, 08/08 Change Added Section 10, AEM-2020 (Analog Expansion Module). Added information for Automatic Generator Detection in Section 4. Improved CAN bus diagrams and notes throughout manual. Added information for Integrating Reset function in Section 4. Added information for Configurable Protection in Section 4. Improved definition of Emergency Stop Input in Section 6. Added installation diagrams for MTU MDEC ECU in Section 6.
BESTCOMSPlus® Version and Date 2.11.02, 12/11 Change 2.11.01, 11/11 2.10.02, 06/11 Changed Manual Regeneration setting to use a button instead of a drop-down menu on the ECU Setup screen. Enhanced settings file printout. Updated to support firmware package version 1.13.04 (see firmware package version history). Settings for generator protection, battery voltage protection, and configurable protection can now be entered in secondary or per unit values.
BESTCOMSPlus® Version and Date 2.03.01, 02/09 Change 2.03.00, 12/08 Added “P” (programmable) curve selection for the 51 function. Improvement to allow spaces in Initializing Message 1 & 2 on General Settings, Front Panel HMI screen in the Settings Explorer. Improved backwards compatibility. Improved Commission Date setting on Run Statistics screen in the Metering Explorer. Added support for CEM-2020H. Added Export to File feature.
BESTCOMSPlus® Version and Date 1.00.07, 11/06 Change Firmware Package Version and Date 1.17.02, 03/13 Change 1.17.00, 01/13 viii Initial release Added new breaker hardware and mains fail transfer settings. Improved breaker hardware, synch check, and mains fail logic. Added a logic element which allows the EPS Supplying Load front panel LED to be driven via logic. Improved event log processing rate. Improved CAN transmit processing rate.
Firmware Package Version and Date 1.15.00, 06/12 Change Added Russian language support. Added Auto Breaker Operation Inhibit, Mains Fail Transfer Inhibit, and Closed Transition Override logic elements. Added Restart Delay setting. Added SPN Conversion Method Increased Max on Weak Battery and Low Battery Pre-alarms. 14 V for 12 V systems and 28 V for 24 V systems.
Firmware Package Version and Date 1.10.00, 03/10 Change 1.09.00, 07/09 1.08.01, 01/09 x Corrected transmittal of parameters to engine for MDEC module types 201, 302, and 303. Implemented most recent MTU fault codes. Engine Total Run Time in metering now displays hours and minutes. Engine Total Run Time previously displayed hours only. Added front panel diagnostics to show Modbus Read Count, Modbus Write Count, and Serial Flash Write Count.
Firmware Package Version and Date Change 1.06.00, 07/08 Added settings for AEM-2020. Added settings for Automatic Generator Detection. Added settings for Integrating Reset on 51 function. Added settings for Configurable Protection. 1.05.00, 04/08 Added settings for CEM-2020. 1.04.00, 12/07 Added settings for LSM-2020. 1.03.00, 08/07 Added 32 and 40Q protection functions. Added Automatic Restart function and Exercise Timer.
xii DGC-2020 Introduction 9400200990 Rev U
DETAILED FIRMWARE RELEASE HISTORY Digital Genset Controller (DGC-2020) Pkg. File Ver. Application Code Version & P/N Load Share Module (LSM-2020) Flash Language Module CANbus App. Ethernet App. Contact Expansion Module (CEM-2020/H) Analog Expansion Module (AEM-2020) Version & P/N Lang.* Version & P/N Version & P/N Version & P/N Version & P/N 5.04.01 02/20/13 9400201078 E,C,R S,F 1.03.01 03/13/13 9417501024 1.03.01 03/13/13 9417501025 1.01.04 02/14/13 9421001014 1.00.
Digital Genset Controller (DGC-2020) Pkg. File Ver. Application Code Load Share Module (LSM-2020) Flash Language Module CANbus App. Ethernet App. Contact Expansion Module (CEM-2020/H) Analog Expansion Module (AEM-2020) Version & P/N Version & P/N Lang.* Version & P/N Version & P/N Version & P/N Version & P/N 1.04.00 1.03.00 11/21/07 9400201022 2.01.00 11/15/07 9400201023 E,C,S 1.00.00 11/21/07 9417501005 1.00.00 11/21/07 9417501004 N/A N/A 1.03.00 1.02.00 08/14/07 9400201020 2.01.
CONTENTS SECTION 1 • GENERAL INFORMATION ................................................................................................ 1-1 SECTION 2 • HUMAN-MACHINE INTERFACE ....................................................................................... 2-1 SECTION 3 • FUNCTIONAL DESCRIPTION ........................................................................................... 3-1 SECTION 4 • BESTCOMSPlus® SOFTWARE ............................................................................
xvi DGC-2020 Introduction 9400200990 Rev U
SECTION 1 • GENERAL INFORMATION TABLE OF CONTENTS SECTION 1 • GENERAL INFORMATION ................................................................................................ 1-1 Description ............................................................................................................................................. 1-1 Features ................................................................................................................................................. 1-1 Functions ..
Loss of Excitation (40Q) ................................................................................................................. 1-9 Overcurrent (51) (Optional) ............................................................................................................. 1-9 Phase Imbalance (47) (Optional) .................................................................................................... 1-9 ROCOF (Rate of Change of Frequency) (81) (Optional) ......................................
SECTION 1 • GENERAL INFORMATION Description The DGC-2020 Digital Genset Controller provides integrated engine-genset control, protection, and metering in a single package. Microprocessor based technology allows for exact measurement, setpoint adjustment, and timing functions. Front panel controls and indicators enable quick and simple DGC-2020 operation. Basler Electric communication software (BESTCOMSPlus®) allows units to be easily customized for each application.
Auto-Synchronizer An optional automatic synchronizer monitors the bus and generator voltages and supplies discrete raise/lower correction signals to synchronize the generator voltage, frequency, and slip angle with that of the bus. Contact Inputs and Output Contacts DGC-2020 controllers have one, dedicated emergency stop contact input and 16 programmable contact inputs. All contact inputs recognize dry contacts. The programmable inputs can be configured to initiate a pre-alarm or alarm.
Dial-Out Modem The optional dial-out modem enables remote control, monitoring, and setting of the DGC-2020. When an alarm or pre-alarm condition occurs, the DGC-2020 can dial up to four telephone numbers, in sequence, until an answer is received and the condition is annunciated. RS-485 Port An optional RS-485 communication port uses the Modbus™ communication protocol and enables remote control and monitoring of the DGC-2020 over a polled network.
For example, if a DGC-2020 style number were 51BNBMEAH, the controller would have the following characteristics and operating features.
Voltage Sensing Generator Configuration ................... Line-to-line or line-to-neutral Bus Configuration ............................. Line-to-Line Range ............................................... 12 to 576 V rms, line-to-line Frequency ......................................... Style selectable, 50/60 Hz or 400 Hz Frequency Range ............................. 10 to 72 Hz for 50/60 style and 10 to 480 Hz for 400 Hz style Burden ............................................. 1 VA 1 Second Rating ....
Oil Pressure Sensing Resistance Range ............................ 0 to 250 Ω nominal Terminals .......................................... 8, 11 (sender common) Engine Speed Sensing Magnetic Pickup Voltage Range .................................. 3 to 35 V peak (6 to 70 V peak-peak) Frequency Range ............................. 32 to 10,000 Hz Terminals .......................................... 31 (+), 32 (–) Generator Voltage Range 12 to 576 V rms Terminals ..........................................
Generator Current (rms) Generator current is measured at the secondary windings of user-supplied 1 A or 5 A CTs. Metering Range ................................ 0 to 5,000 Aac CT Primary Range ............................ 1 to 5,000 Aac in primary increments of 1 Aac Accuracy* ......................................... ±1.0% of programmed rated current or ±2 Aac Display Resolution ............................ 1 Aac * Current metering indicates 0 A when generator current is below 2% of the full-scale rating.
Oil Pressure Metering Range ................................ 0 to 150 psi, 0 to 10.3 bar, or 0 to 1,034 kPa Accuracy ........................................... ±3% of actual indication or ±2 psi, ±0.12 bar, or ±12 kPa (subject to accuracy of sender) Display Resolution ............................ 1 psi, 0.1 bar, or 1 kPa Coolant Temperature Metering Range ................................ 32 to 410°F or 0 to 204°C Accuracy ...........................................
Reverse Power (32) Pickup Range ................................... –50 to 5% of Genset kW Rating Pickup Increment .............................. 0.1% Hysteresis Range ............................. 1 to 10% of Genset kW Rating Hysteresis Increment ........................ 0.1% Activation Delay Range .................... 0 to 30 s Activation Delay Increment ............... 0.1 s Loss of Excitation (40Q) Pickup Range ................................... –150 to 0% of Rated kvar* Pickup Increment .............
Stop Bits ........................................... 1 Terminals .......................................... 14 (A), 13 (B), and 12 (shield) RDP-110 Minimum Wire Size ........................... 20 AWG Maximum Wire Length ...................... 4,000 feet (1,219 meters) Terminals .......................................... 6 (RDP TXD–), 7 (RDP TXD+) CANbus Differential Bus Voltage .................... 1.5 to 3 Vdc Maximum Voltage .............................
LCD Heater The ambient temperature is monitored by a temperature sensor located near the LCD inside the DGC2020. The LCD heater turns on when the ambient temperature falls below 0°C (32°F). The heater turns off when the ambient temperature rises above 5°C (41°F). This range of operation implements 5°C (9°F) of hysteresis between heater turn on and turn off. Type Tests Shock and Vibration ......................... EN60068-2-6 Dielectric Strength ............................ IEC 255-5 Impulse ...............
CSA Certification CSA certified per Standard CAN/CSA-C22.2 No. 14. NFPA Compliance Complies with NFPA Standard 110, Standard for Emergency and Standby Power.
SECTION 2 • HUMAN-MACHINE INTERFACE TABLE OF CONTENTS SECTION 2 • HUMAN-MACHINE INTERFACE ....................................................................................... 2-1 Introduction ............................................................................................................................................ 2-1 Front Panel.............................................................................................................................................
ii DGC-2020 Human-Machine Interface 9400200990 Rev U
SECTION 2 • HUMAN-MACHINE INTERFACE Introduction This section describes the components of the DGC-2020 human-machine interface (HMI). DGC-2020 HMI components are located on the front panel (controls and indicators) and the rear panel (terminals and connectors). Front Panel Figure 2-1 illustrates the front panel HMI of the DGC-2020. Table 2-1 lists the call-outs of Figure 2-1 along with a description of each HMI component. Figure 2-1.
Table 2-1. Front Panel HMI Descriptions Locator Description A Liquid Crystal Display. The backlit, 64 by 128 pixel LCD serves as the local information source for metering, alarms, pre-alarms, and protective functions. Display operation is maintained at −40°C. B Not in Auto Indicator. This red LED lights when the DGC-2020 is not operating in Auto mode. C Alarm Indicator. This red LED lights continuously during alarm conditions and flashes during pre-alarm conditions. D Supplying Load Indicator.
appears in the list of SETTINGS. To logout, navigate to SETTINGS, LOGOUT and press the Edit key. The LOGOUT selection is removed from the SETTINGS list. Permissions If communications access is active through the modem or USB, the front panel will display REMOTE COMMS, FRONT PANEL IS READ ONLY and the summary screen. This informs the user that the front panel can only be used for viewing metering data and settings information. Remote access must be ended before modifying settings through the front panel.
• kW A • kW B • CHRG AIR TMP • ENGINE % LOAD Sleep Mode Sleep mode serves as a power saving feature. If the DGC-2020 is in Off mode or Auto mode not running and a key is not pressed for more than 15 minutes, the front panel LCD backlight and LCD heater are turned off. The DGC-2020 resumes normal display operation when any front panel button is pressed or the genset is started remotely via the ATS input. The DGC-2020 will not go to sleep while in an Alarm state.
● ● ● ● ● ● ● ● GEN AMPS B GEN AMPS C BUS V BUS FREQ SYNCHRONIZER ○ SLIP ANGLE ○ DELTA HERTZ ○ DELTA VOLTS ○ STATUS MAX VECT SHIFT (Optional) MAX ROCOF (Optional) ROCOF (Optional) POWER ● ● ● ● ● ● ● ● ● ● ● ● ● kW A kW B kW C kW TOTAL kVA A kVA B kVA C kVA TOTAL kvar A kvar B kvar C kvar TOTAL PF BIAS CONTROL (Visible when LSM-2020 is enabled.
○ UNLOADED RUN TIME ■ HOURS ■ MINUTES ALARMS-STATUS ● ● ● ● 2-6 ACTIVE ALARMS ACTIVE PRE-ALARMS MTU FAULT CODES (Visible when ECU is configured for MTU MDEC, MTU ADEC, or MTU ECU7/ECU8.) MTU STATUS (Visible when ECU is configured for MTU MDEC, MTU ADEC, MTU ECU7/ECU8, or MTU Smart Connect.) ○ NMT-ALIVE STATUS (Visible when ECU is configured for MTU MDEC or MTU ECU7/ECU8.) ■ SPS_NODE ■ SW_TYP ■ SW_VAR ■ SW_ED1 ■ SW_ED2 ■ REV ■ SW_MOD ○ TRIP FUEL (Visible when ECU is configured for MTU ECU7/ECU8.
■ ■ ■ ■ ■ ■ ■ ○ RESRV PWR % (Visible when ECU is configured for MTU ECU7/ECU8.) START SEQ (Visible when ECU is configured for MTU ECU7/ECU8 or MTU Smart Connect.) ECU OVRD FDBK (Visible when ECU is configured for MTU Smart Connect.) COOLNT PRHT DONE (Visible when ECU is configured for MTU Smart Connect.) REQ TORQUE (Visible when ECU is configured for MTU Smart Connect.) EXT STOP (Visible when ECU is configured for MTU Smart Connect.) OPERATING MODE (Visible when ECU is configured for MTU Smart Connect.
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ● ● ● ● ● ● ● 2-8 FUEL LEAK DETECT (Visible when the Fuel Leak Detect programmable function is configured to be driven by an input.) GRND DELTA O-RIDE (Visible when Generator Connection is configured for Delta and the Grounded Delta Override programmable function is configured to be driven by an input.) 1 PHASE O-RIDE (Visible when the 1-Phase Override programmable function is configured to be driven by an input.
○ ● ● ● ● ● SCALED ■ ALG OUT X (X = 1 to 4) ○ RAW ■ ALG OUT X (X = 1 to 4) ANALOG STATUS (Visible when AEM-2020 is enabled.) CONF ELEMENTS ○ CONFIG ELEMENT X (X = 1 to 8) CONF PROT STATUS EVENT LOG ○ [EVENT NAME] ■ ACTIVE ■ OCCURRENCE COUNT ■ FIRST DATE ■ FIRST TIME ■ LAST DATE ■ LAST TIME ■ FIRST ENG HRS ■ LAST ENG HRS ■ DETAILS □ OCCURRENCE (Use the Edit/Up/Down keys to change the occurrence.) □ DATE □ TIME □ ENG HRS ■ CLEAR EVENT (Visible when logged in through the front panel.
○ ○ ○ ○ ○ ○ ● ● ● ● ● FUEL 1 LEAK FUEL 2 LEAK ALARM RST FDBK ECU SHUTDOWN DEF TANK 1 LVL % DEF TANK 2 LVL % J1939 ENGINE CONFIG (Visible when ECU is configured for Standard, Volvo Penta, MTU ADEC, GM/Doosan, or Cummins.
SETTINGS GENERAL SETTINGS COMMUNICATIONS SYSTEM PARAMS PROGRAMMABLE INPUTS PROGRAMMABLE OUTPUTS CONFIG PROTECTION ALARM CONFIGURATION GENERATOR PROTECTION BREAKER MANAGEMENT BIAS CONTROL MULTIGEN MANAGEMENT (Available when LSM-2020 is enabled.) LOGIC TIMERS ENTER PASSWORD P0059-82 Figure 2-3.
○ ■ ■ ■ ■ ■ ■ FIRMWARE VERSION BOOT CODE VERSION SERIAL NUMBER PART NUMBER MODEL NUMBER BUILD DATE AEM-2020 (Visible when AEM-2020 is enabled.) ■ FIRMWARE VERSION ■ BOOT CODE VERSION ■ SERIAL NUMBER ■ PART NUMBER ■ MODEL NUMBER ■ BUILD DATE COMMUNICATIONS ● CANBUS SETUP ○ CANBUS SETUP ■ CANBUS ENABLE ■ DTC ENABLE (Visible when CANBUS is enabled.) ■ SPN CONV METHOD (Visible when CANBUS is enabled.) ■ CANBUS ADDR (Visible when CANBUS is enabled.) ■ ECU OPT SLCT (Visible when CANBUS is enabled.
□ □ □ □ □ □ □ □ □ ● ● □ GOV PRM SW (Visible when ECU is configured for MTU ADEC or MTU Smart Connect.) ENG STRT PRIME (Visible when ECU is configured for MTU ECU7/ECU8.) FAN OVERRIDE (Visible when ECU is configured for MTU ECU7/ECU8.) MODE SWITCH (Visible when ECU is configured for MTU ECU7/ECU8.) GOV PARAM SET (Visible when ECU is configured for MTU ECU7/ECU8.) CAN RATING SW 1 (Visible when ECU is configured for MTU ECU7/ECU8.) CAN RATING SW 2 (Visible when ECU is configured for MTU ECU7/ECU8.
□ DHCP ENABLE LOAD SHARE DEBUG (Visible when LSM-2020 is enabled.) □ FDBK VOLT □ AUX VOLT □ AUX CURR □ SPEED BIAS □ VOLT BIAS □ WATT DEMAND □ kW TOTAL □ RATED kW □ var DEMAND □ kvar TOTAL □ RATED kvar □ LSM RT BIN □ DGC RT BIN CEM SETUP ■ ENABLE ■ OUTPUTS (Visible when CEM-2020 is enabled.) ■ CANBUS ADDR (Visible when CEM-2020 is enabled.) ■ VERSION INFO (Visible when CEM-2020 is enabled.
○ ○ ○ ○ ○ ● ● ● ● ● ● CONT TIME (Visible when Continuous is selected for Cranking Style.) CYCLE TIME COOLDWN TIME OFF MODE COOLDN PRESTART REST CONFIG ■ CONF ○ OIL PRS CRANK DISC ■ ENABLE ■ CRANK DISC PRS AUTOMATIC RESTART ○ ENABLE ○ ATTEMPTS ○ INTERVAL EXERCISE TIMER ○ MODE ○ RUN WITH LOAD ○ START HOUR ○ START MINUTE ○ RUN HOURS ○ RUN MINUTES SENSING TRANS ○ GEN PT PRI V ○ GEN PT SEC V ○ GEN CT PRI A ○ CT LOW LINE SF (Visible when an input is selected for the Low Line Override programmable function.
■ RECOGNITION (Visible when an INPUT is selected.) 1 PHASE O-RIDE ■ INPUT ■ RECOGNITION (Visible when an INPUT is selected.) ■ 1 PH O-RIDE CFG (Visible when an INPUT is selected.) ○ 1 PHASE AC O-RIDE ■ INPUT ■ RECOGNITION (Visible when an INPUT is selected.) ○ BATT CHRG FAIL ■ INPUT ■ ALARM CONFIG (Visible when an INPUT is selected.) ■ ACTIVATN DLY (Visible when an INPUT is selected.) ■ RECOGNITION (Visible when an INPUT is selected.
□ □ ○ THRESHOLD ALARM CONFIG ■ UNDER 2 □ THRESHOLD □ ALARM CONFIG ■ ARMING DELAY ■ THR1 ACT DLY ■ THR2 ACT DLY ■ HYSTERESIS ■ OOR ALM CFG ■ NAME THRM CPL X (X = 1 to 2) ■ OVER 1 □ THRESHOLD □ ALARM CONFIG ■ OVER 2 □ THRESHOLD □ ALARM CONFIG ■ UNDER 1 □ THRESHOLD □ ALARM CONFIG ■ UNDER 2 □ THRESHOLD □ ALARM CONFIG ■ ARMING DELAY ■ THR1 ACT DLY ■ THR2 ACT DLY ■ HYSTERESIS ■ OOR ALM CFG ■ NAME PROGRAMMABLE OUTPUTS ● ● ● OUTPUTS ○ OUTPUT X (X = 1 to 12) (X = 1 to 36 when CEM-2020 is enabled.
○ ○ ○ ○ ○ ○ ○ ■ ■ THRESHOLD ALARM CONFIG UNDER 1 ■ THRESHOLD ■ ALARM CONFIG UNDER 2 ■ THRESHOLD ■ ALARM CONFIG ARMING DELAY THR1 ACT DLY THR2 ACT DLY HYSTERESIS NAME ALARM CONFIGURATION ● ● HORN CONFIGURATION ○ HORN ○ NOT IN AUTO HORN PRE-ALARMS ○ HIGH COOLANT TEMP ■ ENABLE ■ THRESHOLD ○ LOW COOLANT TEMP ■ ENABLE ■ THRESHOLD ○ LOW OIL PRESSURE ■ ENABLE ■ THRESHOLD ○ LOW FUEL LEVEL ■ ENABLE ■ THRESHOLD ○ ENGINE OVERLOAD ■ ENG kW OVRLD-X (X = 1 to 3) □ ENABLE □ LOW LINE SF (Visible when an input is sel
■ THRESHOLD AVR OUTPUT LIMIT (Visible when LSM-2020 is enabled.) ■ ENABLE ■ ACTIVATN DLY ○ GOV OUTPUT LIMIT (Visible when LSM-2020 is enabled.) ■ ENABLE ■ ACTIVATN DLY ○ INTERGENSET COMM FAIL (Visible when LSM-2020 is enabled.) ■ ENABLE ○ LSM COMM FAIL (Visible when LSM-2020 is enabled.) ■ ENABLE ○ CEM COMM FAIL (Visible when CEM-2020 is enabled.) ■ ENABLE ○ AEM COMM FAIL (Visible when AEM-2020 is enabled.) ■ ENABLE ○ ID MISSING (Visible when LSM-2020 is enabled.
○ ○ ■ ACTIVATN DLY VOLTAGE SENSE FAIL ■ CONFIG TYPE ■ ACTIVATN DLY SPEED SENDR FAIL ■ TIME DELAY GENERATOR PROTECTION ● ● ● ● ● ● 27 UNDERVOLTAGE ○ 27-1 / 27-2 ■ LOW LINE SF (Visible when an input is selected for the Low Line Override programmable function.) ■ 3 / 1 PHASE SETTINGS □ PICKUP □ HYSTERESIS □ TIME DELAY □ FREQ INHIBIT □ ALARM CONFIG 59 OVERVOLTAGE ○ 59-1 / 59-2 ■ LOW LINE SF (Visible when an input is selected for the Low Line Override programmable function.
○ ● ● 3 / 1 PHASE SETTINGS ■ PICKUP ■ HYSTERESIS ■ TIME DELAY ■ ALARM CONFIG 40 LOSS OF EXCITATION ○ 3 / 1 PHASE SETTINGS ■ PICKUP ■ HYSTERESIS ■ TIME DELAY ■ ALARM CONFIG LOSS OF MAINS PROTECT (Optional) ○ 78 VECTOR SHIFT ■ PICKUP ■ ALARM CONFIG ■ OPEN MAINS ON TRP ■ OPEN GEN ON TRP ○ 81 ROCOF ■ PICKUP ■ TIME DELAY ■ ALARM CONFIG ■ OPEN MAINS ON TRP ■ OPEN GEN ON TRP BREAKER MANAGEMENT ● BREAKER HARDWARE ○ MAINS FAIL TRANSFER ■ ENABLE ■ RETURN DELAY ■ TRANSFER DELAY ■ MAX TRANSFER TIME ■ TRANSFER TYPE
■ ● LOW LINE SF (Visible when an input is selected for the Low Line Override programmable function.) ■ ALT FREQ SF ○ GEN FAILED ■ TIME DELAY ○ BUS DEAD ■ THRESHOLD ■ TIME DELAY ○ BUS STABLE ■ OV PICKUP ■ OV DROPOUT ■ UV PICKUP ■ UV DROPOUT ■ OF PICKUP ■ OF DROPOUT ■ UF PICKUP ■ UF DROPOUT ■ TIME DELAY ■ LOW LINE SF (Visible when an input is selected for the Low Line Override programmable function.
■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ● ● kvar ALG MAX (Visible when LSM-2020 is enabled.) kvar ALG MIN (Visible when LSM-2020 is enabled.) PF SETPT (Visible when LSM-2020 is enabled.) PF SRC (Visible when LSM-2020 is enabled.) PF ALG MAX (Visible when LSM-2020 is enabled.) PF ALG MIN (Visible when LSM-2020 is enabled.) KI (Visible when LSM-2020 is enabled and OUTPUT TYPE = ANALOG.) KD (Visible when LSM-2020 is enabled and OUTPUT TYPE = ANALOG.) TD (Visible when LSM-2020 is enabled and OUTPUT TYPE = ANALOG.
○ ○ ○ ● ● ● ● ● MIN OUTPUT MAX OUTPUT VOLT RESPONSE GOV ANALOG OUTPUT ○ OUTPUT TYPE ○ MIN OUTPUT ○ MAX OUTPUT ○ SPD RESPONSE LOAD SHARE LINE ○ MIN VOLTAGE ○ MAX VOLTAGE DEMAND START STOP ○ ENABLE ○ START TD 1 ○ START TD 2 ○ STOP TD ○ START LVL 1 ○ START LVL 2 ○ STOP LVL SEQUENCING ○ SEQUENCE ID ○ MODE ○ MAX GEN START ○ MAX GEN STOP ○ LAST UNIT SHUTDN NETWORK CONFIG ○ EXP SEQ ID X (X = 1 TO 16) LOGIC TIMERS ● TIMER X (X = 1 to 10) ○ HOURS ○ MINUTES ○ SECONDS ENTER PASSWORD LOGOUT (Visible when logge
Rear Panel All DGC-2020 terminals and connectors are located on the rear panel. Rear panel terminals and connectors are illustrated in Figure 2-4. (To show the terminals and connectors, Figure 2-4 shows the DGC-2020 with the rear cover removed.) Table 2-2 lists the call-outs of Figure 2-4 along with a description of each connector type. Figure 2-4.
Table 2-2. Rear Panel HMI Descriptions Locator Description A, D The majority of external, DGC-2020 wiring is terminated at 15-position connectors with compression terminals. These connectors plug into headers on the DGC-2020. The connectors and headers have a dovetailed edge that ensures proper connector orientation. Each connector and header is uniquely keyed to ensure that a connector mates only with the correct header. Connector screw terminals accept a maximum wire size of 12 AWG.
SECTION 3 • FUNCTIONAL DESCRIPTION TABLE OF CONTENTS SECTION 3 • FUNCTIONAL DESCRIPTION ........................................................................................... 3-1 Introduction ............................................................................................................................................ 3-1 DGC-2020 Function Blocks ................................................................................................................... 3-1 Power Supply ............
OFF or AUTO Mode (Not Running) .............................................................................................. 3-18 AUTO Mode (Running) ................................................................................................................. 3-18 Breaker Operation ............................................................................................................................ 3-18 Determining if it is Acceptable to Close a Breaker ...........................................
SECTION 3 • FUNCTIONAL DESCRIPTION Introduction This section describes how the DGC-2020 functions. A detailed description of each function block is provided in the paragraphs under the heading of DGC-2020 Function Blocks. DGC-2020 operating and metering features are described in Section 4, BESTCOMSPlus® Software. DGC-2020 Function Blocks To ease understanding, DGC-2020 functions are illustrated in the block diagram of Figure 3-1. The following paragraphs describe each function in detail.
Circuits relating to the microprocessor inputs are described in the following paragraphs. Zero Crossing Detection The zero crossing of A-phase to B-phase or A-phase to C-phase (user-selectable) line voltage is detected and used to calculate the generator frequency. The zero crossing of A-phase to B-phase bus voltage is used to calculate the bus frequency.
for the programming of sender characteristics. See Section 4, BESTCOMSPlus® Software, for more information. Coolant temperature sender connections are made at terminals 10 and 11 (sender common). Fuel Level A current is provided to the fuel level sender. The developed voltage is measured and scaled for use by the internal circuitry. An open circuit or short circuit across the fuel level sender terminals will cause the DGC-2020 to indicate a failed sender.
of the front panel. If neither is programmed, no indication is given. Programming an input as neither is useful when a programmable input is used as an input to programmable logic. Connections for the programmable inputs are provided at terminals 15 (Input 16) through 30 (Input 1). The negative side of the battery voltage (terminal 2) serves as the return connection for the programmable inputs.
Communication Ports DGC-2020 communication ports include a USB jack, CAN terminals, optional RS-485 terminals, and an optional modem jack. USB The rear-panel, mini-B USB socket enables local communication with a PC running BESTCOMSPlus® software. The DGC-2020 is connected to a PC using a standard USB cable. BESTCOMSPlus® is a Windows® based communication software package that is supplied with the DGC-2020. A detailed description of BESTCOMSPlus® is provided in Section 4, BESTCOMSPlus® Software.
Metric Units English Units Update Rate ∗ SPN Exhaust Temperature B °C °F 500 ms 2434 Fuel Delivery Pressure kPa psi 500 ms 94 1s 1239 1s 1240 100 ms 183 ECU Parameter Fuel Leak Filter 1 Binary (0 or 1) Fuel Leak Filter 2 Binary (0 or 1) Fuel Rate liter/hr gal/hr Fuel Temperature °C °F 1s 174 High Exhaust System Temp (HEST) Lamp/Indicator — — 500 ms 3698 Injection Control Pressure MPa psi 500 ms 164 Injector Metering Rail Pressure MPa psi 500 ms 157 Intake Mani
Metric Units English Units Update Rate ∗ SPN Requested Speed Control Range Upper Limit rpm rpm 5s 536 Requested Torque Control Range Lower Limit % % 5s 537 Requested Torque Control Range Upper Limit % % 5s 538 ECU Parameter ∗ SPN is suspect parameter number. CAUTION When the CANbus is enabled, the DGC-2020 will ignore the following sender inputs: oil pressure, coolant temperature, and magnetic pickup.
Voltage Adjustment Bandwidth 1s N/A Field Current 1s N/A Primary Underfrequency Knee-point 1s N/A Alternate Underfrequency Knee-point 1s N/A Underfrequency Slope 1s N/A ∗ SPN is suspect parameter number. Diagnostic Trouble Codes (DTCs) The DGC-2020 obtains diagnostic engine information from a compatible engine control unit (ECU). The DGC-2020 will receive an unsolicited message of a currently active diagnostic trouble code (DTC). Previously active DTCs are available upon request.
FMI 15 16 17 18 19 String Displayed DATA HI LST SEVERE DATA HI MODERATE SVR DATA LO LST SEVERE DATA LO MODERATE SVR NETWORK DATA ERR Description Data is higher than expected at the least severe level Data is higher than expected at a moderately severe level Data is lower than expected at the least severe level Data is lower than expected at a moderately severe level String Indicating Network Data contained an error indication Table 3-6.
SPN FMI 108 109 109 110 31 1 17 0 Barometrc Prs ERR ENG COOLNT PRS LO LO ENG COOLANT PRS LO ENG COOLNT TMP HI HI 110 110 110 110 110 111 111 111 3 4 15 16 17 1 17 # Cool Tmp Sns Volt HI Cool Tmp Sns Volt LO ENG COOLANT TEMP HI Cool Temp MHI Cool Temp LO Coolnt Lvl LO ENG COOLANT LVL LO LOW COOL LEVEL 157 157 157 157 158 158 158 158 168 3 4 10 17 0 1 15 17 # Fuel Rail Prs Vlt HI Fuel Rail Prs Vlt LO Fuel Rail Prs LOSS Fuel Rl Prs NOT DEV KSW BATT VOLTS HI HI KSW BATT VOLTS LO LO KSW BATT VOLTS HI K
SPN FMI 636 636 636 637 637 637 637 637 637 639 641 641 641 641 651 651 651 651 651 651 652 652 652 652 652 652 653 653 653 653 653 653 654 654 654 654 654 654 655 655 655 655 655 655 656 656 656 656 656 656 657 658 659 6 8 10 2 5 6 7 8 10 # 4 12 13 16 2 5 6 7 13 # 2 5 6 7 13 # 2 5 6 7 13 # 2 5 6 7 13 # 2 5 6 7 13 # 2 5 6 7 13 # # # # String Displayed Pump Pos Sns Curr HI Pump Pos Sns In MSNG Pump Pos Sns In ERR Crank Pos Sns Noisy Crank Pos Sns Curr LO Crank Pos Sns Curr HI Crnk/Pmp Pos Tmg OOS Crank P
SPN FMI String Displayed 660 661 662 663 664 665 666 667 668 669 670 671 672 673 674 676 677 701 702 703 704 705 706 707 708 709 710 711 712 713 714 715 716 898 898 898 923 970 970 971 975 1072 1074 1075 1075 1075 1079 1080 1080 1080 1081 1109 # # # # # # # # # # # # # # # # # # # # # # # # # # # # # # # # # 2 9 # # 2 31 31 # # # 5 6 12 # 3 4 # # 31 CYLINDER 10 INJECTOR CYLINDER 11 INJECTOR CYLINDER 12 INJECTOR CYLINDER 13 INJECTOR CYLINDER 14 INJECTOR CYLINDER 15 INJECTOR CYLINDER 16 INJECTOR CYLINDER
SPN FMI String Displayed Description 1109 # EPS SHUTDN APPROACHG 1110 1136 1136 1136 1172 1172 1172 1180 1180 1231 1235 1237 1322 1323 1324 1325 1326 1327 1328 1329 1330 1331 1332 1333 1334 1335 1336 1337 1338 1339 1340 1341 1342 1343 1344 1345 1346 1347 1347 1347 1569 1638 1639 1639 1639 2000 2005 2030 2071 31 0 15 16 3 4 16 0 16 # # # # # # # # # # # # # # # # # # # # # # # # # # # # 3 5 7 31 # 1 16 18 13 9 9 9 Eng Prot Shutdown ECU Temp EXT HI ENG ECU TEMP HI ECU Temp MHI Trbo Cmp Tmp Volt HI Tr
SPN FMI 2629 2630 2630 2630 2630 2630 2634 2659 2659 2659 2790 2791 2791 2791 2791 2791 2791 2795 3719 15 0 3 4 15 16 # 2 15 17 16 2 3 4 13 31 # 7 0 TURBO 1 OUT TMP HI EGR FrAir Tmp EXT HI EGR FrAir Tmp Vlt HI EGR FrAir Tmp Vlt LO EGR FrAir Tmp HI EGR FrAir Tmp MHI POWER RELAY EGR Flo/Tmp MISMATCH EGR Flo Rt High EGR Flo Rt LO Trbo Cmp Out Tmp HI EGR Vlv Pos Invld EGRVlv Pos In Vlt HI EGRVlv Pos In Vlt LO EGR Vlv Control ERR EGR Valve Cal ERR EGR VALVE CONTROL Trbo Act Pos MSMATCH DPF SOOT LVL EXT HI 3
SPN FMI 523566 523567 523568 523600 523601 523602 523604 523605 523606 523607 523608 523609 523610 523611 523612 523613 523615 523617 # # # # # # # # # # # # # # # # # # String Displayed INJECTN PERIOD CYL 6 INJECTN PERIOD CYL 7 INJECTN PERIOD CYL 8 ECU ERROR ECU ERROR FAN SPEED RXENGTMP CAN MSG TSC1-AE MSG MISSING TSC1-AR MSG MISSING TSC1-DE MSG MISSING TSC1-DR MSG MISSING TSC1-PE MSG MISSING TSC1-VE MSG MISSING TSC1-VR MSG MISSING ECU ERROR RAIL PRESSURE METERING UNIT VALVE ECU ERROR Description Capt
PRESTART This output closes to energize the engine glow plugs. The PRESTART output can be programmed to close up to 30 seconds prior to engine cranking. The PRESTART output can also be programmed to open upon engine startup or remain closed as long as the engine is operating. During the resting state, the PRESTART can be set to Off, On, or Preheat Before Crank.
Mains Fail Transfer Functionality If mains fail transfer is enabled, the unit will run when the utility is determined to be bad, and will not stop until the utility has been determined to be good and the load has been transitioned to the utility. This mode is independent of the other self-starting modes. Run with Load Logic Element When the run with load logic element start input is energized, the unit will start, close its breaker, and take on load at the programmed load rate.
• • Com Request - generated through a communication port using BESTCOMSPlus® or the front panel HMI. Logic Request - generated from BESTlogicPlus. The type of response given for a local request depends on the operating mode of the DGC-2020. RUN Mode When in RUN mode, the generator and mains breakers can be closed manually using contact inputs or the breaker buttons on the BESTCOMSPlus® Control screen.
• The DGC-2020 must be in the process of initiating a breaker close Breaker close sources are: • • • • • The DGC-2020 itself when the automatic transfer (ATS) feature is enabled. The DGC-2020 itself when the Run with Load logic element receives a Start pulse in the programmable logic. The DGC-2020 itself when started from a Demand Start as part of demand start/stop and sequencing.
Similar verification should be performed from the BUS VA and BUS VB terminals on the DGC-2020 to the Phase A and Phase B connections on the bus side of the breaker. It is also required that phase rotation is the same on both sides of the breaker for synchronization to be possible. NOTES When using the DGC-2020 synchronizer, it is recommended that local DGC2020 relay outputs be used for breaker closing commands to minimize the possibility of closures outside of desired breaker closing angles.
Event Recording An event log retains history of system events in nonvolatile memory. Thirty event records are retained and each record contains a time stamp of the first and last event occurrence, and the number of occurrences for each event. In addition, each record contains details of the time, date, and engine hours for the most recent 30 occurrences of the event. The number of occurrences stops incrementing at 99.
Event String ALG IN X O2 (X = 1 to 8) ALG IN X O2 A (X = 1 to 8) ALG IN X O2 P (X = 1 to 8) ALG IN X OOR (X = 1 to 8) ALG IN X OOR A (X = 1 to 8) ALG IN X OOR P (X = 1 to 8) ALG IN X U1 (X = 1 to 8) ALG IN X U1 A (X = 1 to 8) ALG IN X U1 P (X = 1 to 8) ALG IN X U2 (X = 1 to 8) ALG IN X U2 A (X = 1 to 8) ALG IN X U2 P (X = 1 to 8) ATS INPUT CLOSED AUTO RESTART AUTO RESTART FAIL A BATT CHRG FAIL A BATT CHRG FAIL P BATT OVERVOLT P BATTLE OVERRIDE CAN BUS OFF CAN ERROR PASSIVE CEM COMM FAIL P CEM HW MISMATCH P
Event String DPF SOOT LVL EXT HI P DPF SOOT LVL MOD HI P ECU SHUTDOWN A EMERGENCY STOP A ENG kW OVRLD-1 P ENG kW OVRLD-2 P ENG kW OVRLD-3 P ENGINE RUNNING FUEL FLT PRS HI P FUEL LEAK 1 P FUEL LEAK 2 P FUEL LEAK DETECT A FUEL LEAK DETECT P FUEL LEVL SENDR A FUEL LEVL SENDR FAIL FUEL LEVL SENDR P GEN REV ROT GEN TEST LOADED GEN TEST UNLOADED GLBL SNDR FAIL A GN BKR CL FL P GN BKR OP FL P GN BKR SYN FL P HI COOLANT TMP A HI COOLANT TMP P HI DAY TANK LEVEL P HI ECU VOLTS A HI EXHAUSE B T P HI EXHAUST A T P HI P
Event String LO FUEL DLV PRESSURE A LO SUPPLY VOLTS P LOAD TAKEOVER LOGIC OUPUT A LOGIC OUPUT P LOSS OF VOLT LOSS OF VOLT A LOSS OF VOLT P LOSS REM COMS P LOST ECU COMM A LOST ECU COMM P LOW BATT VOLT P LOW CHARGE AIR PRESS P LOW COOL LEVEL A LOW COOL LEVEL P LOW COOL TMP A LOW COOL TMP P LOW COOLANT LEVEL P LOW FUEL DELIV PRESS P LOW FUEL LEVEL A LOW FUEL LEVEL P LOW FUEL RAIL PRESS P LOW OIL PRES A LOW OIL PRES P LOW OIL PRESSURE A LOW OIL PRESSURE P LOW STRG TANK LEVEL P LSM AVR OUT LMT P LSM COMMS FAIL
Event String RTD IN X O2 P (X = 1 to 8) RTD IN X OOR (X = 1 to 8) RTD IN X OOR P (X = 1 to 8) RTD IN X U1 (X = 1 to 8) RTD IN X U1 A (X = 1 to 8) RTD IN X U1 P (X = 1 to 8) RTD IN X U2 (X = 1 to 8) RTD IN X U2 A (X = 1 to 8) RTD IN X U2 P (X = 1 to 8) RUNUP SPD LO P SCREEN ERROR SERFLASH RD FAIL SPD SNDR FAIL SPD SNDR FAIL A SPEED DMD FL P SPEED TOO LOW P SS OVERRIDE ON P START SPEED LOW P THRM CPL X O1 (X = 1 to 2) THRM CPL X O1 A (X = 1 to 2) THRM CPL X O1 P (X = 1 to 2) THRM CPL X O2 (X = 1 to 2) THRM CP
3-26 DGC-2020 Functional Description 9400200990 Rev U
SECTION 4 • BESTCOMSPlus® SOFTWARE TABLE OF CONTENTS SECTION 4 • BESTCOMSPlus® SOFTWARE ......................................................................................... 4-1 Introduction ............................................................................................................................................ 4-1 Installation ..............................................................................................................................................
Alarm Configuration ............................................................................................................................. 4-51 Horn Configuration ........................................................................................................................... 4-51 Pre-Alarms........................................................................................................................................ 4-51 Alarms ......................................................
Figures Figure 4-1. Typical User Interface Components ........................................................................................ 4-1 Figure 4-2. BESTCOMSPlus Select Language ......................................................................................... 4-3 Figure 4-3. Splash Screen ......................................................................................................................... 4-3 Figure 4-4. Communication Pull-Down Menu .....................................
Figure 4-60. Breaker Hardware ............................................................................................................... 4-72 Figure 4-61. Mains Fail ............................................................................................................................ 4-74 Figure 4-63. Bus Condition Detection...................................................................................................... 4-78 Figure 4-64. Synchronizer Screen ..................................
Tables Table 4-1. System Recommendations for BESTCOMSPlus and the .NET Framework ........................... 4-2 Table 4-2. Upper Menu Bar (BESTCOMSPlus Shell) ............................................................................. 4-10 Table 4-3. Lower Menu Bar (DGC-2020 Plugin) ..................................................................................... 4-11 Table 4-4. CANbus Address per ECU Type ............................................................................................
vi DGC-2020 BESTCOMSPlus® Software 9400200990 Rev U
SECTION 4 • BESTCOMSPlus® SOFTWARE Introduction BESTCOMSPlus® is a Windows®-based, PC application that provides a user-friendly, graphical user interface (GUI) for use with Basler Electric communicating products. The name BESTCOMSPlus is an acronym that stands for Basler Electric Software Tool for Communications, Operations, Maintenance, and Settings. BESTCOMSPlus provides the user with a point-and-click means to set and monitor the DGC-2020.
Table 4-1. System Recommendations for BESTCOMSPlus and the .NET Framework Component Recommendation Processor 1.0 GHz RAM 256 MB Hard Drive 25 MB (if .NET Framework is already installed on PC.) 250 MB (if .NET Framework is not already installed on PC.) To install and run BESTCOMSPlus, a Windows user must have Administrator rights. A Windows user with limited rights might not be permitted to save files in certain folders.
Figure 4-2. BESTCOMSPlus Select Language The BESTCOMSPlus splash screen is shown for a brief time. See Figure 4-3. Figure 4-3. Splash Screen The BESTCOMSPlus platform window opens. Select New Connection from the Communication pull-down menu and select DGC-2020. See Figure 4-4. The DGC-2020 plugin is activated automatically after connecting to a DGC-2020. Figure 4-4.
The DGC-2020 Connection screen shown in Figure 4-5 will appear. Figure 4-5. DGC-2020 Connection Select USB via Serial RS232, USB, and enter COM Port. The USB drivers are installed automatically during the BESTCOMSPlus installation process. To select the correct COM Port, open the Windows Device Manager and expand the Ports (COM & LPT) branch. Locate the device named CP2101 USB to UART Bridge Controller (COMx). The COM Port number will be displayed in parenthesis (COMx).
When installation of the driver is complete, you might be asked to restart your computer. Manual Activation of the DGC-2020 Plugin Manual activation of the DGC-2020 plugin is required only if your initial use of BESTCOMSPlus will be on a PC that is not connected to a DGC-2020. Manual activation is described in the following paragraphs. Requesting an Activation Key When initially running the DGC-2020 plugin, the Activate Device Plugin pop-up appears.
DGC-2020 and LSM-2020 are properly linked together. If a USB connection to the DGC-2020 is active, the LSM-2020 enable setting and CANbus address can be found by using the Settings Explorer in BESTCOMSPlus to open the System Parameters, Remote Module Setup tree branch. The DGC-2020 will annunciate a pre-alarm if the LSM-2020 is not connected properly when it is enabled. If the connection is valid, the network settings of the LSM-2020 can be configured through the front panel of the DGC-2020. 2.
5. Use the mouse to highlight the desired Load Share Module and click the Configure button. 6. The Configure Ethernet Port screen appears. See Figure 4-10. Figure 4-10. Configure Ethernet Port 7. Assign an IP Address, Default Gateway, and Subnet Mask to the Load Share Module by entering values in the same range as your network or PC. If DHCP will be used, check the Use DHCP box. 8. Click Send to Device. A password is required. The default password is “OEM”.
3. Click the Edit button to change settings. After settings are configured, click the Edit button again to exit. 4. Use the Left arrow key to navigate back to the LSM Setup screen on the front panel HMI. After leaving the leaving the TCP/IP Settings screen, the LSM-2020 will reboot and use the new settings. Alternate Method to Configure LSM-2020 Network Settings through the DGC-2020 1.
If the LSM-2020 is operating on an isolated network, the Subnet Mask can be left at 0.0.0.0 and the Default Gateway can be chosen as any valid IP address from the same range as the LSM-2020 IP address. 3. Click the Send to Device button located on the Configure Ethernet Port screen. A confirmation popup will be displayed notifying the user that the LSM-2020 will reboot after settings are sent. Click the Yes button to allow settings to be sent.
Advanced Properties Click the Advanced button on the Connection screen to display the Advanced Properties dialog. Default settings are shown in Figure 4-13. Figure 4-13. Advanced Properties Menu Bars The menu bars are located near the top of the BESTCOMSPlus screen (see Figure 4-1). The upper menu bar has five pull-down menus. With the upper menu bar, it is possible to manage settings files, configure communication settings, upload and download settings/security files, and compare settings files.
Menu Item Description Communication New Connection Choose new device or DGC-2020 Close Connection Close communication between BESTCOMSPlus and DGC-2020 Download Settings and Logic from Device Download operational and logic settings from the device Upload Settings and Logic to Device Upload operational and logic settings to the device Upload Settings to Device Upload operational settings to the device Upload Logic to Device Upload logic settings to the device Download Security from Device Down
Enables all metering values to be exported into a *.csv file. Displays a drop-down list entitled Live Mode Settings which enables Live mode where settings are automatically sent to the device in real time as they are changed. Sends settings to the DGC-2020 when BESTCOMSPlus is not operating in Live Mode. Click this button after making a setting change to send the modified setting to the DGC-2020.
General Settings General DGC-2020 settings consist of settings controlling the HMI display and indicators. Additional general settings include style number configuration, DGC-2020 identification, DGC-2020 version information, and device security setup. Front Panel HMI A The contrast of the front panel LCD (liquid crystal display) can be adjusted to suit the viewing angle used or compensate for environmental conditions.
Style Number When a PC operating BESTCOMSPlus is communicating with a DGC-2020, the style number of the DGC-2020 is automatically displayed on the BESTCOMSPlus Style Number screen. When configuring DGC-2020 settings off-line, the style number for the unit to be configured can be entered into BESTCOMSPlus to enable configuration of the required settings. The BESTCOMSPlus Style Number screen is illustrated in Figure 4-15. Figure 4-15.
R S When on-line, read-only information includes the application version , boot code version , application T U V W X build date , serial number , application part number , and model number . The Refresh button is used to update the screen after connecting an optional CEM-2020. BESTCOMSPlus device information values and settings are illustrated in Figure 4-16. Analog Expansion Module Information about an AEM-2020 communicating with BESTCOMSPlus can also be obtained on the Device Info tab of BESTCOMSPlus.
A Application Version: When configuring DGC-2020 settings off-line, the application version for the unit to be configured must be selected. B Application Version: Read-only value obtained when BESTCOMSPlus is communicating with the DGC2020. C Boot Code Version: Read-only value obtained when BESTCOMSPlus is communicating with the DGC2020. D Application Build Date: Read-only value obtained when BESTCOMSPlus is communicating with the DGC-2020.
Device Security Setup Password protection guards against unauthorized changing of DGC-2020 settings. DGC-2020 passwords are case sensitive. Three levels of password protection are available. Each level is described in the following paragraphs. • OEM Access. This password level allows access to all settings. The default, OEM-access password is OEM. • Settings Access. This password level allows all except uploading of firmware and clearing of device event log. The default, settings-access password is SET.
Saving Passwords in a DGC-2020 Settings File The passwords can be modified while BESTCOMSPlus is connected to a DGC-2020, then the settings from the BESTCOMSPlus session can be saved into a settings file. The settings file will contain the new passwords. Also, the passwords in a settings file can be modified off line, saved with the file, and then later loaded into a DGC-2020. Saving passwords to a settings file when BESTCOMSPlus is connected to a DGC-2020 (on line): 1.
14. Enter the password for the highest level of password modified; it should be the new modified password. 15. When passwords are shown, verify they are correct. 16. At this point the password information has been successfully saved in the settings file. The process of saving the passwords into the settings file is complete. Loading Passwords from a Settings File into the DGC-2020 1. Connect to the DGC-2020 with BESTCOMSPlus. 2.
Clock Setup Configuration of daylight saving time and coordination of the local time with universal time (if desired) is A performed on this screen. If required, enter the UTC (Universal Time Coordinates) Offset . Choose the B C D E type of DST Configuration and then set the Start Day , End Day , and Bias . The BESTCOMSPlus Clock Setup screen is illustrated in Figure 4-18. Clock Not Set Warning F When the clock not set warning is enabled, the DGC-2020 will notify the user when the clock is not set.
Communications DGC-2020 communication settings include setup parameters for CANbus, ECU, modem, and RS-485 communication. CANbus Setup The DGC-2020 CANbus interface provides high-speed communication between the DGC-2020 and the A engine control unit (ECU) on an electronically controlled engine. When ECU support is enabled , the DGC-2020 will ignore the analog coolant temperature, oil pressure, and engine speed inputs and rely upon the ECU for these parameters.
Not being able to stop the engine without removing ECU power causes two problems. The first problem is that the only way to stop the engine is to turn the ECU off and wait for the engine speed to decrease below 60 rpm before powering the ECU back on. Otherwise, the engine will take off running. The second problem is that while the ECU is off, you can no longer meter and update coolant level, coolant temperature alarm/pre-alarm, and crank control.
Table 4-5.
setting of Primary results in Secondary being sent and a setting of Secondary results in Primary being sent when the Alternate Frequency Override is true. ∗ The Volvo Penta ECU configuration is applicable only to the EDC3 and EMS2 models of Volvo Penta engine controllers. Cummins When Cummins is selected as the ECU type, the following parameters are sent to the engine via Cummins Proprietary J1939 communications: • • • • Start Request - sent when starting or running the engine.
• • • • • • • • • • • • • • • • S Speed Up - Increases speed of the MTU ECU. T Speed Down - Decreases speed of the MTU ECU. U Idle Request - Turns the idle request on or off. V Increased Idle - Sets the MTU ECU idle. Q Trip Reset - Resets trip information such as trip fuel used, trip hours, trip idle time, etc. R Int Oil Prime - Causes an MTU ECU engine to perform an internal lubrication cycle.
Figure 4-20. ECU Setup A ECU Type: Standard, Volvo Penta, MTU MDEC, MTU ADEC, MTU ECU7/ECU8, GM/Doosan, Cummins, or MTU Smart Connect. B Generator Parameter Transmit: Enable or Disable. C Engine Parameter Transmit: Enable or Disable. D Speed Select: Primary or Secondary. E Accelerator Position: Adjustable from 0 to 100% in 1% increments. F Manual Regeneration: Press to set. G Disable Regeneration: Off or On. H CANbus rpm Request: Enable or Disable.
Voltage Regulator Setup The DGC-2020 transmits voltage setpoint and underfrequency compensation parameters to Marathon ® DVR200E+ voltage regulators. The Voltage Regulator Setup screen is found in the BESTCOMSPlus Settings Explorer under the Communications, CANbus category. The CANbus Parameter Transmit A Enable allows the user to enable or disable the transmission of parameters to the voltage regulator. The B Primary Voltage Setpoint value, represents the normal desired system voltage setpoint.
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • 51-1 Trip Pre-Alarm 51-2 Trip Pre-Alarm 51-3 Trip Pre-Alarm 59-1 Trip Pre-Alarm 59-2 Trip Pre-Alarm 78 Vector Shift Trip 81O Trip Pre-Alarm 81U Trip Pre-Alarm 81 ROCOF Trip AEM Comm Failure Auto Restart Failure Alarm Auxiliary Input X Closed (X = 1 to 16) AVR Output Limit Battery Charger Fail Status Battery Overvoltage Pre-Alarm CEM Comm Failure Common Alarm Common Pre-Alarm Config Element X Status (X = 1 to 8) Coolant Temp Sender Fail Alarm Coolant
Figure 4-22. Modem Setup A Dial Out Number: Accepts a telephone number of up to 16 characters. Pager ID: Accepts a pager identification number of up to 16 characters. C Modem Dialout Conditions: Check boxes to select conditions that will initiate a dial-out message. D Pager Coms Data Format: 7 bit – Even Parity or 8 bit – No Parity. E Pager Buffer Limit: Adjustable from 80 to 200 characters in increments of 40. F Modem Offline Delay: Adjustable from 1 to 240 min in 1 min increments.
C Modbus Address: A value of 1 to 247 can be entered in increments of 1. System Parameters System parameters configure the DGC-2020 for operation with a specific application and are divided into eight categories: system settings and rated data, remote module setup, crank settings, automatic restart, exercise timer, sensing transformers, relay control, and auto config detection.
EPS Threshold Indication that the emergency power system is supplying load is determined by a user-adjustable L threshold setting expressed as a percentage of the genset CT (nominal) primary rating. M The Low Line Scale Factor setting is used to automatically adjust the EPS threshold setting in applications that might utilize more than one type of genset connection.
𝐺𝑒𝑛 𝑃𝑇 𝑆𝑒𝑐𝑜𝑛𝑑𝑎𝑟𝑦 𝑉𝑜𝑙𝑡𝑠 � 𝐺𝑒𝑛 𝑃𝑇 𝑃𝑟𝑖𝑚𝑎𝑟𝑦 𝑉𝑜𝑙𝑡𝑠 𝑅𝑎𝑡𝑒𝑑 𝑆𝑒𝑐𝑜𝑛𝑑𝑎𝑟𝑦 𝑉𝑜𝑙𝑡𝑠 = 𝑅𝑎𝑡𝑒𝑑 𝑉𝑜𝑙𝑡𝑠 � 𝑅𝑎𝑡𝑒𝑑 𝑆𝑒𝑐𝑜𝑛𝑑𝑎𝑟𝑦 𝑃ℎ𝑎𝑠𝑒 𝐴𝑚𝑝𝑠 = 𝑅𝑎𝑡𝑒𝑑 𝑃ℎ𝑎𝑠𝑒 𝐴𝑚𝑝𝑠 � 𝐶𝑇 𝑆𝑒𝑐𝑜𝑛𝑑𝑎𝑟𝑦 𝐴𝑚𝑝𝑠 � 𝐶𝑇 𝑃𝑟𝑖𝑚𝑎𝑟𝑦 𝐴𝑚𝑝𝑠 Figure 4-24. System Settings Figure 4-25. Rated Data A Generator Connection: Delta, Wye, 1-Phase A-B, 1-Phase A-C, or Grounded Delta. Phase Rotation: ABC or ACB. C Genset kW Rating: Adjustable from 5 to 9,999 kW in 1 kW increments.
D Rated Volts: Adjustable from 1 to 99,999 Vac in 1 Vac increments. System Type: Single Generator or Multiple Generator. F Alternate Frequency: Adjustable from 10 to 450 Hz in 0.01 Hz increments. G Rated Power Factor: Adjustable from –1 to +1 in increments of 0.0001. H Speed Signal Source: MPU, Gen Freq, or MPU Freq. I Rated Frequency: 50/60 or 400 Hz. J Rated Engine RPM: Adjustable from 750 to 3,600 in increments of 1. K Number Fly Wheel Teeth: Adjustable from 1 to 500 in increments of 0.1.
B Load Share Module: Enable or Disable. LSM Auxiliary Input Source: Local or System Manager D CEM J1939 Address: Adjustable from 1 to 253 in increments of 1. E Contact Expansion Module: Enable or Disable. F CEM Outputs: 18 Outputs or 24 Outputs. G AEM J1939 Address: Adjustable from 1 to 253 in increments of 1. H Analog Expansion Module: Enable or Disable. C Crank Settings A The DGC-2020 can be programmed for either cycle or continuous engine cranking .
stop the machine immediately, pressing the OFF button twice will cause the unit to go to OFF mode immediately. Furthermore, if an Off Mode Cooldown is in progress and the OFF button is pressed, the unit will immediately shut down. If the unit was in RUN mode when the OFF button was pressed, it remains in RUN for the remainder of the cooldown cycle.
I Oil Pressure Crank Disconnect Enable: Disable or Enable. Crank Disconnect Pressure (psi): Adjustable from 2.9 to 150 psi in 0.1 psi increments, 0.2 to 10.3 Bar in 0.1 Bar increments, or 20 to 1,034.5 kPa in 0.1 kPa increments. K No Load Cool Down Time: Adjustable from 0 to 60 min in 1 min increments. L Off Mode Cool Down Enable: Enable or Disable. M Restart Delay: Adjustable from 0 to 120 s in 1 s increments.
Figure 4-29. Exercise Timer A Mode: Monthly, Weekly, or Daily. Start Day Of Month: Adjustable from 1 to 31 in increments of 1. C Start Day Of Week: Sunday, Monday, Tuesday, Wednesday, Thursday, Friday, or Saturday. D Start Hour: Adjustable from 0 to 23 in increments of 1. E Start Minute: Adjustable from 0 to 59 in increments of 1. F Run Period Hours: Adjustable from 0 to 23 in increments of 1. G Run Period Minutes: Adjustable from 0 to 59 in increments of 1. H Run with Load: Enable or Disable.
factor setting is 2.000, the Gen CT Primary Amps setting will be doubled (2.000 x Gen CT Primary Amps setting). The BESTCOMSPlus Sensing Transformers screen is illustrated in Figure 4-30. Figure 4-30. Sensing Transformers A Gen PT Primary Volts: Adjustable from 1 to 99,999 Vac in 1 Vac increments. Gen PT Secondary Volts: Adjustable from 1 to 480 Vac in 1 Vac increments. C Bus PT Primary Volts: Adjustable from 1 to 99,999 Vac in 1 Vac increments.
Auto Config Detection A When enabled , this feature allows the generator to automatically detect whether the unit is in the configured three-phase configuration, a single-phase AB configuration, or a single-phase AC configuration based on line to neutral (L-N) voltage measurements.
• • • • • • • Contact Inputs Programmable Functions Remote LSM Inputs (Available with an optional LSM-2020 (Load Share Module). Remote Contact Inputs (Available with an optional CEM-2020 (Contact Expansion Module). Remote Analog Inputs (Available with an optional AEM-2020 (Analog Expansion Module). Remote RTD Inputs (Available with an optional AEM-2020 (Analog Expansion Module). Remote Thermocouple Inputs (Available with an optional AEM-2020 (Analog Expansion Module).
• • • • G Single-Phase Override (A-C) - The unit switches to single phase A-C sensing configuration even if the 1 Phase Override Sensing setting is set for A-B. (Note: Applies only when the Single-Phase Override input is invoked.) H Battery Charger Fail - When the selected input is invoked, a user selectable pre-alarm or alarm is annunciated after the activation delay. I Low Coolant Level - When the selected input is invoked, a user selectable pre-alarm or alarm is annunciated after the activation delay.
H Battery Charger Fail: Select Input (None, 1-16), Alarm Configuration (None, Alarm, Pre-Alarm), Activation Delay (s) (0 to 300 s in increments of 1), and Contact Recognition (Always or While Engine Running Only). I Low Coolant Level: Select Input (None, 1-16), Alarm Configuration (None, Alarm, Pre-Alarm), Activation Delay (s) (0 to 300 s in increments of 1), and Contact Recognition (Always or While Engine Running Only).
Figure 4-36. Remote Contact Inputs A Alarm Configuration: None, Alarm, or Pre-Alarm. Activation Delay: Adjustable from 0 to 300 s in 1 s increments. C Label Text: An alphanumeric character string with a maximum of 16 characters. D Contact Recognition: Always or While Engine Running Only. B Remote Analog Inputs An optional AEM-2020 (Analog Expansion Module) provides eight analog inputs. To make identifying the A analog inputs easier, a user-assigned name can be given to each input.
Figure 4-37. Remote Analog Input #1 A Label Text: An alphanumeric character string with a maximum of 16 characters. Input Type: Voltage or Current. C Hysteresis: Adjustable from 0 to 100% in 0.1% increments. D Arming Delay: Adjustable from 0 to 300 s in 1 s increments. E Out of Range Alarm Type: None, Alarm, Pre-Alarm, or Status Only. F Param Min: Adjustable from –9999.0 to +9999.0 in increments of 0.1. G Min Input Current: Adjustable from 4 to 20 mA in 0.1 mA increments.
F Each RTD input can be independently configured to annunciate an alarm, pre-alarm, or status only when G H the RTD input signal falls beyond the threshold . A user-adjustable activation delay setting delays alarm annunciation after the threshold has been exceeded. The remote RTD inputs are incorporated into a BESTlogicPlus programmable logic scheme by selecting them from the I/O group in BESTlogicPlus. For more details, refer to Section 5, BESTlogicPlus Programmable Logic.
The remote thermocouple inputs are incorporated into a BESTlogicPlus programmable logic scheme by selecting them from the I/O group in BESTlogicPlus. For more details, refer to Section 5, BESTlogicPlus Programmable Logic. Remote thermocouple input status is available in BESTlogicPlus Programmable Logic when “Status Only” is selected. The BESTCOMSPlus Remote Thermocouple Input #1 screen is illustrated in Figure 4-39. Figure 4-39.
Figure 4-40. Contact Outputs A Label Text: An alphanumeric character string with a maximum of 16 characters. Configurable Elements Configurable elements are connected to the logic scheme as outputs. The configurable elements are incorporated into a BESTlogicPlus programmable logic scheme by selecting them from the Elements group in BESTlogicPlus. For more details, refer to Section 5, BESTlogicPlus Programmable Logic.
The remote contact outputs are incorporated into a BESTlogicPlus programmable logic scheme by selecting them from the I/O group in BESTlogicPlus. For more details, refer to Section 5, BESTlogicPlus Programmable Logic. The BESTCOMSPlus Remote Contact Outputs screen is illustrated in Figure 4-42. Figure 4-42. Remote Contact Outputs A Label Text: An alphanumeric character string with a maximum of 16 characters.
A Param Selection: Oil Pressure, Coolant Temp, Battery Volts, RPM, Fuel Level, Gen VAB, Gen VBC, Gen VCA, Gen VAN, Gen VBN, Gen VCN, Bus Freq, Bus Volts, Gen Freq, Gen PF, Gen IA, Gen IB, Gen IC, kW A, kW B, kW C, kW Total, kVA A, kVA B, kVA C, kVA Total, Analog Input 1-8, RTD Input 1-8, Thermocouple Input 1-2, Fuel Delivery Pressure, kvar A, kvar B, kvar C, kvar Total, Injector Metering Rail Pressure, Total Fuel Used, Fuel Temperature, Engine Oil Temperature, Engine Intercooler Temperature, Coolant Pressu
Figure 4-44. Configurable Protection #1 A Label Text: An alphanumeric character string with a maximum of 16 characters.
Figure 4-45. Scale Factors A Alternate Frequency Scale Factor: Adjustable from 0.001 to 100 in increments of 0.001. Voltage Low Line Scale Factor: Adjustable from 0.001 to 100 in increments of 0.001. C Current Low Line Scale Factor: Adjustable from 0.001 to 100 in increments of 0.001. B Alarm Configuration DGC-2020 alarms and pre-alarms can be used to annunciate system, genset, and engine sender conditions.
• • • • • • Weak Battery Pre-Alarm Breaker Close Fail Pre-Alarms Breaker Open Fail Pre-Alarms Synchronizer Fail Pre-Alarm 81 ROC DF/DT Rate of Change of Frequency Pre-Alarm 78 Vector Shift Pre-Alarm Active pre-alarms are displayed on the main display of the LCD. The LCD annunciates an active prealarm by alternating the pre-alarm message with the normally displayed data. All pre-alarms are individually displayed, in sequence, by scrolling through the LCD pre-alarms list.
enabled, an engine overload pre-alarm occurs when the metered power level exceeds the threshold setting. The threshold setting is expressed as a percentage of the genset kW rating on the BESTCOMSPlus System Settings tab (DGC-2020, System Parameters, System Settings). The hysteresis setting functions as a pre-alarm dropout by preventing rapid switching of the alarm annunciation.
LSM Comm Failure Q LSM-2020 communication failure pre-alarm settings consist of a single enable/disable setting. If enabled, an LSM-2020 communication failure pre-alarm is annunciated when communication between an optional LSM-2020 and DGC-2020 is lost. ID Missing R ID missing pre-alarm settings consist of a single enable/disable setting . If enabled, an ID missing prealarm is annunciated when an expected sequence ID of an optional LSM-2020 is not detected on the network.
Breaker Close Failure X Y Breaker Close failure pre-alarm settings consist of an enable/disable setting and a monitor setting . If enabled, a Breaker Close Failure pre-alarm is annunciated if the DGC-2020 has issued a breaker close output, and has not received feedback from the breaker status indicating it is closed before the breaker close wait time has elapsed. The Monitor setting determines whether this condition is monitored only during transitions or always.
Figure 4-47.
A High Fuel Level: Enable or Disable, threshold is adjustable from 0 to 150% in 1% increments. Activation delay is adjustable from 0 to 30 s in 1 s increments. B Low Battery Voltage: Enable or Disable, threshold is adjustable from 6 to 14 Vdc (12 Vdc battery) or 12 to 28 Vdc (24 Vdc battery) in 0.1 Vdc increments. Activation delay is adjustable from 1 to 10 s in 1 s increments.
Low Oil Pressure B Low oil pressure alarm settings include an enable/disable setting, an arming time delay, and a threshold setting. If enabled, a low oil pressure alarm is triggered instantaneously when the engine oil pressure decreases below the threshold setting. The arming delay disables the low oil pressure alarm function for a user-adjustable time during engine startup. System units and metric pressure units are configured on the System Settings screen.
E trigger a pre-alarm or alarm. The speed sender fail alarm is always enabled. A user-adjustable time delay is provided for each sender/sensing alarm/pre-alarm. Alarm and pre-alarm annunciations for loss of engine speed signals is not user-programmable and operates as follows. If the MPU (magnetic pickup) or generator frequency is programmed as the sole engine speed source and that signal source fails, an alarm (and shutdown) is triggered.
Undervoltage (27-1, 27-2) Two sets of undervoltage settings are provided for each element: one for three-phase generator connections and one for single-phase generator connections. The pickup setting entered is based on the VT secondary side (DGC-2020). When a single-phase override contact input is received, the DGC-2020 automatically switches from the three-phase undervoltage settings to the single-phase undervoltage settings.
A Pickup: Adjustable from 70 to 576 Vac in 1 Vac increments. Activation Delay: Adjustable from 0 to 30 s in 0.1 s increments. C Alarm Configuration: None, Alarm, Pre-Alarm, or Status Only. D Hysteresis: Adjustable from 1 to 60 Vac in 1 Vac increments. E Inhibit Frequency: Adjustable from 20 to 400 Hz in 1 Hz increments. F Low Line Scale Factor: Adjustable from 0.001 to 3 in increments of 0.001. G Pickup (Per Unit): Adjustable from 0.146 to 1.2.
Figure 4-51. Overvoltage A Pickup: Adjustable from 70 to 576 Vac in 1 Vac increments. Activation Delay: Adjustable from 0 to 30 s in 0.1 s increments. C Alarm Configuration: None, Alarm, Pre-Alarm, or Status Only. D Hysteresis: Adjustable from 1 to 60 Vac in 1 Vac increments. E Low Line Scale Factor: Adjustable from 0.001 to 3 in increments of 0.001. F Pickup (Per Unit): Adjustable from 0.146 to 1.2.
Figure 4-52. Phase Imbalance A Pickup: Adjustable from 5 to 100 Vac in 1 Vac increments. Activation Delay: Adjustable from 0 to 30 s in 0.1 s increments. C Alarm Configuration: None, Alarm, Pre-Alarm, or Status Only. D Hysteresis: Adjustable from 1 to 5 Vac in 1 Vac increments. E Low Line Scale Factor: Adjustable from 0.001 to 3 in increments of 0.001. F Pickup (Per Unit): Adjustable from 0.010 to 0.208.
Per Unit Settings which are related to machine ratings can be set in either actual units of hertz or in per unit K L values. Per unit settings are available for Pickup (81O/81U) and Inhibit Volts (81U). When a native unit is edited, BESTCOMSPlus automatically recalculates the per unit value based on the native unit setting and the rated data parameter (on the System Parameters, Rated Data screen) associated with it.
to the single-phase reverse power protection settings. The 32R element monitors three-phase real power when three-phase sensing is active or single-phase real power if single-phase sensing is active. When the total wattage in the tripping direction (generator absorbing power) is greater than the pickup A B setting for the duration of the 32R activation delay setting , a reverse power condition is annunciated.
Figure 4-55. Generator Capability Curve vs. 40Q Response B If reactive power is within the 40Q tripping region for the duration of the 40Q activation delay setting , a loss of excitation condition is annunciated. A loss of excitation annunciation can be user-selected to C C trigger a pre-alarm (warning) or alarm (shutdown). A loss of excitation annunciation can also be userconfigured to close a programmable output.
Overcurrent Protection (51-1, 51-2, 51-3) Two sets of overcurrent settings are provided for each element: one for three-phase generator connections and one for single-phase generator connections. The pickup setting entered is based on the CT secondary side (DGC-2020). When a single-phase override contact input is received by the DGC2020, the overcurrent protection settings automatically switch from the three-phase settings to the singlephase overcurrent protection settings.
Programmable Curves for Overcurrent Protection Inverse overcurrent characteristics for trip and reset programmable curves are defined by Equation 4-1 and 4-2 respectively. These equations comply with IEEE Std C37.112-1996 - IEEE Standard InverseTime Characteristic Equations for Overcurrent Relays. The curve-specific coefficients are defined for the standard curves as listed in Appendix A, Time Overcurrent Characteristic Curves.
BESTCOMSPlus is used to set the 51-x Programmable Curve Constants. To program the Curve Constants, open the Generator Protection/Current tree branch and select the overcurrent element to be modified. Select P from the Curve pull-down menu and then enter the calculated values for each constant. Programmable curve coefficients can only be entered when the P curve is chosen for the protection element from the Curve drop-down menu. Figure 4-57. Overcurrent A Pickup: Adjustable from 0.9 to 7.
Loss of mains protection is only active when the generator is paralleled to the mains as indicated when the Parallel To Mains logic element is true in BESTlogicPlus. The protection is inhibited for five seconds after Parallel To Mains first becomes true so that transients from closing onto the mains will not cause false trips. To minimize false trips, loss of mains protection is disabled if any configured breakers are not closed.
Figure 4-59. ROCOF (81) A Pickup: Adjustable from 0.2 to 10 Hz/s in 0.1 Hz/s increments. Activation Delay: Adjustable from 0 to 10 s in 0.001 s increments. C Open Mains Breaker on Trip: Enable or Disable. D Open Generator Breaker on Trip: Enable or Disable. E Alarm Configuration: Alarm, Pre-Alarm, or Status Only.
open output. Likewise, if an external source closes the breaker, the DGC-2020 issues a breaker close output. N The dead bus close enable setting enables a machine to close its breaker onto a dead bus. This can be used to make sure only one machine can close onto a dead bus at a time, if desired, preventing multiple machines closing to the dead bus at the same time, potentially out of phase with each other. When this setting is disabled, a machine can only close onto a stable bus.
D Open Pulse Time: Adjustable from 0.01 to 0.80 s in 0.01 s increments. This setting applies only when Contact Type is Pulse. This time should be ≥ the Breaker Closing Time setting. E Close Pulse Time: Adjustable from 0.01 to 0.80 s in 0.01 s increments. This setting applies only when Contact Type is Pulse. This time should be ≥ the Breaker Closing Time setting. F Transition Delay: Adjustable from 0 to 1,000, in increments of 1 second. G Breaker Closing Time: Adjustable from 0 to 800 ms in 5 ms increments.
Closed transition override can be enabled through BESTlogicPlus Programmable Logic. When the Closed Transition Override element is set true, it forces a closed transition due to mains failure, overriding an open Mains Fail Transfer Type setting. Two logic elements are present in BESTlogicPlus Programmable Logic that can be used on a machine configured for mains fail operation to transition the load from the mains to the generator. These two logic elements are Mains Fail Test and Load Take Over.
A Mains Fail Transfer: Enable or Disable. This setting does not apply when generator frequency is 400Hz. Mains Fail Transfer Delay: Adjustable from 0 to 300 s in 1 s increments. This specifies the delay between detection of failed mains to initiation of the transfer to the generator. C Mains Fail Return Delay: Adjustable from 0 to 1,800 s in 1 s increments. This specifies the delay between detection of restored (stable) mains and initiation of the return from the generator back to the mains.
logic element in BESTlogicPlus Programmable Logic. When the Alternate Frequency Override is true, the scale factor setting serves as a multiplier for the pickup settings. For example, if a scale factor contact input is received by the DGC-2020 and the scale factor setting is 2.000, the pickup setting will be doubled (2.000 x PU). K Settings which are related to machine ratings can be set in either actual units voltage or in per unit values.
Once all per unit values are assigned, if the rated data parameters are changed, BESTCOMSPlus automatically recalculates all native unit settings based on the modified rated data parameters. The following settings have native units of Primary Volts, and the rated data associated with them is Rated Volts (on the System Parameters, Rated Data screen).
Figure 4-62. Bus Condition Detection A Dead Gen Threshold: Adjustable from 0 to 4,800 Vac in 1 Vac increments. Dead Gen Activation Delay: Adjustable from 0.1 to 600 s in 0.1 second increments. C Gen Stable Overvoltage Pickup and Dropout: Adjustable from 10 to 99,999 Vac in 1 Vac increments. D Gen Stable Undervoltage Pickup and Dropout: Adjustable from 10 to 99,999 Vac in 1 Vac increments. E Gen Stable Overfrequency Pickup and Dropout: Adjustable from 46 to 64 Hz in 0.
S Bus Failed Activation Delay: Adjustable from 0.1 to 600 s in 0.1 s increments. Low Line Scale Factor: Adjustable from 0.001 to 3 in increments of 0.001. U Alternate Frequency Scale Factor: 0.001 to 100 in increments of 0.001. V Dead Bus Threshold (Per Unit): Adjustable from 0 to 10. T Automatic Synchronizer (Optional) A Two methods of generator synchronization are offered: phase lock loop and anticipatory .
I when breaker closure will be considered. If the Vgen>Vbus setting is enabled, the DGC-2020 will drive the generator voltage to be greater than the bus voltage by an amount equal to the regulation offset setting divided by two. Synchronization Failure The maximum desired duration for synchronizing to take place is established by the sync fail activation J delay setting .
J Sync Fail Activation Delay: Adjustable from 0.1 to 600 s in 0.1 s increments. This is the amount of time the DGC-2020 will allow the synchronizer to attempt to synchronize the generator to the bus before annunciating a Sync Fail pre-alarm. The pre-alarm can be cleared by switching to OFF mode or pressing the Reset button on the front panel of the DGC-2020. K Sync Speed Gain: Adjustable from 0.001 to 1000 in increments of 0.001. L Sync Voltage Gain: Adjustable from 0.001 to 1000 in increments of 0.001.
AA droop gain setting determines the gain factor applied to the voltage droop percentage to compensate for governor differences and achieve desired droop performance. In order to test the operation of droop, the unit must be loaded to full load and the resulting generator voltage should be compared to the desired droop. If it is not possible to load the unit to full load, the droop test can be performed at partial load. The expected voltage is determined by the following equation.
PF Setpoint: Adjustable from –0.60 to 0.60 in increments of 0.01. PF Analog Max: Adjustable from –0.60 to 0.60 in increments of 0.01. T PF Analog Min: Adjustable from –0.60 to 0.60 in increments of 0.01. U Proportional Gain (Kp): Adjustable from 0 to 1,000 in increments of 0.001. V Integral Gain (Ki): Adjustable from 0 to 1,000 in increments of 0.001. W Derivative Gain (Kd): Adjustable from 0 to 1,000 in increments of 0.001. X Derivative Filter Constant (Td): Adjustable from 0 to 1 in increments of 0.0001.
V disable speed droop, set the droop percentage to 0. The speed droop gain setting determines the gain factor applied to the speed droop percentage to compensate for governor differences and achieve desired droop performance. In order to test the operation of droop, the unit must be loaded to full load and the resulting generator speed should be compared to the desired droop. If it is not possible to load the unit to full load, the droop test can be performed at partial load.
G Derivative Gain (Kd): Adjustable from 0 to 1,000 in increments of 0.001. Derivative Filter Constant (Td): Adjustable from 0 to 1 in increments of 0.001. I Loop Gain (Kg): Adjustable from 0 to 1,000 in increments of 0.001. J Speed Trim Enable: Enable or Disable. K Speed Trim Setpoint: Adjustable from 47 to 440 Hz in 0.01 Hz increments. L Remote Speed Bias: User Setting, LSM Analog Input 1, or ALG IN 1 through ALG IN 8. M Remote Speed Bias (%): Adjustable from 0 to 5%, in increments of 0.01.
Governor Output A The governor output of the LSM-2020 is used to change the speed setpoint of the generator. If the B B response is set for increasing, an increased bias will cause faster speed. If the response is set for decreasing, an increased bias will cause slower speed. Settings are provided for minimum output C D E F current , maximum output current , minimum output voltage , and maximum output voltage . The BESTCOMSPlus Governor Output screen is illustrated in Figure 4-69. Figure 4-69.
Figure 4-71. Demand Start/Stop A Demand Start Stop Enable: Enable or Disable. Delayed Start Level: Adjustable from 0 to 1 in increments of 0.001. C Start Level Timeout: Adjustable from 0 to 600 s in 0.1 s increments. D Delayed Stop Level: Adjustable from 0 to 1 in increments of 0.001. E Stop Timeout: Adjustable from 0 to 600 s in 0.1 s increments.
highest start priority. Units in Auto Run mode with the highest number of service hours remaining respond to demand stop requests first. Balanced Service Time If this mode is selected, units will seek to sort the start priority of all non-disabled networked units in ascending order of service hours remaining. In this configuration, a network of units will respond to a demand start request by starting the unit with the greatest number of service hours remaining first.
Network Configuration The sequencing ID of the unit being programmed and the sequencing IDs of all other units on a A networked system should be entered in the expected sequence ID table . If the state of any unit changes to offline and the ID Missing pre-alarm is enabled, an ID Missing pre-alarm appears on the front panel HMI and BESTCOMSPlus metering screen.
Figure 4-74. Coolant Temperature A Sender Points: Accepts up to 11 user-defined sender resistance points. Sender Slope: Positive or Negative causes sender points to be sorted and displayed accordingly. C Sender Point Curve: Automatic plot of sender points data. D Print This Graph: Click to print sender point curve. E Save Cool. Data: Click to save file containing sender point data. F Load Cool. Settings File: Click to clear all user-defined sender data and revert to the factory-default values.
Opening a Settings File To open a DGC-2020 settings file with BESTCOMSPlus, pull down the File menu and choose Open. The Open dialog box appears. This dialog box allows you to use normal Windows techniques to select the file that you want to open. Select the file and choose Open. You can also open a file by clicking on the Open File button on the lower menu bar. If connected to a device, you will be asked to upload the settings and logic from the file to the current device.
Figure 4-75. BESTCOMSPlus Settings Compare Setup A dialog box will appear and notify you if any differences were found. The BESTCOMSPlus Settings Compare dialog box (Figure 4-76) is displayed where you can view all settings (Show All Settings), view only the differences (Show Settings Differences), view all logic (Show All Logic Paths), or view only logic differences (Show Logic Path Differences). Select Close when finished. Figure 4-76.
memory that can be reprogrammed through the communication ports. It is not necessary to replace EPROM chips when updating the firmware with a newer version. Future enhancements to the DGC-2020 functionality will make a firmware update desirable. Because default settings are loaded when DGC-2020 firmware is updated, your settings should be saved in a file prior to upgrading firmware. The language of the front panel LCD can be changed by uploading a different language module into the DGC-2020.
4. Connect to the DGC-2020 through the USB port if not already connected. Firmware upgrades cannot be accomplished through the Ethernet port, with the exception of the LSM-2020. 5. Select Upload Device Files from the Communication pull-down menu. 6. You will be asked to save the current settings file. Select Yes or No. 7. When the Basler Electric Device Package Uploader screen (Figure 4-77) appears, click on the Open button to browse for the device package you have received from Basler Electric.
11. After file(s) have been uploaded, click the Close button on the Basler Electric Device Package Uploader screen and disconnect communication to the DGC-2020. Upgrading Firmware in the DGC-2020 A. Upgrade DGC-2020 firmware and then load a saved settings file. 1. Upgrade the DGC-2020 firmware and language module. a. Connect to the DGC-2020 with BESTCOMSPlus. Check the firmware Application Version on the GENERAL SETTINGS-> VERSION INFO->DGC-2020 screen. b.
Metering Explorer The Metering Explorer is a convenient tool within BESTCOMSPlus used to navigate through the following metering screens of the DGC-2020 plugin.
Figure 4-80. Metering, Docking Options Table 4-8. Explanation of Call-Outs on Figure 4-80 CallOut Symbol Explanation A Holding the left mouse button down on a metering tab and dragging it to one of the four arrow boxes will place it inside the selected window on the location selected. To place the metering tab as a tab inside the selected window, drop it on the tabs button in the center of the arrow buttons.
Engine This screen provides information and metering of engine components. Refer to Figure 4-81. Figure 4-81. Metering, Engine Generator This screen provides metering of generator voltages and currents. Refer to Figure 4-82. Figure 4-82. Metering, Generator Power This screen provides metering of generator power and power factor. Refer to Figure 4-83.
Figure 4-83. Metering, Power Bias Control This screen provides var/PF mode status and operating levels. Refer to Figure 4-84. Figure 4-84. Metering, Bias Control Run Statistics This screen provides Cumulative Run Statistics, Session Run Statistics, and Commission Date. Refer to Figure 4-85. The Hours Until Maintenance pre-alarm is configured on the Pre-Alarms screen in the Settings Explorer. The Hours Until Maintenance field will display “OFF” when the Maintenance Interval pre-alarm is disabled.
Status This screen indicates status of breakers, modes, switches, and I/O connection status. The status is TRUE when the corresponding LED is red. Refer to Figure 4-86. Figure 4-86. Metering, Status Inputs Contact Inputs This screen indicates the status of contact inputs, contact input alarms, and contact input pre-alarms. The status is TRUE when the corresponding LED is red. Refer to Figure 4-87. Figure 4-87.
Remote LSM Inputs When an optional LSM-2020 (Load Share Module) is connected, the value of the analog inputs is displayed on this screen. Voltage is displayed when the input is configured for voltage and current is displayed when the input is configured for current. Refer to Figure 4-88. Figure 4-88.
Remote RTD Inputs When an optional AEM-2020 (Analog Expansion Module) is connected, the status of the remote RTD inputs, remote RTD input alarms, and remote RTD input pre-alarms are shown on this screen. The status is TRUE when the corresponding LED is red. Refer to Figure 4-91. Remote RTD Input #1 is shown. Figure 4-91.
Figure 4-93. Metering, Inputs, Remote Analog Input Values The Calibrate button shown on the Remote Analog Input Values screen opens the Analog Input Temperature Calibration screen shown in Figure 4-94. This screen is used to calibrate RTD inputs 1 through 8 and thermocouple inputs 1 and 2. Figure 4-94.
Logic Control Relays Logic Control Relays This screen indicates the status of logic control relays. The status is TRUE when the corresponding LED is green. Refer to Figure 4-95. Figure 4-95. Metering, Outputs, Logic Control Relays Outputs Contact Outputs This screen indicates the status of contact outputs. The status is TRUE when the corresponding LED is green. Refer to Figure 4-96. Figure 4-96.
Configurable Elements This screen indicates the status of configurable elements. It also indicates alarms and pre-alarms of configurable elements. The status is TRUE when the corresponding LED is green. Refer to Figure 4-97. Figure 4-97. Metering, Outputs, Configurable Elements Remote Contact Outputs When an optional CEM-2020 (Contact Expansion Module) is connected, the status of the remote contact outputs is shown on this screen. The status is TRUE when the corresponding LED is green.
Remote Analog Outputs When an optional AEM-2020 (Analog Expansion Module) is connected, the status of the remote analog outputs, scaled analog output values, and raw analog output values are shown on this screen. The status is TRUE when the corresponding LED is red. Refer to Figure 4-99. Figure 4-99. Metering, Outputs, Remote Analog Outputs Configurable Protection This screen indicates the status of configurable protection. The status is TRUE when the corresponding LED is green. Refer to Figure 4-100.
Alarms This screen indicates the status of Alarms, Pre-Alarms, Sender Fail, and Generator Protection. The status is TRUE when the corresponding LED is red. Alarms and pre-alarms are reset when the DGC-2020 is set to the Off mode. The Sync Fail at Gen Breaker, Gen Breaker Fail to Open, Gen Breaker Fail to Close, Sync Fail at Mains Breaker, Mains Breaker Fail to Open, and Mains Breaker Fail to Close pre-alarms can be reset by pressing the Reset key on the front panel HMI. Refer to Figure 4-101. Figure 4-101.
Figure 4-102. Metering, Event Log, Sorted by Date When viewed with BESTCOMSPlus, the event log can be sorted by Event ID, Description, Occurrence, Date, or Engine Hours. Selecting event log sorted by Date yields a list of all event occurrences in sequential order. This is a view that one would see in a typical “sequence of events” type of event log. Figure 4-102 shows the sequential list resulting from sorting by Date.
J1939 ECU The ECU reports operating information to the DGC-2020 through the CANbus interface when the ECU is configured for Volvo Penta. Operating parameters and diagnostic information, if supported by the ECU, are decoded and displayed on these screens. ECU Data This screen displays ECU Lamp Status and ECU Data. The status is TRUE when the corresponding LED is red. Refer to Figure 4-104. Figure 4-104. Metering, ECU Data Engine Configuration This screen displays Engine Configuration.
Active DTC and Previously Active DTC This screen is used for viewing, downloading, and clearing DTC (Diagnostic Trouble Codes). Refer to Figure 4-106. Figure 4-106. Metering, Download DTC MTU The MTU reports operating information to the DGC-2020 through the CANbus interface when the ECU is configured for MTU. Operating parameters and diagnostic information, if supported by the MTU, are decoded and displayed on these screens. MTU Alarms MTU fault codes are displayed in a scrolling window.
MTU Fault Codes MTU Fault Codes can be viewed and downloaded on this screen. Refer to Figure 4-108. Figure 4-108. Metering, MTU Fault Codes MTU Status MTU Status is reported on this screen. The status is TRUE when the corresponding LED is red. Refer to Figure 4-109. Figure 4-109.
MTU Engine Status MTU Engine Status is reported on this screen. The status is TRUE when the corresponding LED is red. Refer to Figure 4-110. Figure 4-110. Metering, MTU Engine Status Summary This screen displays a metering summary. Refer to Figure 4-111. Figure 4-111.
Control Controls for stopping/starting the engine, controls for opening/closing breakers, and controls for opening/closing switches are accessed through the Control branch. The following controls are available by using the Metering Explorer in BESTCOMSPlus to open the Control branch. Refer to Figure 4-112. A. The user has control to stop the generator in case of emergency by clicking on the Emergency Stop button. B. The engine can be started and stopped by clicking on the Start and Stop buttons. C.
Generator Network Status This screen (Figure 4-114) displays the designated system manager, total number of units, number of units on line, system kW capacity, system total generated kW, system total generated kvar, and sequencing IDs of the LSM-2020’s on the network. This can only be accomplished when an optional LSM-2020 (Load Share Module) is connected to the DGC-2020 and actively communicating to the generator network. Figure 4-114.
• You can check for BESTCOMSPlus updates by visiting www.basler.com. An online form can be completed to obtain a password for downloading the software. • You can use the manual “check for updates” function in BESTCOMSPlus to ensure that the latest version is installed by selecting Check for Updates in the Tools drop-down menu. (An internet connection is required.
4-116 DGC-2020 BESTCOMSPlus® Software 9400200990 Rev U
SECTION 5 • BESTlogic™Plus PROGRAMMABLE LOGIC TABLE OF CONTENTS SECTION 5 • BESTlogic™Plus PROGRAMMABLE LOGIC .................................................................... 5-1 Introduction ............................................................................................................................................ 5-1 Overview of BESTlogic™Plus................................................................................................................ 5-1 BESTlogic™Plus Composition .
ii DGC-2020 BESTlogic™Plus Programmable Logic 9400200990 Rev U
SECTION 5 • BESTlogic™Plus PROGRAMMABLE LOGIC Introduction BESTlogicPlus Programmable Logic is a programming method used for managing the input, output, protection, control, monitoring, and reporting capabilities of Basler Electric's DGC-2020 Digital Genset Controller. Each DGC-2020 has multiple, self-contained logic blocks that have all of the inputs and outputs of its discrete component counterpart.
BESTlogic™Plus Composition There are three main groups of objects used for programming BESTlogicPlus. These groups are I/O, Components, and Elements. For details on how these objects are used to program BESTlogicPlus, see the paragraphs on Programming BESTlogicPlus. I/O This group contains Input Objects, Output Objects, Alarms, Pre-Alarms, Senders, and Logic Control Relays. Table 5-1 lists the names and descriptions of the objects in the I/O group. Table 5-1.
Name Description Status Input ATS Input True when the ATS (Auto Transfer Switch) input is true or the ATS logic element is true. Status Input Audible Horn True when the Audible Horn is active. Status Input Auto Mode True when the DGC-2020 is in Auto Mode or the Auto Mode logic element is true. Status Input Auto Restart True when the Automatic Restart function is active. Status Input Battery Charger Fail True when the Battery Charger Fail input is true.
Name Description Status Input Emergency Stop True when the Emergency Stop button has been pressed. Status Input Engine Running True while the Engine is Running. Status Input EPS Supplying Load True while the EPS is supplying load. Status Input Front Panel Buttons True while the AUTO front panel button is pressed. Status Input Front Panel Buttons True while the DOWN front panel button is pressed. Status Input Front Panel Buttons True while the EDIT front panel button is pressed.
Name Description Status Input Gen Forward Rotation True when the sensed generator phase rotation matches the generator phase rotation specified in the system settings. Status Input Gen Reverse Rotation True when the sensed generator phase rotation differs from the generator phase rotation specified in the system settings. Status Input Generator Protection True when the 27-1 element is tripped. Status Input Generator Protection True when the 27-2 element is tripped.
Name Description Status Input Generator Test Loaded True when the Exercise Timer has started the generator and run with load is selected. Status Input Generator Test True when the Exercise Timer has started the generator. Status Input Global Low Coolant Level True when the Low Coolant Level input is true. Status Input Ground Delta Override True when the Grounded Delta Override input is true. Status Input Idle Request True when the Idle Request logic element is true.
Name Description Status Input Load Take Over True when the Load Take Over logic element is true. Status Input Low Line Override True when the Low Line Override input is true. Status Input Mains Fail Test True when the Mains Fail Test logic element is true. Status Input Mains Fail Transfer Complete True when the DGC-2020 is configured for mains fail transfers and has successfully transferred to the generator from the utility.
Name Description Status Input Sync Active True when the auto synchronizer is active to align the generator input and bus input voltages and phases. Status Input Sync Breaker Close OK True when the auto synchronizer is running and determines that the voltage difference between bus and generator voltages, slip frequency, and phase angle are within specified limits so that it is okay to issue a breaker close command.
Name Description Analog Expansion Module Remote Thermocouple Inputs 1-2 True when Over 1, Over 2, Under 1, Under 2, or Out of Range is configured as an alarm and the threshold has been exceeded. (Over 1 shown.) Auto Restart Fail True after the Automatic Restart function fails to restart the generator. Battery Charger Fail True when the Battery Charger Fail function is configured as an alarm and the activation delay has expired.
Name Description Generator Protection 47 True when the 47 element is configured as an alarm and has tripped. Generator Protection 51-1 True when the 51-1 element is configured as an alarm and has tripped. Generator Protection 51-2 True when the 51-2 element is configured as an alarm and has tripped. Generator Protection 51-3 True when the 51-3 element is configured as an alarm and has tripped. Generator Protection 78 True when the 78 element is configured as an alarm and has tripped.
Name Description Symbol Speed Sender Fail True when the Speed Sender Fail activation delay has expired. Unexpected Shutdown Alarm True when the metered engine speed (RPM) unexpectedly drops to 0 while the engine is running. Voltage Sensing Fail True when the Voltage Sensing Fail is configured as an alarm and the activation delay has expired. Pre-Alarms Analog Expansion Module Analog Expansion Module Comm Fail True when communication from the AEM-2020 to the DGC-2020 has been lost.
Name Description Contact Expansion Module Multiple Contact Expansion Modules Connected True when more than one CEM-2020 is connected. Contact Expansion Module Contact Expansion Module Comm Fail True when communication from the CEM-2020 to the DGC-2020 has been lost. Contact Expansion Module Contact Expansion Modules Hardware Mismatch True when the connected CEM-2020 does not have the same number of outputs as defined on the System Parameters, Remote Module Setup screen in BESTCOMSPlus.
Name Description Diag Trouble Code True when a Diagnostic Trouble Code exists. DPF Regenerate Disabled True when the Diesel Particulate Filter (DPF) lamp status broadcast over CANbus indicates that DPF regeneration is inhibited. DPF Regenerate Required True when the Diesel Particulate Filter (DPF) lamp status broadcast over CANbus indicates that DPF regeneration is required. DPF Soot Level High True when the engine ECU reports via CANbus that Diesel Particulate Filter (DPF) soot level is high.
Name Description Generator Protection 27-2 True when the 27-2 element is configured as a prealarm and has tripped. Generator Protection 59-1 True when the 59-1 element is configured as a prealarm and has tripped. Generator Protection 59-2 True when the 59-2 element is configured as a prealarm and has tripped. Generator Protection 32 True when the 32 element is configured as a prealarm and has tripped. Generator Protection 40 True when the 40 element is configured as a prealarm and has tripped.
Name Description Load Share Module Load Share Module Comm Fail True when communication from the LSM-2020 to the DGC-2020 has been lost. Load Share Module Multiple Load Share Modules Detected True when more than one LSM-2020 is connected. Low Battery Voltage True when the Low Battery Voltage Pre-Alarm settings have been exceeded. Low Coolant Level True when the Low Coolant Level function is configured as a pre-alarm and the activation delay has expired.
Name Description Network ID Missing Error True if an expected sequence ID of an optional LSM2020 is not detected on the network. Expected sequence IDs are entered on the Network Configuration screen. Network ID Repeat Error True if two or more optional LSM-2020’s report the same expected sequence ID. Expected sequence IDs are entered on the Network Configuration screen. Oil Pressure Sender Fail True when the Oil Pressure Sender Fail is configured as a pre-alarm and the activation delay has expired.
Table 5-2. Components Group, Names and Descriptions Name Description Symbol Logic Gates AND Input 0 0 0 1 1 0 1 1 Output 0 0 0 1 NAND Input 0 0 0 1 1 0 1 1 Output 1 1 1 0 OR Input 0 0 0 1 1 0 1 1 Output 0 1 1 1 NOR Input 0 0 0 1 1 0 1 1 Output 1 0 0 0 XOR Input 0 0 0 1 1 0 1 1 Output 0 1 1 0 XNOR Input 0 0 0 1 1 0 1 1 Output 1 0 0 1 NOT (INVERTER) Input 0 1 Output 1 0 Pickup and Dropout Timers Drop Out Timer Used to set a delay in the logic.
Name Description Symbol Latches Reset Priority Latch When the Set input is on and the Reset input is off, the latch will go to the SET (ON) state. When the Reset input is on and the Set input is off, the latch will go to the RESET (OFF) state. If both the Set and Reset inputs are on at the same time, a reset priority latch will go to the RESET (OFF) state. Set Priority Latch When the Set input is on and the Reset input is off, the latch will go to the SET (ON) state.
Name Description 47TRIP (Optional) True when the 47 phase imbalance is in a TRIP condition. Connect to another logic block input. 51-1TRIP (Optional) True when the 51-1 overcurrent is in a TRIP condition. Connect to another logic block input. 51-2TRIP (Optional) True when the 51-2 overcurrent is in a TRIP condition. Connect to another logic block input. 51-3TRIP (Optional) True when the 51-3 overcurrent is in a TRIP condition. Connect to another logic block input.
Name Description ATS When this logic element is true, and the DGC-2020 is in AUTO mode, the generator will run. This can be used in place of the ATS programmable function if it is desired to generate the ATS signal as a combination of programmable logic rather than a simple contact input. If either the ATS logic element is true or the contact mapped to the ATS programmable function is true, and the DGC-2020 is in AUTO mode, the generator will run.
Name COOLSTOPREQ Description Symbol RUN Mode If the unit is in RUN mode when the Cool Stop Request is received, the unit will unload, open its breaker, and go into a cooldown cycle. While in the cooldown cycle, the unit will display “COOL & STOP REQ” in addition to displaying the cooldown timer. After the cooldown timer expires, the unit will go to OFF mode. The Cool Stop Request must be removed before the unit can be run again.
Name Description DPFMANREGEN Diesel Particulate Filter Regeneration is forced manually when the Set input is true. DPFREGENINHIBIT Diesel Particulate Filter Regeneration is inhibited when the Set input is true. EPSSUPPLYINGLD When this element is true and the generator is deemed stable, the EPS Supplying Load LED, on the front panel, is illuminated.
Name GENBRK Description Symbol This element is used to connect the breaker open and close output signals from the DGC-2020 to physical output contacts to open and close the generator breaker, and map breaker status feedback to a contact input. In addition, contact inputs can be mapped to allow switches to be implemented to manually initiate breaker open and close requests. Inputs Status: This input allows a contact input to be mapped that will provide breaker status feedback to the DGC-2020.
Name Description GOVR Can be connected to inputs of other logic blocks. When the Governor is being raised, the Raise output is true. When being lowered, the Lower output is true. IDLEREQUEST When this element is true, the DGC-2020 will send an idle request to the engine ECU on J1939 engines that are equipped to receive such a request. At this time, only Volvo and Cummins are implemented.
Name MAINSBRK Description Symbol This element is used to connect the breaker open and close output signals from the DGC-2020 to physical output contacts to open and close the mains breaker and map breaker status feedback to a contact input. In addition, contact inputs can be mapped to allow switches to be implemented to manually initiate breaker open and close requests.
Name Description MODEM (Optional) Connect the input to the output of another logic block. When true, the Modem will dial out. MTUCYLCUTOUTDISABLE (MTU Cylinder Cutout Disable) When this logic element is true, Cylinder Cutout Disable 1 and Cylinder Cutout Disable 2 are both sent to the engine ECU with true status.
Name Description RDPPROGPREALM2 When true, this element illuminates the Battery Charger Failure LED on the Remote Display Panel RDP-110. When this element is connected in logic, it overrides all other commands to the LED. Otherwise, the LED operates as normal. RESET Reset will be active when this element is true. Reset can also be accomplished by pressing the Reset button on the front panel of the DGC-2020.
Name Description STARTOUTPUT This element is used to drive the start output relay from logic when the Start Output Relay configuration is set to “Programmable”. When the Start Output Relay configuration is set to “Programmable”, the start relay will not close unless logic is used to drive this element. When the Start Output Relay configuration is set to “Predefined”, the start relay is closed according to the predefined start functionality of the DGC-2020.
Sending a Logic Scheme to the DGC-2020 To send settings to the DGC-2020, the DGC-2020 must be connected to a computer through a communications port. Once the necessary connections are made, settings can be uploaded to the DGC2020 by selecting Upload Settings and Logic on the Communication pull-down menu. CAUTION Always remove the DGC-2020 from service prior to changing or modifying the active logic scheme.
Table 5-4. Status LEDs LED Color Definition Orange Logic Save Status (Left LED) Logic Diagram Status (Center LED) Green Logic has NOT changed since last save. Red Requirements NOT met as listed above. Green Red Logic Layer Status (Right LED) Logic has changed since last save. Green Requirements met as listed above. Requirements NOT met as listed above. Requirements met as listed above.
Saving a BESTlogicPlus File After programming BESTlogicPlus settings, click on the Save button to save the settings to memory. Before the new BESTlogicPlus settings can be uploaded to the DGC-2020, you must select Save from the File pull-down menu located at the top of the BESTCOMSPlus main shell. This step will save both the BESTlogicPlus settings and the operating settings to a file. The user also has the option to save the BESTlogicPlus settings to a unique file that contains only BESTlogicPlus settings.
Figure 5-4. Example 1 - AVR Logic Block Connections Example 2 - AND Gate Connections Figure 5-5 illustrates a typical AND gate connection. In this example, Output 11 will become active when the Low Fuel alarm AND the Low Oil Pressure alarm are true. Figure 5-5. Example 2 - AND Gate Connections Example 3 - Multiple Logic Connections In this example, there are two comment boxes, which may be placed on the logic diagram. Double-click a comment box to modify the inside text.
SECTION 6 • INSTALLATION TABLE OF CONTENTS SECTION 6 • INSTALLATION .................................................................................................................. 6-1 General .................................................................................................................................................. 6-1 Product Registration .............................................................................................................................. 6-1 Hardware .....
Table 6-9. Programmable Output Contact Terminals ................................................................................ 6-8 Table 6-10. RS-485 Communication Port Terminals ................................................................................. 6-9 Table 6-11. CANbus Interface Terminals .................................................................................................. 6-9 Table 6-12. RDP-110 Interface Terminals ..............................................................
SECTION 6 • INSTALLATION General DGC-2020 controllers are delivered in sturdy cartons to prevent shipping damage. Upon receipt of a unit, check the part number against the requisition and packing list for agreement. Inspect for damage, and if there is evidence of such, immediately file a claim with the carrier and notify the Basler Electric regional sales office or your sales representative.
Figure 6-2.
Connections DGC-2020 connections are dependent on the application. Incorrect wiring may result in damage to the controller. NOTES Be sure that the DGC-2020 is hard-wired to earth ground with no smaller than 12 AWG copper wire attached to the chassis ground terminal (terminal 1) on the rear of the controller. Operating power from the battery must be of the correct polarity. Although reverse polarity will not cause damage, the DGC-2020 will not operate.
Terminal 68 (IA–) 69 (IA+) 71 (IB–) 72 (IB+) 74 (IC–) 75 (IC+) Description A-phase current sensing input B-phase current sensing input C-phase current sensing input NOTE Unused current sensing inputs should be shorted to minimize noise pickup. Generator Voltage Sensing The DGC-2020 accepts either line-to-line or line-to-neutral generator sensing voltage over the range of 12 to 576 volts, rms line-to-line.
Sender input terminals are listed in Table 6-5. Table 6-5. Sender Input Terminals Terminal Description 8 (OIL) Oil pressure sender input 9 (FUEL) Fuel level sender input 10 (COOLANT) Coolant temperature sender input 11 (SENDER COM) Sender return terminal Emergency Stop Input The emergency stop input is intended for use with a normally closed switch and recognizes an emergency stop input when the connection from terminal 46 (ESTOP) to ground is removed. See Figure 6-3.
ESTOP Button Relay ESTOP (46) DGC-2020 P0066-18 ESTOP (47) Figure 6-4. Interposing Relay Diagram The relay is the type that when the coil is NOT energized, the contacts are open. When the coil is energized, the relay contacts are closed. The ESTOP button is normally closed (i.e. closed when it is NOT pushed). The relay coil is always energized when the ESTOP switch is closed (NOT pushed), so relay contacts are closed in normal operation.
ESTOP Button ESTOP (46) Relay DGC-2020 P0053-93 ESTOP (47) Figure 6-6. Interposing Relay Diagram (Optional ESTOP Wiring Method) The relay is the type that when the coil is NOT energized, the contacts are open. When the coil is energized, the relay contacts are closed. The ESTOP button is normally closed (i.e. closed when it is NOT pushed). The relay coil is always energized when the ESTOP switch is closed (NOT pushed), so relay contacts are closed in normal operation.
Terminal Description 23 (INPUT 8) Programmable contact input 8 24 (INPUT 7) Programmable contact input 7 25 (INPUT 6) Programmable contact input 6 26 (INPUT 5) Programmable contact input 5 27 (INPUT 4) Programmable contact input 4 28 (INPUT 3) Programmable contact input 3 29 (INPUT 2) Programmable contact input 2 30 (INPUT 1) Programmable contact input 1 Output Contacts The DGC-2020 has three sets of fixed-function output contacts: Pre, Start, and Run.
RS-485 Communication Port DGC-2020 controllers with the optional RS-485 communication port (style number xxxRxxxxx) are equipped for polled communication over a Modbus™ network. Twisted-pair, shielded cable is recommended for RS-485 port connections. RS-485 communication port terminals are listed in Table 6-10. Table 6-10.
CEM-2020 (Optional) AEM-2020 (Optional) Bus Stub CAN-H DGC-2020 Engine CAN-L 120 ohm Termination LSM-2020 (Optional) Other Devices 120 ohm Termination P0053-95 Figure 6-7. CANbus Interface with DGC-2020 providing One End of the Bus CEM-2020 (Optional) DGC-2020 Bus Stub CAN-H AEM-2020 (Optional) Engine CAN-L 120 ohm Termination Other Devices LSM-2020 (Optional) 120 ohm Termination P0053-94 Figure 6-8.
Table 6-12 lists the DGC-2020 terminals that connect to the RDP-110. Table 6-12.
3-Phase Wye Connections for Typical Applications GEN CKT BKR L1 GENERATOR ≤ 480V L2 L3 MAINS CKT BKR L O A D A B C N N Mechanical Senders 68 72 71 75 74 41 39 37 35 45 43 IB+ IB– IC+ IC– GEN VA GEN VB GEN VC GEN VN BUS VA BUS VB IA– 69 IA+ M P U 31 MPU+ 32 MPU– 8 OIL 9 FUEL DGC-2020 COOLANT 11 SENDER COM 46 ESTOP 47 ESTOP 15 INPUT 16 16 INPUT 15 Mains Bkr Status 17 INPUT 14 Gen Bkr Status 18 INPUT 13 Close Mains Breaker 19 INPUT 12 Open Mains Bre
3-Phase Delta Connections for Typical Applications GEN CKT BKR L1 GENERATOR ≤ 480V L2 L3 MAINS CKT BKR L O A D A B C N N Mechanical Senders Emergency Stop 68 72 71 75 74 41 39 37 35 45 43 IB+ IB– IC+ IC– GEN VA GEN VB GEN VC GEN VN BUS VA BUS VB IA– 69 IA+ M P U 31 MPU+ 32 MPU– 8 OIL 9 FUEL DGC-2020 10 COOLANT 11 SENDER COM 46 ESTOP 47 ESTOP 15 INPUT 16 16 17 INPUT 14 Gen Bkr Status 18 INPUT 13 Close Mains Breaker 19 INPUT 12 Open Mains Breaker 2
Single-Phase A-B Connections for Typical Applications GEN CKT BKR L1 GENERATOR ≤ 480V L2 L O A D MAINS CKT BKR A B N N 1 Mechanical Senders Emergency Stop 68 72 71 75 74 41 39 37 35 45 43 IB– IC+ IC– GEN VA GEN VB GEN VC GEN VN BUS VA BUS VB IA– 69 IA+ M P U IB+ 1 31 MPU+ 32 MPU– 8 OIL 9 FUEL 51 DGC-2020 10 COOLANT 11 SENDER COM 46 ESTOP 47 ESTOP 15 INPUT 16 16 INPUT 15 17 INPUT 14 Gen Bkr Status 18 INPUT 13 Close Mains Breaker 19 INPUT 12 2
Single-Phase A-C Connections for Typical Applications GEN CKT BKR L1 GENERATOR ≤ 480V L3 L O A D MAINS CKT BKR A C N N 2 1 Mechanical Senders Emergency Stop 68 72 71 75 74 41 39 37 35 45 43 IB– IC+ IC– GEN VA GEN VB GEN VC GEN VN BUS VA BUS VB IA– 69 IA+ M P U IB+ 1 31 MPU+ 32 MPU– 8 OIL 9 FUEL 51 DGC-2020 10 COOLANT 11 SENDER COM 46 ESTOP 47 ESTOP 15 INPUT 16 16 INPUT 15 17 INPUT 14 Gen Bkr Status 18 INPUT 13 Close Mains Breaker 19 INPUT 12
Connections with AEM-2020, CEM-2020, and LSM-2020 The AEM-2020 (Analog Expansion Module), CEM-2020 (Contact Expansion Module), and LSM-2020 (Load Share Module) are optional modules that may be installed with the DGC-2020. These modules interface to the DGC-2020 via CANbus, thus the CANBUS terminals are the only common connections (Figure 6-13) between the DGC-2020, AEM-2020, CEM-2020, and LSM-2020. Refer to Section 9, LSM2020 (Load Share Module), for independent LSM-2020 connections.
SECTION 7 • SETUP TABLE OF CONTENTS SECTION 7 • SETUP ................................................................................................................................ 7-1 Introduction ............................................................................................................................................ 7-1 DGC-2020 Initial Setup ..........................................................................................................................
Figure 7-21. Settings Explorer, System Parameters, Remote Module Setup Screen ............................ 7-18 Figure 7-22. Settings Explorer, Programmable Inputs, Contact Inputs Screen ...................................... 7-19 Figure 7-23. Settings Explorer, Programmable Inputs, Programmable Functions Screen ..................... 7-20 Figure 7-24. Settings Explorer, Programmable Inputs, Remote LSM Inputs Screen .............................. 7-23 Figure 7-25.
SECTION 7 • SETUP Introduction The following paragraphs provide information for DGC-2020 initial setup, setting up DGC-2020 programmable inputs and outputs, generator and bus breaker control, synchronizer, setting up a DGC2020 and LSM-2020 for a load sharing and kW control application, and mains fail transfer. DGC-2020 Initial Setup The DGC-2020 must be set up with parameters specific to the controlled machine in order to provide the desired machine control and protection.
Communications If the engine has an ECU (electronic control unit) and the DGC-2020 is to communicate with it, the communications must be set up. CANbus Setup (Figure 7-2) 1. Enable ECU Support - Set to Enabled for the DGC-2020 to communicate with the ECU. 2. Enable DTC (Diagnostic Trouble Code) Support - If the ECU is a J1939 ECU, enable DTC support. If the engine ECU does not support it, no diagnostic trouble codes will be logged by the DGC-2020. 3.
ECU Setup (Figure 7-3) 1. ECU Type - For most engines, select Standard. However, there are exceptions. If your engine is a Volvo, select Volvo-Penta. If you have an MTU MDEC, ADEC, ECU-7/ECU8, GM/Doosan, Cummins, or MTU Smart Connect, make the appropriate selection. Depending on the ECU type selected, some parameters may become enabled, allowing you to configure them for the specific engine. No modification of these parameters is required for the initial setup.
announced. If MPU-GEN is selected as rpm source, if the MPU input does not provide valid speed information, the DGC-2020 will switch to generator frequency as the rpm source, annunciate an MPU FAIL pre-alarm, and continue running. 7. NFPA Level - Set this if NFPA level 1 or 2 compliance is required for the machine. Figure 7-4. Settings Explorer, System Parameters, System Settings Screen Rated Data (Figure 7-5) Note: Click the Edit button to change settings. 1.
Figure 7-5. Settings Explorer, System Parameters, Rated Data Remote Module Setup (Figure 7-6) This screen is used to enable any I/O modules that are to be used with the DGC-2020. Refer to the appropriate sections in the DGC-2020 manual for more details regarding the individual I/O modules. Disable all if no modules are present. Figure 7-6. Settings Explorer, System Parameters, Remote Module Setup Screen Crank Settings (Figure 7-7) 1.
accordingly. Refer to the appropriate paragraphs in Section 4, BESTCOMSPlus® Software, for additional information. 5. Oil Pressure Crank Disconnect - This setting provides an alternate method of determining conditions under which crank disconnect should occur. If the machine has no magnetic pick up (MPU) for rpm detection or a failed, MPU, and the DGC-2020 cannot read generator frequency to obtain rpm information, it will use oil pressure as criterion for crank disconnect.
2. Generator PT Secondary Volts - This setting defines the voltage of the potential transformer (PT) secondary. The parameter must be less than 576 Vac because that is the maximum voltage that can be metered by the DGC-2020 voltage inputs. If no PT is used, leave this parameter at its default value. 3. Bus PT Primary Volts - This parameter defines the voltage of the potential transformer (PT) primary. If no PT is used, leave this parameter at its default value. 4.
Figure 7-9. Settings Explorer, System Parameters, Relay Control Screen Auto Config Detection If the machine connection type is not reconfigurable, disregard this setting. However, if a machine is reconfigurable, these parameters define how automatic detection of the generator connection type for some machines is accomplished. Refer to the appropriate paragraphs in Section 4, BESTCOMSPlus® Software, for additional information. See Figure 7-10. Figure 7-10.
Section 4, BESTCOMSPlus® Software, for additional information regarding pre-alarm configuration. See Figure 7-12.
Figure 7-12.
Alarms Examine each of the alarms. Alarm setup is not required to operate the machine, but is likely to be desired to provide shutdowns for machine protection. Enable any desired alarms and enter an appropriate threshold. Set the Activation Delay where possible. The activation delay is the duration that a condition remains in effect before annunciating an alarm. Refer to the appropriate paragraphs in Section 4, BESTCOMSPlus® Software, for additional information regarding alarm configuration.
Figure 7-14. Settings Explorer, Alarm Configuration, Sender Fail Screen Programmable Senders If a DGC-2020 is receiving engine information from an engine ECU, the programmable sender parameters for the coolant temperature and oil pressure senders do not need configured because they have no effect. They are appropriate for resistive senders only. Coolant Temperature (Figure 7-15) 1.
Figure 7-15. Settings Explorer, Programmable Senders, Coolant Temperature Screen Oil Pressure (Figure 7-16) 1. The oil pressure sender can be configured by selecting one of the sender types that come as a part of the BESTCOMSPlus® sender library by clicking on Load Oil Settings File and selecting the appropriate sender. 2.
Figure 7-16. Settings Explorer, Programmable Senders, Oil Pressure Screen Percent Fuel Level (Figure 7-17) 1. The percent fuel level sender is configured by selecting one of the sender types that come as a part of the BESTCOMSPlus® sender library by clicking on Load Fuel Settings File and selecting the appropriate sender. 2.
Figure 7-17. Settings Explorer, Programmable Senders, Fuel Level Screen This completes the discussion of initial DGC-2020 setup parameters that are required prior to running a unit. Initial Setup (Optional) This section discusses some of the basic setup parameters that are not required to start and run the unit, but may be set up to further customize the DGC-2020 to the application. This discussion is not comprehensive; it presents some of the basic setup parameters.
6. Initializing Message 1 - This parameter defines the first line of text that appears on the front panel of the DGC-2020 as it is going through its power up and initializing sequence. 7. Initializing Message 2 - This parameter defines the second line of text that appears on the front panel of the DGC-2020 as it is going through its power up and initializing sequence. Figure 7-18.
Clock Setup Configure the date and time for the DGC-2020. The daylight-savings time parameters are also configured on this screen. See Figure 7-20. Figure 7-20. Settings Explorer, General Settings, Clock Setup Screen This completes the discussion of optional DGC-2020 setup parameters. This discussion is not comprehensive; it presents some of the basic setup parameters.
Enable LSM-2020, CEM-2020, and AEM-2020 The parameters for remote inputs and remote outputs are disabled and cannot be configured in BESTCOMSPlus® until after the appropriate module has been enabled. Thus, expansion modules connected to the DGC-2020 must be enabled before the associated parameters can be modified. See Figure 7-21. Figure 7-21. Settings Explorer, System Parameters, Remote Module Setup Screen Configure the following parameters: 1.
Figure 7-22.
For each contact input, configure the following parameters: 1. Alarm Configuration - Select None, Alarm, or Pre-Alarm. When an alarm occurs, the horn output annunciates with a constant beep and the engine shuts down. When a pre-alarm occurs, the horn output annunciates with an alternating on and off beep and the engine remains running. If None is selected, the input is status only. The status is available to BESTlogicPlus Programmable Logic regardless of Alarm Configuration setting. 2.
Configure the following parameters: 1. Auto Transfer Switch a. Input - This function is used to start the generator from a contact input when the DGC-2020 is in AUTO mode. Select the desired input or select None to disable the programmable function. b. Contact Recognition - Select Always. 2. Grounded Delta Override a.
Charger Fail indicator on the RDP-110 (Remote Display Panel) will illuminate. Select None to disable the programmable function. b. Alarm Configuration - Select None, Alarm, or Pre-Alarm for the desired behavior of this function. Regardless of the selection, the indicator on the RDP-110 will illuminate if an input has been assigned and the input is on. c. Activation Delay - Set the delay for which the input must be true before the alarm or prealarm will be annunciated.
Configuring Remote LSM Inputs on the LSM-2020 (Load Share Module) The LSM-2020 has one analog input. It is reserved for use with kW and/or kvar control and can be used as a source for the kW Base Load (%) setting, the kvar Setpoint (%) setting, or the PF Setpoint setting. However, the input type (4-20 mA or 0-10 Vdc) and the input range must be set on the Remote LSM Inputs screen in BESTCOMSPlus®. See Figure 7-24. Figure 7-24.
Configuring Remote Contact Inputs on the CEM-2020 (See Figure 7-25) The settings of this screen are disabled unless the CEM-2020 (Contact Expansion Module) has been enabled as previously explained. Figure 7-25. Settings Explorer, Programmable Inputs, Remote Contact Inputs Screen For each contact input, configure the following parameters: 1. Alarm Configuration - Select an alarm configuration of None, Alarm, or Pre-Alarm.
2. Activation Delay - This parameter defines how long the input remains on before any annunciation occurs. 3. Label Text - Enter descriptive text that signifies the use of the input. This text appears next to the input in BESTlogicPlus Programmable Logic and in the event log if the input is configured as an Alarm or Pre-Alarm. 4. Contact Recognition - Select whether the contact input should be recognized always, or only while the engine is running.
2. Hysteresis (%) - Enter a value for the desired hysteresis for threshold detection. This helps prevent intermittent detection of thresholds. 3. Input Type - Select Voltage for 0-10 Vdc inputs or Current for 4-20 mA current inputs. 4. Arming Delay - The Arming Delay is the wait time after engine startup, before input monitoring begins. Set the arming delay to zero if constant monitoring is desired, including while the engine is not running.
g. Under Threshold Alarm Configuration - Select None to disable, Status Only to make the threshold status available to BESTlogicPlus Programmable Logic, Pre-Alarm to annunciate a pre-alarm, or Alarm to annunciate an alarm. h. Over Threshold - This parameter defines when Status, Alarm, or Pre-Alarm annunciation is desired. i.
5. Out-of-Range Alarm Type - An out-of-range condition occurs when the DGC-2020 detects that the input is outside of the normal range of what is detected for the RTD type. Primarily this provides indication of an open or shorted RTD circuit. If Alarm or Pre-Alarm is selected, annunciation will occur. If Status Only is selected, the status is available to BESTlogicPlus Programmable Logic but annunciation will not occur. 6.
Programmable Outputs The programmable outputs consist of: • • • • Contact outputs internal to the DGC-2020 o Programmable contact outputs o Run relay, Pre-Start relay, and Start relay outputs Remote contact outputs on the CEM-2020 Remote analog outputs on the AEM-2020 Configurable elements in the DGC-2020. Configurable elements allow one to take an output from BESTlogicPlus Programmable Logic and set it up as a pre-alarm or alarm condition, as well as an input for subsequent logic in the PLC program.
Figure 7-30. Settings Explorer, System Parameters, Relay Control Screen For each relay (Start, Run, and Pre-Start), select whether it should use its predefined functionality or be made programmable. When Programmable is selected for a relay, it becomes available to BESTlogicPlus Programmable Logic as a logic element. The elements are titled Start Output, PreStart Out, and Run Output. The predefined functionality is available as an input to the logic.
Figure 7-32. Settings Explorer, Programmable Outputs, Configurable Elements Screen The parameters for configurable elements are similar to those for programmable inputs. Set the following parameters for each configurable element: 1. Alarm Configuration - Select None, Alarm, or Pre-Alarm. When an alarm occurs, the horn annunciates with a constant high-pitched sound and the engine stops. When a pre-alarm occurs, the horn annunciates with an alternating on and off beep and the engine remains running.
Figure 7-33. Using a Configurable Element Logic Diagram Input 5, configured as a Pre-Alarm, triggers a pre-alarm if the door is opened whether the engine is running or stopped. Configurable Element 1, configured as an Alarm, triggers an alarm if the door is opened while the engine is running.
the analog output is at the minimum of its output range. Similarly, when the metered parameter is at the maximum of the parameter range, the analog output is at the maximum of its output range. The parameters for Remote Analog Output 1 are shown in Figure 7-35. Figure 7-35. Settings Explorer, Programmable Outputs, Remote Analog Outputs Screen Configure the following parameters: 1. Parameter Selection - This setting defines the metered parameter within the DGC-2020 (e.g.
• The unit is in AUTO and one of the following is true: 1. The RUN WITH LOAD logic element is implemented in the logic and it is true. 2. A Run session has been initiated by the exercise timer and the Run With Load check box in the generator exercise timer parameters is checked. 3. Mains Fail Transfer is enabled and utility power has failed. The mains fail transfer is discussed in detail under Mains Fail Transfer.
breaker failures, and/or Mains Breaker Close Fail or Mains Breaker Open Fail will be annunciated for mains breaker failures. b. Generator Breaker. i. Enable Dead Bus Close if it is desired to close to a dead bus. ii. Set the contact type and pulse times if pulsed contacts are used. iii. Set the breaker close time. This is the time used by the anticipatory synchronizer to calculate the advance angle before 0 degrees slip angle that a breaker close command will be issued. c. Mains Breaker. d.
iv. If it is desired to have physical inputs that can request breaker open and close commands, connect the desired inputs to the open and close command inputs of the breaker element. These inputs should be pulsed. If they both close at the same time, the breaker will not change state. If it is not desired to have inputs for breaker commands, connect a “Logic 0” input object to the open and close command inputs of the breaker block. b. Mains Breaker (if configured) i.
Figure 7-38. Settings Explorer, Breaker Management, Bus Condition Detection i. Dead Bus Voltage Threshold and Activation Delay. When the voltage of the generator is below this threshold for the duration equal to the activation delay, the generator is deemed “Dead”. ii. Gen Stable Over and Under Voltage thresholds and Over and Under Frequency thresholds and the Bus Stable and Bus Failed Activation Delay times.
ii. Bus Stable Over and Under Voltage thresholds and Over and Under Frequency thresholds and the Bus Stable and Bus Failed Activation Delay times. When the bus voltage and frequencies are within the specified ranges for the duration equal to the Bus Stable Activation Delay, the bus is deemed “Stable”. Otherwise, it is deemed “Failed”. CAUTION The bus condition parameters are critical because they determine when a breaker can be closed.
Figure 7-39. Settings Explorer, General Settings, Style Number Screen 2. If using a remote module to control the governor or voltage regulator i.e. LSM-2020 or CEM-2020, click on System Parameters then Remote Module Setup. Enable the applicable module. This step is not necessary if you are using the DGC-2020’s available contact outputs for AVR and governor control. See Figure 7-40. Figure 7-40. Settings Explorer, System Parameters, Remote Module Setup Screen 3.
Figure 7-41. Settings Explorer, Programmable Inputs, Contact Inputs Screen 4. Click on Programmable Outputs then Contact Outputs. Select and label the appropriate outputs for Breaker Close (Output 5 is the default) and Breaker Open (Output 6 is the default). If using contact outputs on the DGC-2020 for Governor and Voltage Regulator control, the contact outputs can be labeled here as well. Default logic is Output 9 =GOV Raise, Output 10 = GOV Lower, Output 11 = AVR Raise, and Output 12 = AVR Lower.
a. Breaker Close Wait Time. This is an interval in which it is expected that the breaker will transition from open to closed or closed to open. If it does not change state within the specified time, either a Gen Breaker Close Fail or Gen Breaker Open Fail is annunciated as generator breaker failures, and/or Mains Breaker Close Fail or Mains Breaker Open Fail is annunciated as mains breaker failures. b. Generator Breaker: i. Enable the Dead Bus Close Enable parameter if it is desired to close to a dead bus.
equal to the Bus Stable Activation Delay, the bus input is deemed “Stable”. Otherwise it is deemed “Failed”. Figure 7-44. Settings Explorer, Breaker Management, Bus Condition Detection Screen 7. Next, click on Synchronizer under the Breaker Management section of the Settings Explorer. See Figure 7-45.
Figure 7-45. Settings Explorer, Breaker Management, Synchronizer Screen Anticipatory vs. Phase Lock Synchronizer If Phase Lock Loop synchronization is selected, the synchronizer will drive the angle between the generator and bus toward zero, and will drive the voltage between the generator and the bus so that the difference is less than the allowed difference set by the user. If Anticipatory synchronization is selected, the synchronizer controls the slip frequency between the generator and the bus.
8. Click on Bias Control Settings then AVR Bias Control Settings in the Settings Explorer. If using the DGC-2020 only, select Contact as the bias control output type. Then select either Continuous or Proportional as the bias control output type. If using the DGC-2020 in conjunction with an LSM-2020, you may choose to select Analog as the bias control output type. If this is chosen, you will also be required to enter gains and loop gains of the voltage PID controller.
Figure 7-47. Settings Explorer, Bias Control Settings, Governor Bias Control Settings Screen 10. If using the LSM-2020 to control the voltage regulator with an analog signal, click on Multigen Management and then AVR Output. On this screen, you must select the bias output parameters and levels as required by your voltage regulator. See Figure 7-48. Figure 7-48.
Settings should be entered for each of the following parameters when appropriate: a. Output Type - Select whether the AVR bias signal should be Voltage or Current. b. Response - Select Increasing or Decreasing. Increasing should be selected if an increase in the output parameter results in an increase of generator output voltage. c. Min Output Current (mA) and Max Output Current (mA) - If the Output Type is Current, these parameters must be configured.
Figure 7-50. Settings Explorer, BESTlogicPlus Programmable Logic (Step 12) 13. Next, click on the I/O tab, drag the inputs assigned in step 3 above to the main logic, and connect them to the appropriate input or output of the Generator Breaker block. Note the “Open Gen Breaker” and “Close Gen Breaker” are inputs to the generator breaker block, and are used to request a breaker open or close through contact inputs. The “Gen 52 Open” and “Gen 52 Close” are outputs from the DGC-2020 to the physical breaker.
Figure 7-51. Settings Explorer, BESTlogicPlus Programmable Logic (Step 13) 14. If using the LSM-2020 to bias the voltage regulator and governor, no further setup is necessary. If using contact outputs, the output contacts should be set up to drive these functions. In the programmable logic, click on the Elements tab. Locate and drag the Governor and AVR logic blocks into the main logic. See Figure 7-52.
Figure 7-52. Settings Explorer, BESTlogicPlus Programmable Logic (Step 14) 15. Next, click on the I/O tab and drag the selected output contacts into the main logic. Connect the Governor and AVR blocks to the appropriate outputs. This concludes implementation of the automatic synchronizer. See Figure 7-53.
Figure 7-53. Settings Explorer, BESTlogicPlus Programmable Logic (Step 15) Setting up a DGC-2020 and LSM-2020 for a Load Sharing and kW Control Application The following paragraphs provide information and setup procedures for load sharing and kvar control using the DGC-2020 and LSM-2020.
line voltages contributed by each unit. This average voltage is proportional to the average percentage load of the machines. The goal of a load sharing system is for all machines to share equally on a percentage of capacity basis. To accomplish this, each machine contains a load controller or kW controller, which provides regulation of the machine’s kW output. The setting for each kW controller is derived from the system load share line voltage.
In short, when the generator breaker is open, the kW controller is disabled. When the generator breaker is closed and the unit is not paralleled to the utility, the kW controller’s set point is derived from the load share line. When the generator breaker is closed and the machine is paralleled to the utility, the kW controller uses the Base Load Level (%) setting as its set point.
Step by Step Setup Procedures 1. Wire the DGC-2020, LSM-2020, and any external devices that interact with the DGC-2020 or the LSM-2020. Descriptions of DGC-2020 connections and diagrams showing typical wiring schemes for a DGC-2020 on a generator in various connection schemes (single-phase AB, single-phase AC, Wye, Delta, etc.) are found under Connections.
b. Configure the load share line voltage range. If load sharing to equipment not produced by Basler Electric, the range of load share voltage utilized by the equipment must be determined. If the voltage range set up in the DGC-2020 does not match that of the devices, correct load sharing will not occur. If all devices are Basler Electric devices, a range of 0 to 10 V is a convenient range.
i. Output Type - Select Voltage or Current, depending on the output type. ii. Response - Select Increasing if a higher level of bias causes the AVR to increase generator output voltage; select Decreasing if a higher level of bias causes the AVR to decrease generator output voltage. iii. Min Output Current (mA) - This setting defines the minimum AVR bias current level if the bias Output Type is set to Current. iv.
Figure 7-59. Settings Explorer, Bias Control Settings, Governor Bias Control Settings Screen i. Bias Control Output Type - Select Contact or Analog, according to the machine’s implementation. ii. Bias Control Contact Type - Select Continuous or Proportional, depending on the contact output type. Proportional is a PWM based implementation. The duty cycle increases when more control output is required.
as indicated by the parallel to mains (ParToMains) logic element in BESTlogicPlus Programmable Logic. vi. Speed Controller Gains (Kp, Ki, Kd, Td, Kg) - There are four Proportional - Integral Derivative (PID) controllers involved when a DGC-2020 and LSM-2020 are used in a load sharing or load control system. The gains of the controllers involved with speed control are discussed below. Controller gains are configured as part of the controller tuning procedure.
demand is 80 percent, it will take 8 seconds to come up, etc. This is also the rate at which the machine will ramp down when going off line in a normal machine stop. xiii. Base Load Level (%) - When the kW controller is active, this setting defines the level of the machines rated kW capacity that the DGC-2020 will regulate when the generator is paralleled to the utility as indicated by the parallel to mains (ParToMains) logic element in BESTlogicPlus Programmable Logic. xiv.
Figure 7-60. Settings Explorer, Bias Control Settings, AVR Bias Control Settings Screen i. Bias Control Output Type - Select Contact or Analog, according to the machine’s implementation. ii. Bias Control Contact Type - Select Continuous or Proportional, depending on the contact output type. Proportional is a PWM based implementation. The duty cycle increases when more control output is required.
settings have been configured and is the last step in setting up a DGC-2020 and LSM-2020 for load sharing or load control. The voltage controller gains are: (1) Voltage Controller Kp - Proportional Gain (2) Voltage Controller Ki - Integral Gain (3) Voltage Controller Kd - Derivative Gain (4) Voltage Controller Td - Derivative filter time constant (5) Voltage Controller Kg - Loop Gain, must be nonzero for control to occur vi.
xii. kvar Setpoint (%) - When the kvar controller is in Var Control Mode, this setting defines the level of the machine’s Rated kvar Capacity (calculated from Rated kW and Rated Power Factor) that the DGC-2020 will regulate when the generator is paralleled to the utility as indicated by the parallel to mains (ParToMains) logic element in BESTlogicPlus Programmable Logic. xiii.
Figure 7-61. Settings Explorer, Multigen Management, Demand Start/Stop Screen There are two demand start levels and timeouts. This allows the user to set up a lower system power level with a long timeout for normal generator starts, but if the system power level exceeds a higher level for a shorter time (e.g. a machine has an alarm shut down or some other abnormal system power phenomenon occurs) machines can be brought on quickly.
Figure 7-62. Settings Explorer, Multigen Management, Generator Sequencing Screen Set up the individual parameters according to: (1) Mode - Select the desired generator-sequencing mode. Selections include Disabled, Staggered Service Time, Balanced Service Time, Largest Size First, Smallest Size First, Smallest Unit ID First, and Adopt System Mode. When Disabled, the unit does not participate in sequencing.
Figure 7-63. Settings Explorer, Multigen Management, Network Configuration These settings are the non-zero sequence IDs of all units that are on the inter-genset communications network. This allows the DGC-2020s to annunciate a pre-alarm if a machine is missing (ID Missing pre-alarm) or if an ID is repeated (ID Repeat prealarm) on the network. These pre-alarms help in diagnosing problems with the intergenset communications network. If these pre-alarms are not desired, set all expected sequence IDs to zero.
Mains Fail Transfer The DGC-2020 has an internal ATS feature which allows it to monitor the utility, and when the utility fails, opens the mains breaker, starts the generator, then closes the generator breaker to drive the load. When the utility returns and is deemed stable, it will return the load to the utility power. When using the mains fail transfer feature, the DGC-2020 will control the breakers to open and close them to achieve the transition from the utility to the generator.
iii. Enter the max transfer time. This is the maximum duration allowed for the transfer to be accomplished. If this time is exceeded, a mains fail transfer pre-alarm is annunciated. iv. Configure the Mains Fail Transfer Type setting for open or closed transitions. In open transitions, the generator is not connected directly to the utility at any time.
ii. Connect the breaker element open and close outputs to the contact outputs that will drive the breaker. iii. Connect the physical input or remote input that has the breaker status (closed if breaker is closed, open when breaker is open) to the Status input of the breaker element. This is the only way to indicate breaker status to the DGC-2020. iv.
5. Set the parameters for detecting stable and failed bus and generator under SETTINGS EXPLORERBREAKER MANAGEMENTBUS CONDITION DETECTION. a. Generator Sensing. See Figure 7-67. i. Dead Bus Voltage Threshold and Activation Delay. When the voltage of either the generator or bus is below this threshold for the duration equal the activation delay, the generator or bus is deemed “Dead”. ii.
b. Bus Sensing. See Figure 7-67. i. Bus Stable Over and Under Voltage Thresholds and Over and Under Frequency Thresholds. When the bus input voltage and frequencies are within the specified ranges for the duration equal to the Bus Stable Activation Delay, the bus input is deemed “Stable”. Otherwise, it is deemed “Failed”. CAUTION The bus condition parameters are critical because they determine when a breaker can be closed.
7-70 DGC-2020 Setup 9400200990 Rev U
SECTION 8 • MAINTENANCE AND TROUBLESHOOTING TABLE OF CONTENTS SECTION 8 • MAINTENANCE AND TROUBLESHOOTING .................................................................... 8-1 Maintenance........................................................................................................................................... 8-1 Backup Battery for the Real Time Clock ............................................................................................ 8-1 Troubleshooting ..........................
ii DGC-2020 Maintenance and Troubleshooting 9400200990 Rev U
SECTION 8 • MAINTENANCE AND TROUBLESHOOTING Maintenance Preventative maintenance consists of periodic replacement of the backup battery and periodically checking that the connections between the DGC-2020 and the system are clean and tight. DGC-2020 units are manufactured using state-of-the-art, surface-mount technology. As such, Basler Electric recommends that no repair procedures be attempted by anyone other than Basler Electric personnel.
Step 3. Verify that all Ethernet devices comply with IEC 61000-4 series of specifications for Industrial Ethernet Devices. Commercial devices are not recommended and may result in erratic network communications. USB Port Does Not Operate Properly Step 1. Verify that the proper port of your computer is being used. For more information, refer to Section 4, BESTCOMSPlus® Software, Communication.
Incorrect Measurement or Display of Generator Current Step 1. Verify that all wiring is properly connected. Refer to Section 6, Installation, Connections. Step 2. Ensure that the proper current is present at the DGC-2020 current sensing inputs 68/69, 71/72, and 74/75. Step 3. Verify that the current sensing transformer ratios are correct. Step 4. Confirm that the current sensing transformers are correct and properly installed. Incorrect Display of Engine RPM Step 1.
close commands simultaneously. The breaker will not change state if it is being commanded to open and close at the same time. Step 7: Verify the breaker is receiving a close command. Breaker close command sources are: • • • • • Step 8: The DGC-2020 itself when the automatic transfer (ATS) feature is enabled. The DGC-2020 itself when the RUN WITH LOAD logic element receives a Start pulse in the programmable logic.
Step 8: Verify the wiring to the breaker from the DGC-2020. If it seems OK, you can do a manual close and open by modifying the programmable logic. Map some unused outputs to the OPEN and CLOSE outputs from the Gen Breaker Block in the programmable logic. Map a virtual switch to the logic output that would normally be the breaker close output. Map another virtual switch to the logic output that would normally be the breaker close output.
CLOSE outputs from the Gen Breaker Block in the programmable logic. Map a virtual switch to the logic output that would normally be the breaker close output. Map another virtual switch to the logic output that would normally be the breaker close output. Connect with BESTCOMSPlus®, and exercise the virtual switches using the Control panel located in the Metering Explorer. Never turn open and close on at the same time. This could damage the breaker and/or motor operator.
Synchronizer Active for a Short Time, Then Stops Step 1: Check if a Sync Fail pre-alarm or a Breaker Close Fail pre-alarm is occurring or has occurred. The synchronizer stops acting when such a pre-alarm occurs. Press the Off button or the Reset button on the DGC-2020 front panel to clear these pre-alarms. Step 2: Verify that the Sync Fail Activation delay is sufficiently long to allow the synchronizer to complete the synchronization process.
If the voltage still does not change when varying the bias: • • • Verify that the AVR is equipped and configured to accept bias inputs. Check connections to verify the wiring to the AVR bias is correct. If you have digital voltage regulator, verify it set up and programmed to accept a voltage bias input. Generator Voltage Decreases When AVR Speed Bias is Increased Step 1: Navigate to the SETTINGSMULTIGEN MANAGEMENTAVR OUTPUT screen and set VOLT RESPONSE to DECREASING.
use a relay intended for low voltage, low current applications to preserve signal integrity. Signal relays, not power relays, must be used for this application. Verify the relay contacts are not affecting the signal. Step 8: If speed trim is enabled, verify that the speed trim set point is at the correct value for desired operation. Generators Do Not Share Load Equally Step 1: Verify that load sharing is enabled in SETTINGSBIAS CONTROL SETTINGSGOVERNOR BIAS CONTROL SETTINGSLOAD CONTROL ENABLED.
Step 2: Re-attach load share lines to all LSM-2020s that are part of the load sharing system. Run the SINGLE machine with load, and verify that it loads and unloads correctly, and runs at the correct speed. If the machine slows down when the generator breaker is closed, check the load share line voltage. It should be equal, on a normalized basis, to the normalized kW produced by the generator.
bias output range. If the generator breaker is open, voltage trim and kvar control are disabled, so the output from the LSM-2020 will be the midpoint of the range, indicating the voltage regulator should operate at rated voltage. Any relay contacts that are used to switch load share lines, governor analog speed bias signal, or voltage regulator analog voltage bias signals must use a relays intended for low voltage, low current applications to preserve signal integrity.
• WATT DEMAND: This is the normalized requested kW demand on the generator. It is normalized such that 1.0 indicates the full kW capacity of the generator, 0.5 indicates 50% of the generator’s capacity, etc. When the generator breaker is closed, and the kW controller is enabled, the WATT DEMAND indicates what level of power should be generated. In an island load share system, this will correspond to the normalized value read on the load share lines.
• var DEMAND: This is the normalized requested kvar demand on the generator. It is normalized such that 1.0 indicates the full kvar capacity of the generator, 0.5 indicates 50% of the generator’s capacity, etc. When the generator breaker is closed, and the var/PF controller is enabled, the var DEMAND indicates what level of reactive power should be generated. In an island load share system, this will be determined by the droop characteristics set by the Droop Percentage and Voltage Droop Gain parameters.
number representing the metered states of the CEM-2020 inputs. The left most bit is the first input, etc. AEM DEBUG This screen shows the binary data that is being sent between the AEM-2020 (Analog Expansion Module) and the DGC-2020. The AEM DEBUG screen is located on the front panel at SETTINGSSYSTEM PARAMSREMOTE MODULE SETUPAEM SETUPAEM DEBUG MENU. The following parameters are visible on the AEM DEBUG screen: • DGC TO AEM BP: DGC-2020 to AEM-2020 Binary Points.
SECTION 9 • LSM-2020 (LOAD SHARE MODULE) TABLE OF CONTENTS SECTION 9 • LSM-2020 (LOAD SHARE MODULE) ................................................................................ 9-1 General Information ............................................................................................................................... 9-1 Features ................................................................................................................................................. 9-1 Specifications .
Maintenance ......................................................................................................................................... 9-14 Figures Figure 9-1. Device Info Screen .................................................................................................................. 9-4 Figure 9-2. Device Security Setup Screen ................................................................................................ 9-5 Figure 9-3. LSM-2020 Overall Dimensions ................
SECTION 9 • LSM-2020 (LOAD SHARE MODULE) General Information The LSM-2020 is a remote auxiliary device that interfaces to the DGC-2020 and provides analog outputs to the power system in the form of analog bias signals to the voltage regulator and speed governor. When the breaker is closed and Load Sharing is enabled, the LSM-2020 will share real power load proportionally with the other generators on the Analog Load Share Line.
Load Share Line Output 0-10 Vdc isolated output signal. (Selectable in increments of 0.1 Vdc. Isolated to 500 Vdc between outputs and ground Terminals ................................... P2-6 (LS+), P2-5 (LS–), P2-4 (LS’) Communication Interface CAN Differential Bus Voltage ............. 1.5 to 3 Vdc Maximum Voltage ...................... –32 to +32 Vdc with respect to negative battery terminal Communication Rate ................. 250 kb/s Terminals ...................................
NFPA Compliance Complies with NFPA Standard 110, Standard for Emergency and Standby Power.
Ethernet Port An Ethernet port provides communications via BESTCOMSPlus® to the LSM-2020 and to the DGC-2020 that the module is connected to. Ethernet communication between LSM-2020s allows for generator sequencing on an islanded system. Firmware updates to the LSM-2020 are made through the Ethernet port. Firmware updates to the DGC-2020 are only available through the USB port of the DGC-2020.
C Boot Code Version: Read-only value obtained when BESTCOMSPlus is communicating with the Load Share Module. D Application Build: Read-only value obtained when BESTCOMSPlus is communicating with the Load Share Module. E Serial Number: Read-only value obtained when BESTCOMSPlus is communicating with the Load Share Module. F Application Part Number: Read-only value obtained when BESTCOMSPlus is communicating with the Load Share Module.
Mounting LSM-2020’s are contained in a potted plastic case and may be mounted in any convenient position. The construction of a LSM-2020 is durable enough to mount directly on a genset using ¼-inch hardware. Hardware selection should be based on any expected shipping/transportation and operating conditions. The torque applied to the mounting hardware should not exceed 65 in-lb (7.34 N•m). See Figure 9-3 for LSM-2020 overall dimensions. All dimensions are shown in inches with millimeters in parenthesis.
The RJ-45 socket mates with a standard Ethernet cable and provides local communication between the LSM-2020 and a PC running BESTCOMSPlus® software. This allows for setting of the LSM-2020 and for the DGC-2020 that the module is connected to. LSM-2020 connections are made with an 18-position connector with screw-down compression terminals. This connector plugs into a header on the LSM-2020. The connector and header have a dovetailed edge that ensures proper connector orientation.
LSM-2020 P2-9 (V+) P2-8 (IN–) P2-7 (IN+) P0059-81 0 – 10 Vdc Voltage Transducer Figure 9-5. Analog Inputs - Voltage Input Connections Analog Outputs The LSM-2020 has three sets of analog output contacts: AVR control, GOV control, and Load Share Line. The AVR control output contacts provide remote control of the generator voltage setpoint. The GOV control output contacts provide remote control of the generator speed (RPM) setpoint.
NOTES 1. If the LSM-2020 is providing one end of the J1939 bus, a 120 Ω, ½ watt terminating resistor should be installed across terminals P2-12 (CANL) and P2-11 (CANH). 2. If the LSM-2020 is not part of the J1939 bus, the stub connecting the LSM2020 to the bus should not exceed 914 mm (3 ft) in length. 3. The maximum bus length, not including stubs, is 40 m (131 ft). 4. The J1939 drain (shield) should be grounded at one point only. If grounded elsewhere, do not connect the drain to the LSM-2020.
Ethernet Port The LSM-2020 has Ethernet capability. The LSM-2020 connects to a PC through a RJ-45 jack (J3). Industrial Ethernet devices designed to comply with IEC 61000-4 series of specifications are recommended. Connections for Typical Applications Figure 9-8 illustrates typical LSM-2020 connections. Figure 9-9 illustrates a typical interconnection of two systems tied together via separate Load Share Modules.
Bus Metering Gen Breaker Control 48 49 50 GEN ENGINE 12 11 10 CANL CANH GND DGC-2020 AVR GOV CANL CANH GND Ethernet To Other LSM-2020's 5 6 LSLS+ LSM-2020 AVRAVR+ 17 18 GOVGOV+ 14 15 Bus Metering L O A D Gen Breaker Control Industrial Ethernet Switch 49 50 GEN ENGINE AVR GOV 12 11 10 CANL CANH GND Ethernet 48 CANL CANH GND DGC-2020 5 6 LSLS+ LSM-2020 AVRAVR+ 17 18 GOVGOV+ 14 15 Bus Metering Up to 16 LSM-2020's are supported on the network.
Connections using AVR’, GOV’, and LS’ Additional terminals provide a landing point to add series resistance to the GOV, AVR, and LS analog outputs. These terminals are not internally connected to the LSM-2020. Figure 9-10 illustrates connections using the additional AVR’ terminal as a landing point.
12 or 24 Vdc To System Load Share Line SHIELD DGC-2020 CANH Governor Analog Aux Output + Analog Aux Input + GND 3 4 B- Breaker A Contact Ethernet LS’ LS+ 7 8 IN- 11 12 Breaker B Contact B+ 5 6 9 10 CANL External Device 1 2 LSI+ V+ GND LSM-2020 CANH CANL 13 14 GOV’ 15 16 GOV+ 17 18 AVR- GOVAVR’ AVR+ P0057-92 Figure 9-11.
To System Load Share Line 12 or 24 Vdc SHIELD DGC-2020 CANH CANL External Device Governor 1 2 GND 3 4 B- 5 6 LS- 7 8 9 10 11 12 Analog Aux Output + B+ Ethernet LS’ LS+ I+ INV+ GND LSM-2020 CANH CANL 13 14 GOV’ 15 16 GOV+ 17 18 AVR- GOVAVR’ AVR+ Analog Aux Input + P0056-92 Figure 9-12.
SECTION 10 • CEM-2020 (CONTACT EXPANSION MODULE) TABLE OF CONTENTS SECTION 10 • CEM-2020 (CONTACT EXPANSION MODULE) ........................................................... 10-1 General Information ............................................................................................................................. 10-1 Features ............................................................................................................................................... 10-1 Specifications .......
ii DGC-2020 CEM-2020 (Contact Expansion Module) 9400200990 Rev U
SECTION 10 • CEM-2020 (CONTACT EXPANSION MODULE) General Information The optional CEM-2020 is a remote auxiliary device that provides additional DGC-2020 contact inputs and outputs. Two types of modules are available. A low current module (CEM-2020) provides 24 contact outputs and a high current module (CEM-2020H) provides 18 contact outputs.
Vibration Swept over the following ranges for 12 sweeps in each of three mutually perpendicular planes with each 15-minute sweep consisting of the following: 5 to 29 to 5 Hz ........................... 1.5 G peak for 5 min. 29 to 52 to 29 Hz ....................... 0.036” Double Amplitude for 2.5 min. 52 to 500 to 52 Hz ..................... 5 G peak for 7.5 min. Ignition System Tested in closed proximity to an unshielded, unsuppressed Altronic DISN 800 ignition system.
Functional Description Contact Inputs The CEM-2020 provides 10 programmable contact inputs with the same functionality as the contact inputs on the DGC-2020. The label text of each contact input is customizable. Contact Outputs CEM-2020 The CEM-2020 provides 24 programmable contact outputs with the same functionality as the contact outputs on the DGC-2020. Outputs 13 through 24 can carry 1 A. Outputs 25 through 36 can carry 4 A. The label text of each contact output is customizable.
Mounting Contact Expansion Modules are contained in a potted plastic case and may be mounted in any convenient position. The construction of a Contact Expansion Module is durable enough to mount directly on a genset using ¼-inch hardware. Hardware selection should be based on any expected shipping/transportation and operating conditions. The torque applied to the mounting hardware should not exceed 65 in-lb (7.34 N•m). See Figure 10-1 for CEM-2020 overall dimensions.
Figure 10-2. CEM-2020H Overall Dimensions Connections Contact Expansion Module connections are dependent on the application. Incorrect wiring may result in damage to the module. NOTES Operating power from the battery must be of the correct polarity. Although reverse polarity will not cause damage, the CEM-2020 will not operate. Be sure that the CEM-2020 is hard-wired to earth ground with no smaller than 12 AWG copper wire attached to the chassis ground terminal on the module.
It is recommended that a fuse be added for additional protection for the wiring to the battery input of the Contact Expansion Module. A Bussmann ABC-7 fuse or equivalent is recommended. Table 10-1. Operating Power Terminals Terminal P1- (SHIELD) Description Chassis ground connection P1- – (BATT–) Negative side of operating power input P1- + (BATT+) Positive side of operating power input Contact Inputs and Contact Outputs The CEM-2020 (Figure 10-3) has 10 contact inputs and 24 contact outputs.
Figure 10-4. CEM-2020H Contact Input and Contact Output Terminals CANbus Interface These terminals provide communication using the SAE J1939 protocol and provide high-speed communication between the Contact Expansion Module and the DGC-2020. Connections between the CEM-2020 and DGC-2020 should be made with twisted-pair, shielded cable. CANbus interface terminals are listed in Table 10-2. Refer to Figure 10-5 and Figure 10-6. Table 10-2.
NOTES 1. If the CEM-2020 is providing one end of the J1939 bus, a 120 Ω, ½ watt terminating resistor should be installed across terminals P1- LO (CANL) and P1- HI (CANH). 2. If the CEM-2020 is not part of the J1939 bus, the stub connecting the CEM-2020 to the bus should not exceed 914 mm (3 ft) in length. 3. The maximum bus length, not including stubs, is 40 m (131 ft). 4. The J1939 drain (shield) should be grounded at one point only. If grounded elsewhere, do not connect the drain to the CEM-2020.
SECTION 11 • AEM-2020 (ANALOG EXPANSION MODULE) TABLE OF CONTENTS SECTION 11 • AEM-2020 (ANALOG EXPANSION MODULE) .............................................................. 11-1 General Information ............................................................................................................................. 11-1 Features ............................................................................................................................................... 11-1 Specifications ......
Tables Table 11-1. Operating Power Terminals.................................................................................................. 11-5 Table 11-2. Input and Output Terminals .................................................................................................. 11-6 Table 11-3. CAN Interface Terminals ......................................................................................................
SECTION 11 • AEM-2020 (ANALOG EXPANSION MODULE) General Information The optional AEM-2020 is a remote auxiliary device that provides additional DGC-2020 analog inputs and outputs. Features AEM-2020s have the following features: • • • • • • 8 Analog Inputs 8 RTD Inputs 2 Thermocouple Inputs 4 Analog Outputs Functionality of Inputs and Outputs assigned by BESTLogicPlus programmable logic Communications via CAN Specifications Operating Power Nominal ......................................
Communication Interface CAN Differential Bus Voltage ............. 1.5 to 3 Vdc Maximum Voltage ...................... –32 to +32 Vdc with respect to negative battery terminal Communication Rate ................. 250 kb/s Type Tests Shock Withstands 15 G in 3 perpendicular planes. Vibration Swept over the following ranges for 12 sweeps in each of three mutually perpendicular planes with each 15-minute sweep consisting of the following: 5 to 29 to 5 Hz ........................... 1.5 G peak for 5 min.
This product conforms to the following Harmonized Standards: • EN 50178:1997 - Electronic Equipment for use in Power Installations • EN 61000-6-4:2001 - Electromagnetic Compatibility (EMC), Generic Standards, Emission Standard for Industrial Environments • EN 61000-6-2:2001 - Electromagnetic Compatibility (EMC), Generic Standards, Immunity for Industrial Environments Physical Weight ........................................ 1.80 lb (816 g) Dimensions ................................
Product Registration Registering with Basler Electric enables you to receive important information updates on your product plus new product announcements. Register your product by directing your web browser to www.basler.com. Mounting Analog Expansion Modules are contained in a potted plastic case and may be mounted in any convenient position. The construction of an Analog Expansion Module is durable enough to mount directly on a genset using ¼-inch hardware.
AEM-2020 connections are made with one 5-position connector, two 12-position connectors, two 16position connectors, and two 2-position thermocouple connectors. The 16, 5, and 2-position connectors plug into headers on the AEM-2020. The connectors and headers have dovetailed edges that ensure proper connector orientation. The connectors and headers are uniquely keyed to ensure that the connectors mate only with the correct headers.
AEM-2020 Inputs and Outputs Input and output terminals are shown in Figure 11-2 and listed in Table 11-2. Figure 11-2. Input and Output Terminals Table 11-2.
External Analog Input Connections Voltage input connections are shown in Figure 11-3 and current input connections are shown in Figure 11-4. When using the current input, AIN V+ and AIN I+ must be tied together. AEM-2020 0 – 10 Vdc Voltage Transducer AIN – AIN V+ P0059-78 AIN I+ Figure 11-3. Analog Inputs - Voltage Input Connections AEM-2020 AIN I+ AIN – AIN V+ P0059-79 4 – 20 mA Current Transducer Figure 11-4.
External RTD Input Connections External 2-wire RTD input connections are shown in Figure 11-5. Figure 11-6 shows external 3-wire RTD input connections. RED AEM-2020 Jumper RTD1+ RTD1– RTD1C P0053-64 BLACK Figure 11-5. External Two-Wire RTD Input Connections RED AEM-2020 BLACK BLACK RTD1– RTD1C P0053-65 RTD1+ Figure 11-6.
NOTES 1. If the AEM-2020 is providing one end of the J1939 bus, a 120 Ω, ½ watt terminating resistor should be installed across terminals P1- LO (CANL) and P1- HI (CANH). 2. If the AEM-2020 is not part of the J1939 bus, the stub connecting the AEM-2020 to the bus should not exceed 914 mm (3 ft) in length. 3. The maximum bus length, not including stubs, is 40 m (131 ft). 4. The J1939 drain (shield) should be grounded at one point only. If grounded elsewhere, do not connect the drain to the AEM-2020.
11-10 DGC-2020 AEM-2020 (Analog Expansion Module) 9400200990 Rev U
APPENDIX A • TIME OVERCURRENT CHARACTERISTIC CURVES TABLE OF CONTENTS APPENDIX A • TIME OVERCURRENT CHARACTERISTIC CURVES ................................................... A-1 Introduction ............................................................................................................................................ A-1 Curve Specifications ..............................................................................................................................
ii DGC-2020 Time Overcurrent Characteristic Curves 9400200990 Rev U
APPENDIX A • TIME OVERCURRENT CHARACTERISTIC CURVES Introduction The inverse time overcurrent characteristic curves provided by the DGC-2020 (style xxxxxxExx only) closely emulate most of the common electromechanical, induction-disk, overcurrent relays sold in North America. To further improve proper relay coordination, selection of integrated reset or instantaneous reset characteristics is also provided. Curve Specifications Timing Accuracy: Within ±500 milliseconds of indicated operating point.
Table A-1. 51 Time Characteristic Curve Constants Curve Selection Curve Name Reset † Trip Characteristic Constants A B C N K Q R S1 Short Inverse 0.2663 0.03393 1 1.2969 0.028 1 0.5 S2 Short Inverse 0.0286 0.0208 1 0.9844 0.028 1 0.094 L1 Long Inverse 5.6143 2.18592 1 1 0.028 1 15.75 L2 Long Inverse 2.3955 0 1 0.3125 0.028 1 7.8001 D Definite Time 0.4797 0.21359 1 1.5625 0.028 1 0.875 M Moderately Inverse 0.3022 0.1284 1 0.5 0.028 1 1.
Table A-2.
Table A-3 .Time Dial Setting Cross-Reference 0.5 S1 ABB CO-2 0.3 0.8 1.7 2.4 3.4 4.2 5.0 5.8 6.7 7.7 8.6 L1 ABB CO-5 0.4 0.8 1.5 2.3 3.3 4.2 5.0 6.0 7.0 7.8 8.8 9.9 D ABB CO-6 0.5 1.1 2.0 2.9 3.7 4.5 5.0 5.9 7.2 8.0 8.9 10.1 M ABB CO-7 0.4 0.8 1.7 2.5 3.3 4.3 5.3 6.1 7.0 8.0 9.0 9.8 I1 ABB CO-8 0.3 0.7 1.5 2.3 3.2 4.0 5.0 5.8 6.8 7.6 8.7 10.0 V1 ABB CO-9 0.3 0.7 1.4 2.1 3.0 3.9 4.8 5.7 6.7 7.8 8.7 9.6 E1 ABB CO-11 0.3 0.
Figure A-1.
Figure A-2.
Figure A-3.
Figure A-4.
Figure A-5.
Figure A-6.
Figure A-7.
Figure A-8.
Figure A-9.
Figure A-10.
Figure A-11.
Figure A-12.
Figure A-13.
Figure A-14.
Figure A-15.
Figure A-16.
APPENDIX B • MODBUS™ COMMUNICATION TABLE OF CONTENTS APPENDIX B • Modbus™ COMMUNICATION .......................................................................................... B-1 Introduction ............................................................................................................................................ B-1 General Overview ...............................................................................................................................
ii DGC-2020 Modbus™ Communication 9400200990 Rev U
APPENDIX B • MODBUS™ COMMUNICATION Introduction General Overview An optional feature of the DGC-2020 performs Modbus™ communications by emulating a subset of the Modicon 984 Programmable Controller. This document describes the Modbus communications protocol employed by the DGC-2020 and how to exchange information with the DGC-2020 over a Modbus network. The DGC-2020 maps all parameters into the Modicon 984 Holding Register address space (4XXXX).
Function Code Field The Function Code field in the Query message defines the action to be taken by the addressed slave. This field is echoed in the Response message, and will be altered by setting the MSB of the field to "1" if the response is an error response. This field is 1 byte. Data Block Field The query Data block contains additional information needed by the slave to perform the requested function. The response Data block contains data collected by the slave for the queried function.
• • • • Function 03 - Read Holding Registers Function 6 - Preset Single Register, Non-Broadcast & Broadcast Function 08, Subfunction 00 - Diagnostics: Return Query Data Function 16 - Preset Multiple Registers, Non-Broadcast & Broadcast The only Broadcast query supported by the DGC-2020 is the Preset Multiple Registers query. Read Holding Registers Read Holding Registers - General QUERY: This query message requests a register or block of registers to be read.
Preset Multiple Registers, Non-Broadcast & Broadcast Preset Multiple Registers - General QUERY: This query message requests a register or block of registers to be written. The data block contains the starting address and the quantity of registers to be written, followed by the Data Block byte count and data. A device address is 0 for a broadcast query. A register address of N will write Holding Register N+1.
• • • Queries writing to Read Only or unsupported registers result in an error response with Exception Code of “Illegal Data Address”. There are several instances of registers that are grouped together (signified as DP or TP) to collectively represent a single numerical (vs. ASCII string) DGC-2020 parameter value. A query to write a subset of such a register group will result in an error response with Exception Code “Illegal Data Address”.
Long Integer Data Format (INT32) The Modbus long integer data format uses two consecutive holding registers to represent a 32-bit data value. The first register contains the low-order 16 bits and the second register contains the high-order 16 bits. Example: The value 95,800 represented in long integer format is hexadecimal 0x00017638.
The value of the floating-point number is obtained by multiplying the binary mantissa times two raised to the power of the unbiased exponent. The assumed bit of the binary mantissa has the value of 1.0, with the remaining 23 bits providing a fractional value. Table B-2 shows the floating-point format. Table B-2. Floating Point Format Sign Exponent + 127 Mantissa 1 bit 8 bits 23 bits -37 38 The floating-point format allows for values ranging from approximately 8.43X10 to 3.38X10 .
Interdependence of Preset Multiple Register Data Preset Multiple Register data is collectively written only after the query has been determined to be legal, which includes a range-check of the entire data block. Therefore, data which must be written prior to other data must use a separate query.
Register 42068 42070 Description Max Parallel Time Mains Fail Transfer Type Type Int32 Int32 Units Second N/A Scaling Factor Deci N/A R/W RW RW 42072 In Phase Monitor Enable Int32 N/A N/A RW 42074 Dead Gen Close Enable Int32 N/A N/A RW 42076 42078 42080 42082 RESERVED Min Slip Control Limit Max Slip Control Limit Rev.
42330 42332 42334 42336 42338 42340 kW Integrator Limit Minus kW Output Upper Limit kW Output Lower Limit RESERVED Droop Percent Load Control Float Float Float N/A N/A N/A Scaling Factor N/A N/A N/A Float Int32 Percent N/A 42342 42344 42346 kW Load Rate Breaker Open Setpoint AVR Bias Control Output Type Int32 Int32 Int32 42348 42350 42352 42354 Governor Bias Control Output Type Speed Droop Gain Voltage Droop Gain Speed Trim Enable 42356 Register Description Type Units R/W Range RW RW RW
94 42396 42398 42400-06 42408 42410 42412 42414 PF Analog Max PF Analog Min var Droop Percentage RESERVED Base Load Level kvar Setpoint PF Setpoint var Control Mode Int32 Int32 Float N/A N/A Percent Scaling Factor Centi Centi N/A Float Float Int32 Int32 Percent Percent N/A N/A 42416 Load Share Interface Int32 42418 Remote Speed Bias Source 42420 42422 42424 RESERVED RESERVED LSM Aux Input Source 42426 42428 42430498 kW Ramp Status kvar Ramp Status FUTURE USE Register Description Type U
Register 42780 42782 42784 42786 42788 42790 42792 42794 42796 42798 42800 42802 42804 42806 42808 42810 42812 42814 42816 42818 42820 42822 42824 42826-3432 Description Bus Sensing Dead Bus Time Delay RESERVED Bus Sensing Stable Undervoltage Pickup Bus Sensing Stable Undervoltage Dropout Bus Sensing Stable Overvoltage Pickup Bus Sensing Stable Overvoltage Dropout Bus Sensing Stable Underfrequency Pickup Bus Sensing Stable Underfrequency Dropout Bus Sensing Stable Overfrequency Pickup Bus Sensing Stable Ov
Description Type 43452 Low Coolant Level Config Type Int32 N/A Scaling Factor N/A 43454 43456 Low Coolant Level Time Delay Battery Charge Failed Contact Input Int32 Int32 Second N/A N/A N/A RW RW 43458 Battery Charge Failed Config Type Int32 N/A N/A RW 43460 43462 Battery Charge Failed Time Delay Fuel Leak Detect Contact Input Int32 Int32 Second N/A N/A N/A RW RW 43464 Fuel Leak Detect Config Type Int32 N/A N/A RW 43466 43468 Fuel Leak Detect Time Delay User Configurable Inpu
43478 User Configurable Input 6 Eng Run Only Int32 N/A Scaling Factor N/A 43480 User Configurable Input 7 Eng Run Only Int32 N/A N/A RW 43482 User Configurable Input 8 Eng Run Only Int32 N/A N/A RW 43484 User Configurable Input 9 Eng Run Only Int32 N/A N/A RW 43486 User Configurable Input 10 Eng Run Only Int32 N/A N/A RW 43488 User Configurable Input 11 Eng Run Only Int32 N/A N/A RW 43490 User Configurable Input 12 Eng Run Only Int32 N/A N/A RW 43492 User Configurab
43518 Virtual Input 3 Status Int32 N/A Scaling Factor N/A 43520 Virtual Input 4 Status Int32 N/A N/A R 43522 43524 43526 43528 43530 43532 43534 RTC Clock Hour RTC Minute RTC Second RTC Month RTC Day RTC Year RTC DST Enable Int32 Int32 Int32 Int32 Int32 Int32 Int32 Hour Minute Second N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A RW RW RW RW RW RW RW 43536 43538 43540 43542 43544 43546 Gen PT Primary Gen PT Secondary Gen CT Primary Bus PT Primary Bus PT Secondary Cranking Style Int32 Int32 I
43598 43600 DSP Bias Minutes DST Start Month Int32 Int32 N/A N/A Scaling Factor N/A N/A 43602 43604 DST Start Day DST Start Week of Month Int32 In32 N/A N/A N/A N/A RW RW 43606 DST Start Day of Week Int32 N/A N/A RW 43608 43610 43612 DST Start Hour DST Start Minute DST End Month Int32 Int32 Int32 N/A N/A N/A N/A N/A N/A RW RW RW 43614 43616 DST End Day DST End Week of Month Int32 Int32 N/A N/A N/A N/A RW RW 43618 DST End Day of Week Int32 N/A N/A RW 43620 43622 43624 43626
43640 43642 43644 Low Line Detect Threshold Single Phase Detect Threshold Start Relay Control Int32 Int32 Uint32 Volt Volt N/A Scaling Factor N/A N/A N/A 43646 Run Relay Control Uint32 N/A N/A RW 43648 Prestart Relay Control Uint32 N/A N/A RW 43650 Int32 N/A N/A RW 43652 Single Phase Connect Generator Detection Off Mode Cool Down Enable Uint32 N/A N/A RW 43654 43656 RESERVED Not In Auto Horn Enable Uint32 N/A N/A RW 43658 Clock Not Set Warning Enable Uint32 N/A N/A RW
Register 43772 43774 Description FUTURE USE Virtual Input 1 Close Type Units Int32 N/A 43776 Virtual Input 1 Open Int32 43778 Virtual Input 2 Close 43780 Scaling Factor R/W Range N/A RW N/A N/A RW Int32 N/A N/A RW Virtual Input 2 Open Int32 N/A N/A RW 43782 Virtual Input 3 Close Int32 N/A N/A RW 43784 Virtual Input 3 Open Int32 N/A N/A RW 43786 Virtual Input 4 Close Int32 N/A N/A RW 43788 Virtual Input 4 Open Int32 N/A N/A RW 43790 ESTOP Latch Status In
44024-25 Modem Dialout Conditions 1 Uint32 N/A Scaling Factor N/A 44026-27 Modem Dialout Conditions 2 Uint32 N/A N/A RW 44028-30 44032 RESERVED CANbus Enable Int32 N/A N/A RW Register Description 9400200990 Rev U Type Units R/W Range RW Bit 0 = Aux Input 5 Closed Bit 1 = Aux Input 4 Closed Bit 2 = Aux Input 3 Closed Bit 3 = Aux Input 2 Closed Bit 4 = Aux Input 1 Closed Bit 5 = Cooldown Timer Active Bit 6 = Switch Not In Auto Bit 7 = Scheduled Maintenance PreAlarm Bit 8 = Weak Batter
44034 DTC Enable Int32 N/A Scaling Factor N/A 44036 44038 44040 Rings for Modem Answer Modem Offline Delay Modbus Baud Rate Int32 Int32 Int32 N/A Minute N/A N/A N/A N/A RW RW RW 44042 Modbus Parity Int32 N/A N/A RW 44044 44046-47 Modbus Address Modem Dialout Conditions 3 Int32 Uint32 N/A N/A N/A N/A RW RW 44048 LSM-2020 Enable Int32 N/A N/A RW 44050 DHCP Enabled Uint32 N/A N/A R 44052-56 44058 RESERVED CEM-2020 Enable Int32 N/A N/A RW 0 = Disable 1 = Enable 44060 44
44066-67 Modem Dialout Conditions 4 Uint32 N/A Scaling Factor N/A 44068 44070 44072 44074-248 Active IP Address Gateway IP Address Subnet Mask FUTURE USE Uint32 Uint32 Uint32 N/A N/A N/A N/A N/A N/A Register Description Type Units R/W Range RW Bit 0 = Not Used Bit 1 = Not Used Bit 2 = Not Used Bit 3 = Not Used Bit 4 = Not Used Bit 5 = Not Used Bit 6 = Not Used Bit 7 = Not Used Bit 8 = Not Used Bit 9 = Not Used Bit 10 = Not Used Bit 11 = Not Used Bit 12 = Not Used Bit 13 = Not Used Bit 14 =
44256 3 Phase Overcurrent Alarm Configuration (51-1) Uint32 N/A Scaling Factor N/A 44258 1 Phase Overcurrent Pickup (51-1) 1 Phase Overcurrent Time Dial (51-1) 1 Phase Overcurrent Curve (51-1) Uint32 CentiAmp Centi RW 0 = None 1 = Alarm 2 = Pre-Alarm 3 = Status Only 18 - 775 Uint32 DeciUnit Deci RW 0 - 72000 Uint32 N/A N/A RW 44264 1 Phase Overcurrent Alarm Configuration (51-1) Uint32 N/A N/A RW 44266 44268 Phase Imbalance Pickup Phase Imbalance Activation Delay Phase Imbalance A
Type Units 1 Phase Overvoltage Activation Delay (59-1) 1 Phase Overvoltage Alarm Configuration (59-1) Uint32 Decisecond Scaling Factor Deci Uint32 N/A 44300 44302 44304 44306 Underfrequency Pickup Underfrequency Activation Delay Underfrequency Inhibit Voltage Underfrequency Alarm Configuration Uint32 Uint32 Uint32 Uint32 44308 44310 44312 Overfrequency Pickup Overfrequency Activation Delay Overfrequency Alarm Configuration 44314 Overcurrent Low Line Scale Factor (51-1) Overvoltage Low Line Sca
44332 1 Phase Overcurrent Curve (51-2) Uint32 N/A Scaling Factor N/A 44334 1 Phase Overcurrent Alarm Configuration (51-2) Uint32 N/A N/A RW 44336 3 Phase Undervoltage Pickup (27-2) 3 Phase Undervoltage Activation Delay (27-2) 3 Phase Undervoltage Inhibit Frequency (27-2) 3 Phase Undervoltage Alarm Configuration (27-2) Uint32 Volt N/A RW 0 = S1 Curve 1 = S2 Curve 2 = L1 Curve 3 = L2 Curve 4 = D Curve 5 = M Curve 6 = I1 Curve 7 = I2 Curve 8 = V1 Curve 9 = V2 Curve 10 = E1 Curve 11 = E2 Curve
Description Type 1 Phase Undervoltage Hysteresis (27-1) 3 Phase Overvoltage Hysteresis (59-1) 1 Phase Overvoltage Hysteresis (59-1) Underfrequency Hysteresis Overfrequency Hysteresis 3 Phase Undervoltage Hysteresis (27-2) 1 Phase Undervoltage Hysteresis (27-2) 3 Phase Overvoltage Hysteresis (59-2) 1 Phase Overvoltage Hysteresis (59-2) 3 Phase Reverse Power Pickup 3 Phase Reverse Power Activation Delay 3 Phase Reverse Power Alarm Configuration Uint32 Volt Scaling Factor N/A Uint32 Volt Uint32 Regist
51-1 Curve Constant N 51-1 Curve Constant R 51-2 Curve Constant A 51-2 Curve Constant B 51-2 Curve Constant C 51-2 Curve Constant N 51-2 Curve Constant R 3 Phase Overcurrent Pickup (51-3) 3 Phase Overcurrent Time Dial (51-3) 3 Phase Overcurrent Curve (51-3) Float Float Float Float Float Float Float Uint32 N/A N/A N/A N/A N/A N/A N/A CentiAmp Scaling Factor N/A N/A N/A N/A N/A N/A N/A Centi Uint32 DeciUnit Uint32 44458 3 Phase Overcurrent Alarm Configuration (51-3) 44460 Register 44438 44440 44442
44480 44482 44484 51-3 Curve Constant N 51-3 Curve Constant R 78 Vector Shift Alarm Config Float Float Uint32 N/A N/A N/A Scaling Factor N/A N/A N/A 44486 44488 78 Vector Shift Pickup 78 Open Mains Breaker on Trip Int32 Int32 Degree N/A N/A N/A RW RW 44490 81 ROCOF Alarm Config Uint32 N/A N/A RW 44492 44494 44496 81 ROCOF Pickup 81 ROCOF Activation Delay 81 ROCOF Open Mains Breaker on Trip Alternate Frequency Scale Factor Uint32 Uint32 Int32 Hz/Second Second N/A Deci Milli N/A RW RW RW
Register 44544 44546 44548 44550 44552 44554 44556 44558 44560 44562 44564 44566 44568 44570 44572 44574 44576 44578 44580 44582 44584 44586 44588 44590 44592 44594 44596 44598 44600 44602 44604 44606 B-28 Description High Fuel Level Pre-Alarm Activation Delay Low Fuel Level Pre-Alarm Enable Low Fuel Level Pre-Alarm Threshold Low Battery Pre-Alarm Enable Type Int32 Units Second Scaling Factor N/A R/W RW Uint32 N/A N/A RW Uint32 Percent N/A RW Uint32 N/A N/A RW Low Battery Pre-Alarm Thresh
Register 44608 Type Int32 Units Percent Scaling Factor N/A R/W RW 0 - 200 Int32 Percent N/A RW 1 - 10 Float N/A N/A RW 0.001 - 3 Int32 N/A N/A RW Int32 Percent N/A RW 0 = Disable 1 = Enable 0 - 200 Int32 Percent N/A RW 1 - 10 Int32 Percent N/A RW 0 - 200 Int32 Percent N/A RW 1 - 10 Float N/A N/A RW 0.
Register 44756 44758 44760 44762 44764 44766 44768 44770 44772 44774 44776 44778 44780 44782 44784 44786 44788 44790 44792 44794 44796 44798 44800 44802 44804 44806 44808 44810 44812-13 B-30 Volt Volt Volt Volt Amp Amp Amp KiloVA KiloVA KiloVA KiloVA KiloWatt KiloWatt KiloWatt KiloWatt N/A N/A Hertz Hertz N/A RPM Percent Deg F PSI DeciVolt N/A N/A Scaling Factor N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A R R R R R R R R R R R R R R R R R R
44814-15 Pre-Alarm Metering 1 Int32 N/A Scaling Factor N/A 44816-17 MTU Alarm Metering Int32 N/A N/A Register Description 9400200990 Rev U Type Units R/W R R DGC-2020 Modbus™ Communication Range Bit 0 = Not Used Bit 1 = Not Used Bit 2 = Serial Flash Read Failure Bit 3 = Checksum Fail Bit 4 = Global Pre-Alarm Bit 5 = Fuel Filter 2 Leak Bit 6 = Fuel Filter 1 Leak Bit 7 = Engine kW Overload 3 Bit 8 = Engine kW Overload 2 Bit 9 = MPU Fail Bit 10 = Fuel Leak Detect Bit 11 = Battery Charger Fail
44818-19 MTU Pre-Alarm Metering Int32 N/A Scaling Factor N/A 44820-21 Sender Fail Alarm Metering Int32 N/A N/A 44822-26 RESERVED Register B-32 Description Type Units R/W R R DGC-2020 Modbus™ Communication Range Bit 0 = Low Storage Tank Bit 1 = High Storage Tank Bit 2 = Low Day Tank Bit 3 = High Day Tank Bit 4 = Alternator Winding Temp Bit 5 = Idle Speed Low Bit 6 = Run Up Speed Low Bit 7 = Start Speed Low Bit 8 = Priming Fault Bit 9 = Low Charge Air Coolant Level Bit 10 = High Fuel Temp.
44828-29 Local Input Metering Int32 N/A Scaling Factor N/A 44830-31 Local Output Metering Int32 N/A N/A Register Description 9400200990 Rev U Type Units R/W R R DGC-2020 Modbus™ Communication Range Bit 0 = Not Used Bit 1 = Not Used Bit 2 = Not Used Bit 3 = Not Used Bit 4 = Not Used Bit 5 = Not Used Bit 6 = Not Used Bit 7 = Not Used Bit 8 = Not Used Bit 9 = Not Used Bit 10 = Not Used Bit 11 = Not Used Bit 12 = Not Used Bit 13 = Not Used Bit 14 = Not Used Bit 15 = Not Used Bit 16 = Input 16
44832-33 Status Metering 1 Int32 N/A Scaling Factor N/A 44834 44836 Hours Until Maintenance Cum. Total Engine Run Hrs. Cum. Total Engine Run Min. Cum. Loaded Engine Run Hrs. Cum. Loaded Engine Run Min. Cum. Unloaded Engine Run Hrs. Cum. Unloaded Engine Run Min. Cum. Total kW-Hrs Cum. Total kW-Mins Commission Date Month Commission Date Day Commission Date Year Session Total Engine Run Hrs. Session Total Engine Run Min. Session Loaded Engine Run Hrs. Session Loaded Engine Run Min.
Description Type Uint32 N/A 44874 44876 44878 44880 Cumulative Number of Engine Starts Session Start Date Month Session Start Date Day Session Start Date Year Generator Status Scaling Factor N/A Uint32 Uint32 Uint32 Uint32 N/A N/A N/A N/A 44882-918 44920-32 44934-35 RESERVED FUTURE USE Protection Alarm Metering Int32 44936 Cumulative Stats - Total Run Hours Cumulative Stats Loaded Run Hours Cumulative Stats Unloaded Run Hours Run Stats - Total Run Hours Run Stats - Loaded Run Hours Run Stats - U
44948-49 LSM Alarm Bits Uint32 N/A Scaling Factor N/A 44950 Global Alarm Uint32 N/A N/A R 44952 Global Pre-Alarm Uint32 N/A N/A R Register B-36 Description Type Units R/W R DGC-2020 Modbus™ Communication Range Bit 0 = Not Used Bit 1 = Not Used Bit 2 = Not Used Bit 3 = Not Used Bit 4 = Not Used Bit 5 = Not Used Bit 6 = Not Used Bit 7 = Not Used Bit 8 = Not Used Bit 9 = Not Used Bit 10 = Not Used Bit 11 = Not Used Bit 12 = Not Used Bit 13 = Not Used Bit 14 = Not Used Bit 15 = Not Used
54-55 Local Configurable Inputs Pre-Alarm Bits Int32 N/A Scaling Factor N/A 44956-57 Local Configurable Inputs Alarm Bits Int32 N/A N/A Register Description 9400200990 Rev U Type Units R/W R R DGC-2020 Modbus™ Communication Range Bit 0 = Not Used Bit 1 = Not Used Bit 2 = Not Used Bit 3 = Not Used Bit 4 = Not Used Bit 5 = Not Used Bit 6 = Not Used Bit 7 = Not Used Bit 8 = Not Used Bit 9 = Not Used Bit 10 = Not Used Bit 11 = Not Used Bit 12 = Not Used Bit 13 = Not Used Bit 14 = Not Used B
44958-59 Configurable Elements Status Bits Int32 N/A Scaling Factor N/A 44960-61 Configurable Elements Pre-Alarm Bits Int32 N/A N/A Register B-38 Description Type Units R/W R R DGC-2020 Modbus™ Communication Range Bit 0 = Not Used Bit 1 = Not Used Bit 2 = Not Used Bit 3 = Not Used Bit 4 = Not Used Bit 5 = Not Used Bit 6 = Not Used Bit 7 = Not Used Bit 8 = Not Used Bit 9 = Not Used Bit 10 = Not Used Bit 11 = Not Used Bit 12 = Not Used Bit 13 = Not Used Bit 14 = Not Used Bit 15 = Not Used Bi
44962-63 Configurable Elements Alarm Bits Int32 N/A Scaling Factor N/A 44964-65 Remote Inputs Status Bits Int32 N/A N/A Register Description 9400200990 Rev U Type Units R/W R R DGC-2020 Modbus™ Communication Range Bit 0 = Not Used Bit 1 = Not Used Bit 2 = Not Used Bit 3 = Not Used Bit 4 = Not Used Bit 5 = Not Used Bit 6 = Not Used Bit 7 = Not Used Bit 8 = Not Used Bit 9 = Not Used Bit 10 = Not Used Bit 11 = Not Used Bit 12 = Not Used Bit 13 = Not Used Bit 14 = Not Used Bit 15 = Not Used Bi
44966-67 Remote Outputs Status Bits Int32 N/A Scaling Factor N/A 44968-69 CEM Alarm Bits Uint32 N/A N/A Register B-40 Description Type Units R/W R R DGC-2020 Modbus™ Communication Range Bit 0 = Not Used Bit 1 = Not Used Bit 2 = Not Used Bit 3 = Not Used Bit 4 = Not Used Bit 5 = Not Used Bit 6 = Not Used Bit 7 = Not Used Bit 8 = Remote Output 36 Bit 9 = Remote Output 35 Bit 10 = Remote Output 34 Bit 11 = Remote Output 33 Bit 12 = Remote Output 32 Bit 13 = Remote Output 31 Bit 14 = Remote Ou
44970-71 Remote Configurable Inputs Pre-Alarm Bits Uint32 N/A Scaling Factor N/A 44972-73 Remote Configurable Inputs Alarm Bits Uint32 N/A N/A Register Description 9400200990 Rev U Type Units R/W R R DGC-2020 Modbus™ Communication Range Bit 0 = Not Used Bit 1 = Not Used Bit 2 = Not Used Bit 3 = Not Used Bit 4 = Not Used Bit 5 = Not Used Bit 6 = Not Used Bit 7 = Not Used Bit 8 = Not Used Bit 9 = Not Used Bit 10 = Not Used Bit 11 = Not Used Bit 12 = Not Used Bit 13 = Not Used Bit 14 = Not Us
44974-75 AEM Alarm Bits Uint32 N/A Scaling Factor N/A 44976 44978 44980 Slip Frequency Slip Angle Voltage Difference Int32 Int32 Int32 Hertz DeciUnit Volt Centi Deci N/A Register B-42 Description Type Units R/W R R R R DGC-2020 Modbus™ Communication Range Bit 0 = Not Used Bit 1 = Not Used Bit 2 = Not Used Bit 3 = Not Used Bit 4 = Not Used Bit 5 = Not Used Bit 6 = Not Used Bit 7 = Not Used Bit 8 = Not Used Bit 9 = Not Used Bit 10 = Not Used Bit 11 = Not Used Bit 12 = Not Used Bit 13 = Not U
44982-83 MDEC Pre-Alarms Int32 N/A Scaling Factor N/A 44984-85 MTU Status Int32 N/A N/A R 44986 44988 Generator Frequency Bus Frequency Int32 Int32 Hertz Hertz Deci Deci R R Register Description 9400200990 Rev U Type Units R/W R DGC-2020 Modbus™ Communication Range Bit 0 = Not Used Bit 1 = Not Used Bit 2 = Not Used Bit 3 = Not Used Bit 4 = Not Used Bit 5 = Not Used Bit 6 = Not Used Bit 7 = Not Used Bit 8 = Not Used Bit 9 = Not Used Bit 10 = Not Used Bit 11 = Not Used Bit 12 = Not Use
44990 44992 44994-98 45000-01 Power Factor Slip Frequency RESERVED ECU Lamp Status Int32 Int32 N/A N/A Scaling Factor Centi Milli Int32 N/A N/A R 45002 DTC Lamp Status Note: Odd bits are always a zero value Int32 N/A N/A R 45004 45006-326 45328 Number of DTC’s RESERVED Engine Parameter Transmit Enable Requested MTU SMC ENG Operating Mode SPN Conversion Method RESERVED Analog Input 1 Metering Value Analog Input 2 Metering Value Int32 N/A N/A R Int32 N/A N/A RW Int32 N/A N/A RW 0
Register 45504 45506 45508 45510 45512 45514 45516 45518 45520 45522 45524 45526 45528 45530 45532 45534 45536-37 Description Analog Input 3 Metering Value Analog Input 4 Metering Value Analog Input 5 Metering Value Analog Input 6 Metering Value Analog Input 7 Metering Value Analog Input 8 Metering Value RTD Input 1 Metering Value RTD Input 2 Metering Value RTD Input 3 Metering Value RTD Input 4 Metering Value RTD Input 5 Metering Value RTD Input 6 Metering Value RTD Input 7 Metering Value RTD Input 8 Mete
45538-39 AEM Input Threshold Status Bits Reg 2 Uint32 N/A Scaling Factor N/A 45540-41 AEM Input Threshold Status Bits Reg 3 Uint32 N/A N/A Register B-46 Description Type Units R/W R R DGC-2020 Modbus™ Communication Range Bit 0 = Not Used Bit 1 = Not Used Bit 2 = RTD Input 4 Under 2 Bit 3 = RTD Input 4 Under 1 Bit 4 = RTD Input 4 Over 2 Bit 5 = RTD Input 4 Over 1 Bit 6 = RTD Input 4 Out of Range Bit 7 = RTD Input 3 Under 2 Bit 8 = RTD Input 3 Under 1 Bit 9 = RTD Input 3 Over 2 Bit 10 = RTD
45542-43 AEM Input Threshold Status Bits Reg 4 Uint32 N/A Scaling Factor N/A 45544-45 AEM Input Threshold Alarm Bits Reg 1 Uint32 N/A N/A Register Description 9400200990 Rev U Type Units R/W R R DGC-2020 Modbus™ Communication Range Bit 0 = Not Used Bit 1 = Not Used Bit 2 = Not Used Bit 3 = Not Used Bit 4 = Not Used Bit 5 = Not Used Bit 6 = Not Used Bit 7 = Not Used Bit 8 = Not Used Bit 9 = Not Used Bit 10 = Not Used Bit 11 = Not Used Bit 12 = Not Used Bit 13 = Not Used Bit 14 = Not Used Bi
45546-47 AEM Input Threshold Alarm Bits Reg 2 Uint32 N/A Scaling Factor N/A 45548-49 AEM Input Threshold Alarm Bits Reg 3 Uint32 N/A N/A Register B-48 Description Type Units R/W R R DGC-2020 Modbus™ Communication Range Bit 0 = Not Used Bit 1 = Not Used Bit 2 = RTD Input 4 Under 2 Bit 3 = RTD Input 4 Under 1 Bit 4 = RTD Input 4 Over 2 Bit 5 = RTD Input 4 Over 1 Bit 6 = RTD Input 4 Out of Range Bit 7 = RTD Input 3 Under 2 Bit 8 = RTD Input 3 Under 1 Bit 9 = RTD Input 3 Over 2 Bit 10 = RTD In
45550-51 AEM Input Threshold Alarm Bits Reg 4 Uint32 N/A Scaling Factor N/A 45552-53 AEM Input Threshold PreAlarm Bits Reg 1 Uint32 N/A N/A Register Description 9400200990 Rev U Type Units R/W R R DGC-2020 Modbus™ Communication Range Bit 0 = Not Used Bit 1 = Not Used Bit 2 = Not Used Bit 3 = Not Used Bit 4 = Not Used Bit 5 = Not Used Bit 6 = Not Used Bit 7 = Not Used Bit 8 = Not Used Bit 9 = Not Used Bit 10 = Not Used Bit 11 = Not Used Bit 12 = Not Used Bit 13 = Not Used Bit 14 = Not Used
Description Type 45554-55 AEM Input Threshold PreAlarm Bits Reg 2 Uint32 N/A Scaling Factor N/A 45556-57 AEM Input Threshold PreAlarm Bits Reg 3 Uint32 N/A N/A Register B-50 Units R/W R R DGC-2020 Modbus™ Communication Range Bit 0 = Not Used Bit 1 = Not Used Bit 2 = RTD Input 4 Under 2 Bit 3 = RTD Input 4 Under 1 Bit 4 = RTD Input 4 Over 2 Bit 5 = RTD Input 4 Over 1 Bit 6 = RTD Input 4 Out of Range Bit 7 = RTD Input 3 Under 2 Bit 8 = RTD Input 3 Under 1 Bit 9 = RTD Input 3 Over 2 Bit 10 =
Description Type 45558-59 AEM Input Threshold PreAlarm Bits Reg 4 Uint32 N/A Scaling Factor N/A 45560 Analog Output 1 Metering Value Analog Output 2 Metering Value Analog Output 3 Metering Value Analog Output 4 Metering Value Int32 CentiUnit Centi R Bit 0 = Not Used Bit 1 = Not Used Bit 2 = Not Used Bit 3 = Not Used Bit 4 = Not Used Bit 5 = Not Used Bit 6 = Not Used Bit 7 = Not Used Bit 8 = Not Used Bit 9 = Not Used Bit 10 = Not Used Bit 11 = Not Used Bit 12 = Not Used Bit 13 = Not Used Bit 14
45568-69 Configurable Protection Threshold Status Bits Uint32 N/A Scaling Factor N/A 45570-71 Configurable Protection Alarm Bits Uint32 N/A N/A Register B-52 Description Type Units R/W R R DGC-2020 Modbus™ Communication Range Bit 0 = Conf Protection 8 Under 2 Bit 1 = Conf Protection 8 Under 1 Bit 2 = Conf Protection 8 Over 2 Bit 3 = Conf Protection 8 Over 1 Bit 4 = Conf Protection 7 Under 2 Bit 5 = Conf Protection 7 Under 1 Bit 6 = Conf Protection 7 Over 2 Bit 7 = Conf Protection 7 Over 1
45572-73 Configurable Protection Pre-Alarm Bits Uint32 N/A Scaling Factor N/A 45574 45576 45578 45580 45582 Gen Kvar A Gen Kvar B Gen Kvar C Gen Kvar Total FUTURE USE Int32 Int32 Int32 Int32 kvar kvar kvar kvar N/A N/A N/A N/A Register Description 9400200990 Rev U Type Units R/W R R R R R DGC-2020 Modbus™ Communication Range Bit 0 = Conf Protection 8 Under 2 Bit 1 = Conf Protection 8 Under 1 Bit 2 = Conf Protection 8 Over 2 Bit 3 = Conf Protection 8 Over 1 Bit 4 = Conf Protection 7 Under 2
Register Description Type 45584-85 Logic Control Relay Status Uint32 N/A Scaling Factor N/A 45586-87 I/O Modules Connected Uint32 N/A N/A R 45588 45590 Max Vector Shift Max DF/DT Int32 Int32 N/A N/A Centi Centi R R B-54 Units R/W R DGC-2020 Modbus™ Communication Range Bit 0 = Not Used Bit 1 = Not Used Bit 2 = Not Used Bit 3 = Not Used Bit 4 = Not Used Bit 5 = Not Used Bit 6 = Not Used Bit 7 = Not Used Bit 8 = Not Used Bit 9 = Not Used Bit 10 = Not Used Bit 11 = Not Used Bit 12 = Not
45592 45594-95 Current DF/DT Status Metering 2 Int32 Int32 N/A N/A Scaling Factor Centi N/A 45596-97 Gen Protect Pre-Alarm Status Int32 N/A N/A Register Description 9400200990 Rev U Type Units R/W R R R DGC-2020 Modbus™ Communication Range 0 - 100000 Bit 0 = Not Used Bit 1 = Not Used Bit 2 = Not Used Bit 3 = Not Used Bit 4 = Not Used Bit 5 = Not Used Bit 6 = Not Used Bit 7 = Not Used Bit 8 = Not Used Bit 9 = Not Used Bit 10 = Not Used Bit 11 = Not Used Bit 12 = Not Used Bit 13 = Not Used B
45598-99 Gen Protect Alarm Status Int32 N/A Scaling Factor N/A 45600-01 Pre-Alarm Metering 2 Int32 N/A N/A Register B-56 Description Type Units R/W R R DGC-2020 Modbus™ Communication Range Bit 0 = Not Used Bit 1 = Not Used Bit 2 = Not Used Bit 3 = Not Used Bit 4 = Not Used Bit 5 = Not Used Bit 6 = Not Used Bit 7 = Not Used Bit 8 = Not Used Bit 9 = Not Used Bit 10 = Not Used Bit 11 = Not Used Bit 12 = Not Used Bit 13 = Not Used Bit 14 = Not Used Bit 15 = Not Used Bit 16 = Not Used Bit 17 =
Register 45602 45604 45606 45608 45610 45612 45614 45616 45618 45620 45622 45624 45626 45628 45630 45632 45634 45636 45638 45640 45642 45644 45646 45648 45650 45652 45654 45656 45658 45660 45662 45664-748 45750 45752 Description Operating Units Config Data kW Rate of Change Data Generator Network System Manager Data Generator Network Unit ID 1 Generator Network Unit ID 2 Generator Network Unit ID 3 Generator Network Unit ID 4 Generator Network Unit ID 5 Generator Network Unit ID 6 Generator Network Unit ID
Register 45754 45756 45758-60 45762 45764 45766 45768 B-58 N/A Scaling Factor N/A RW Uint32 N/A N/A RW Uint32 N/A N/A R Int32 N/A N/A R Uint32 Uint32 N/A N/A N/A N/A R R Description Type pc Relay Closed: Runs when in Auto mode Test Buttons Image RESERVED Embedded Code Version Number Boot Code Version Number Model Number Embedded Code Part Number Uint32 Units R/W DGC-2020 Modbus™ Communication Range 0 = Stop 1 = Start 0 - 255 9400200990 Rev U
Description Type 45770 Conf Prot 1 Param Select Unit32 N/A Scaling Factor N/A 45772 45774 45776 Conf Prot 1 Hysteresis Conf Prot 1 Arming Delay Conf Prot 1 Threshold 1 Activation Delay Conf Prot 1 Threshold 2 Activation Delay Int32 Int32 Int32 Percent Second Second Int32 Second Register 45778 9400200990 Rev U Units R/W Range RW 0 = Oil Pressure 1 = Coolant Temp 2 = Battery Volts 3 = RPM 4 = Fuel Level 5 = Gen VAB 6 = Gen VBC 7 = Gen VCA 8 = Gen VAN 9 = Gen VBN 10 = Gen VCN 11 = Bus Freq
Conf Prot 1 Over 1 Threshold Conf Prot 1 Over 2 Threshold Conf Prot 1 Under 1 Threshold Conf Prot 1 Under 2 Threshold Conf Prot 1 Over 1 Alarm Type Int32 N/A Scaling Factor Centi Int32 N/A Centi RW (-99999900) - 99999900 Int32 N/A Centi RW (-99999900) - 99999900 Int32 N/A Centi RW (-99999900) - 99999900 Int32 N/A N/A RW 45790 Conf Prot 1 Over 2 Alarm Type Int32 N/A N/A RW 45792 Conf Prot 1 Under 1 Alarm Type Int32 N/A N/A RW 45794 Conf Prot 1 Under 2 Alarm Type Int32 N/
Description Type 45796 Conf Prot 2 Param Select Unit32 N/A Scaling Factor N/A 45798 45800 45802 Conf Prot 2 Hysteresis Conf Prot 2 Arming Delay Conf Prot 2 Threshold 1 Activation Delay Conf Prot 2 Threshold 2 Activation Delay Int32 Int32 Int32 Percent Second Second Int32 Second Register 45804 9400200990 Rev U Units R/W Range RW 0 = Oil Pressure 1 = Coolant Temp 2 = Battery Volts 3 = RPM 4 = Fuel Level 5 = Gen VAB 6 = Gen VBC 7 = Gen VCA 8 = Gen VAN 9 = Gen VBN 10 = Gen VCN 11 = Bus Freq
Conf Prot 2 Over 1 Threshold Conf Prot 2 Over 2 Threshold Conf Prot 2 Under 1 Threshold Conf Prot 2 Under 2 Threshold Conf Prot 2 Over 1 Alarm Type Int32 N/A Scaling Factor Centi Int32 N/A Centi RW (-99999900) - 99999900 Int32 N/A Centi RW (-99999900) - 99999900 Int32 N/A Centi RW (-99999900) - 99999900 Int32 N/A N/A RW 45816 Conf Prot 2 Over 2 Alarm Type Int32 N/A N/A RW 45818 Conf Prot 2 Under 1 Alarm Type Int32 N/A N/A RW 45820 Conf Prot 2 Under 2 Alarm Type Int32 N/
Description Type 45822 Conf Prot 3 Param Select Uint32 N/A Scaling Factor N/A 45824 45826 45828 Conf Prot 3 Hysteresis Conf Prot 3 Arming Delay Conf Prot 3 Threshold 1 Activation Delay Conf Prot 3 Threshold 2 Activation Delay Int32 Int32 Int32 Percent Second Second Int32 Second Register 45830 9400200990 Rev U Units R/W Range RW 0 = Oil Pressure 1 = Coolant Temp 2 = Battery Volts 3 = RPM 4 = Fuel Level 5 = Gen VAB 6 = Gen VBC 7 = Gen VCA 8 = Gen VAN 9 = Gen VBN 10 = Gen VCN 11 = Bus Freq
Conf Prot 3 Over 1 Threshold Conf Prot 3 Over 2 Threshold Conf Prot 3 Under 1 Threshold Conf Prot 3 Under 2 Threshold Conf Prot 3 Over 1 Alarm Type Int32 N/A Scaling Factor Centi Int32 N/A Centi RW (-99999900) - 99999900 Int32 N/A Centi RW (-99999900) - 99999900 Int32 N/A Centi RW (-99999900) - 99999900 Int32 N/A N/A RW 45842 Conf Prot 3 Over 2 Alarm Type Int32 N/A N/A RW 45844 Conf Prot 3 Under 1 Alarm Type Int32 N/A N/A RW 45846 Conf Prot 3 Under 2 Alarm Type Int32 N/
Description Type 45848 Conf Prot 4 Param Select Uint32 N/A Scaling Factor N/A 45850 45852 45854 Conf Prot 4 Hysteresis Conf Prot 4 Arming Delay Conf Prot 4 Threshold 1 Activation Delay Conf Prot 4 Threshold 2 Activation Delay Int32 Int32 Int32 Percent Second Second Int32 Second Register 45856 9400200990 Rev U Units R/W Range RW 0 = Oil Pressure 1 = Coolant Temp 2 = Battery Volts 3 = RPM 4 = Fuel Level 5 = Gen VAB 6 = Gen VBC 7 = Gen VCA 8 = Gen VAN 9 = Gen VBN 10 = Gen VCN 11 = Bus Freq
Conf Prot 4 Over 1 Threshold Conf Prot 4 Over 2 Threshold Conf Prot 4 Under 1 Threshold Conf Prot 4 Under 2 Threshold Conf Prot 4 Over 1 Alarm Type Int32 N/A Scaling Factor Centi Int32 N/A Centi RW (-99999900) - 99999900 Int32 N/A Centi RW (-99999900) - 99999900 Int32 N/A Centi RW (-99999900) - 99999900 Int32 N/A N/A RW 45868 Conf Prot 4 Over 2 Alarm Type Int32 N/A N/A RW 45870 Conf Prot 4 Under 1 Alarm Type Int32 N/A N/A RW 45872 Conf Prot 4 Under 2 Alarm Type Int32 N/
Description Type 45874 Conf Prot 5 Param Select Uint32 N/A Scaling Factor N/A 45876 45878 45880 Conf Prot 5 Hysteresis Conf Prot 5 Arming Delay Conf Prot 5 Threshold 1 Activation Delay Conf Prot 5 Threshold 2 Activation Delay Int32 Int32 Int32 Percent Second Second Int32 Second Register 45882 9400200990 Rev U Units R/W Range RW 0 = Oil Pressure 1 = Coolant Temp 2 = Battery Volts 3 = RPM 4 = Fuel Level 5 = Gen VAB 6 = Gen VBC 7 = Gen VCA 8 = Gen VAN 9 = Gen VBN 10 = Gen VCN 11 = Bus Freq
Conf Prot 5 Over 1 Threshold Conf Prot 5 Over 2 Threshold Conf Prot 5 Under 1 Threshold Conf Prot 5 Under 2 Threshold Conf Prot 5 Over 1 Alarm Type Int32 N/A Scaling Factor Centi Int32 N/A Centi RW (-99999900) - 99999900 Int32 N/A Centi RW (-99999900) - 99999900 Int32 N/A Centi RW (-99999900) - 99999900 Int32 N/A N/A RW 45894 Conf Prot 5 Over 2 Alarm Type Int32 N/A N/A RW 45896 Conf Prot 5 Under 1 Alarm Type Int32 N/A N/A RW 45898 Conf Prot 5 Under 2 Alarm Type Int32 N/
Description Type 45900 Conf Prot 6 Param Select Uint32 N/A Scaling Factor N/A 45902 45904 45906 Conf Prot 6 Hysteresis Conf Prot 6 Arming Delay Conf Prot 6 Threshold 1 Activation Delay Conf Prot 6 Threshold 2 Activation Delay Int32 Int32 Int32 Percent Second Second Int32 Second Register 45908 9400200990 Rev U Units R/W Range RW 0 = Oil Pressure 1 = Coolant Temp 2 = Battery Volts 3 = RPM 4 = Fuel Level 5 = Gen VAB 6 = Gen VBC 7 = Gen VCA 8 = Gen VAN 9 = Gen VBN 10 = Gen VCN 11 = Bus Freq
Conf Prot 6 Over 1 Threshold Conf Prot 6 Over 2 Threshold Conf Prot 6 Under 1 Threshold Conf Prot 6 Under 2 Threshold Conf Prot 6 Over 1 Alarm Type Int32 N/A Scaling Factor Centi Int32 N/A Centi RW (-99999900) - 99999900 Int32 N/A Centi RW (-99999900) - 99999900 Int32 N/A Centi RW (-99999900) - 99999900 Int32 N/A N/A RW 45920 Conf Prot 6 Over 2 Alarm Type Int32 N/A N/A RW 45922 Conf Prot 6 Under 1 Alarm Type Int32 N/A N/A RW 45924 Conf Prot 6 Under 2 Alarm Type Int32 N/
Description Type 45926 Conf Prot 7 Param Select Uint32 N/A Scaling Factor N/A 45928 45930 45932 Conf Prot 7 Hysteresis Conf Prot 7 Arming Delay Conf Prot 7 Threshold 1 Activation Delay Conf Prot 7 Threshold 2 Activation Delay Int32 Int32 Int32 Percent Second Second Int32 Second Register 45934 9400200990 Rev U Units R/W Range RW 0 = Oil Pressure 1 = Coolant Temp 2 = Battery Volts 3 = RPM 4 = Fuel Level 5 = Gen VAB 6 = Gen VBC 7 = Gen VCA 8 = Gen VAN 9 = Gen VBN 10 = Gen VCN 11 = Bus Freq
Conf Prot 7 Over 1 Threshold Conf Prot 7 Over 2 Threshold Conf Prot 7 Under 1 Threshold Conf Prot 7 Under 2 Threshold Conf Prot 7 Over 1 Alarm Type Int32 N/A Scaling Factor Centi Int32 N/A Centi RW (-99999900) - 99999900 Int32 N/A Centi RW (-99999900) - 99999900 Int32 N/A Centi RW (-99999900) - 99999900 Int32 N/A N/A RW 45946 Conf Prot 7 Over 2 Alarm Type Int32 N/A N/A RW 45948 Conf Prot 7 Under 1 Alarm Type Int32 N/A N/A RW 45950 Conf Prot 7 Under 2 Alarm Type Int32 N/
Description Type 45952 Conf Prot 8 Param Select Uint32 N/A Scaling Factor N/A 45954 45956 45958 Conf Prot 8 Hysteresis Conf Prot 8 Arming Delay Conf Prot 8 Threshold 1 Activation Delay Conf Prot 8 Threshold 2 Activation Delay Int32 Int32 Int32 Percent Second Second Int32 Second Register 45960 9400200990 Rev U Units R/W Range RW 0 = Oil Pressure 1 = Coolant Temp 2 = Battery Volts 3 = RPM 4 = Fuel Level 5 = Gen VAB 6 = Gen VBC 7 = Gen VCA 8 = Gen VAN 9 = Gen VBN 10 = Gen VCN 11 = Bus Freq
Conf Prot 8 Over 1 Threshold Conf Prot 8 Over 2 Threshold Conf Prot 8 Under 1 Threshold Conf Prot 8 Under 2 Threshold Conf Prot 8 Over 1 Alarm Type Int32 N/A Scaling Factor Centi Int32 N/A Centi RW (-99999900) - 99999900 Int32 N/A Centi RW (-99999900) - 99999900 Int32 N/A Centi RW (-99999900) - 99999900 Int32 N/A N/A RW 45972 Conf Prot 8 Over 2 Alarm Type Int32 N/A N/A RW 45974 Conf Prot 8 Under 1 Alarm Type Int32 N/A N/A RW 45976 Conf Prot 8 Under 2 Alarm Type Int32 N/
AEM Input 1 Param Max AEM Input 1 Param Min AEM Input 1 Hysteresis AEM Input 1 Arming Delay AEM Input 1 Threshold 1 Activation Delay AEM Input 1 Threshold 2 Activation Delay AEM Input 1 Over 1 Threshold AEM Input 1Over 2 Threshold AEM Input 1 Under 1 Threshold AEM Input 1Under 2 Threshold AEM Input 1 Over 1 Alarm Type Int32 Int32 Int32 Int32 Centi Unit Centi Unit Deci Percent Second Scaling Factor Centi Centi Deci N/A Int32 Second N/A RW 0 – 300 Int32 Second N/A RW 0 – 300 Int32 Centi Unit C
46378 AEM Input 2 Over 2 Alarm Type Int32 N/A Scaling Factor N/A 46380 AEM Input 2 Under 1 Alarm Type Int32 N/A N/A RW 46382 AEM Input 2 Under 2 Alarm Type Int32 N/A N/A RW 46384 AEM Input 2 Out of Range Alarm Type Int32 N/A N/A RW AEM Input 3 Max Voltage Int32 Int32 Int32 Int32 Int32 Int32 Int32 Int32 DeciVolt Milliamp x 10 DeciVolt Milliamp x 10 Centi Unit Centi Unit Deci Percent Second Deci Deci Deci Deci Centi Centi Deci N/A RW RW RW RW RW RW RW RW 0 = None 1 = Alarm 2 = Pre-
AEM Input 4 Hysteresis AEM Input 4 Arming Delay AEM Input 4 Threshold 1 Activation Delay AEM Input 4 Threshold 2 Activation Delay AEM Input 4 Over 1 Threshold AEM Input 4Over 2 Threshold AEM Input 4 Under 1 Threshold AEM Input 4Under 2 Threshold AEM Input 4 Over 1 Alarm Type Int32 Int32 Deci Percent Second Scaling Factor Deci N/A Int32 Second N/A RW 0 – 300 Int32 Second N/A RW 0 – 300 Int32 Centi Unit Centi RW (-100000000) – 99999900 Int32 Centi Unit Centi RW (-100000000) – 99999900
46530 AEM Input 5 Over 2 Alarm Type Int32 N/A Scaling Factor N/A 46532 AEM Input 5 Under 1 Alarm Type Int32 N/A N/A RW 46534 AEM Input 5 Under 2 Alarm Type Int32 N/A N/A RW 46536 AEM Input 5 Out of Range Alarm Type Int32 N/A N/A RW AEM Input 6 Max Voltage Int32 Int32 Int32 Int32 Int32 Int32 Int32 Int32 DeciVolt Milliamp x 10 DeciVolt Milliamp x 10 Centi Unit Centi Unit Deci Percent Second Deci Deci Deci Deci Centi Centi Deci N/A RW RW RW RW RW RW RW RW 0 = None 1 = Alarm 2 = Pre-
AEM Input 7 Hysteresis AEM Input 7 Arming Delay AEM Input 7 Threshold 1 Activation Delay AEM Input 7 Threshold 2 Activation Delay AEM Input 7 Over 1 Threshold AEM Input 7Over 2 Threshold AEM Input 7 Under 1 Threshold AEM Input 7Under 2 Threshold AEM Input 7 Over 1 Alarm Type Int32 Int32 Deci Percent Second Scaling Factor Deci N/A Int32 Second N/A RW 0 – 300 Int32 Second N/A RW 0 – 300 Int32 Centi Unit Centi RW (-100000000) – 99999900 Int32 Centi Unit Centi RW (-100000000) – 99999900
46646 AEM Input 8 Under 1 Alarm Type Int32 N/A Scaling Factor N/A 46648 AEM Input 8 Under 2 Alarm Type Int32 N/A N/A RW 46650 AEM Input 8 Out of Range Alarm Type Int32 N/A N/A RW 46652 AEM Output 1 Max Voltage AEM Output 1 Max Current AEM Output 1 Min Voltage AEM Output 1 Min Current AEM Output 1 Param Max AEM Output 1 Param Min Int32 DeciVolt Deci RW 0 = None 1 = Alarm 2 = Pre-Alarm 3 = Status Only 0 = None 1 = Alarm 2 = Pre-Alarm 3 = Status Only 0 = None 1 = Alarm 2 = Pre-Alarm 3 =
46664 AEM Output 1 Param Selection Uint32 N/A Scaling Factor N/A 46666 AEM Output 1 Out of Range Alarm Type Int32 N/A 46668 AEM Output 1 Out of Range Time Delay Int32 Second Register Description 9400200990 Rev U Type Units R/W Range RW 0 = Oil Pressure 1 = Coolant Temp 2 = Battery Volts 3 = RPM 4 = Fuel Level 5 = Gen VAB 6 = Gen VBC 7 = Gen VCA 8 = Gen VAN 9 = Gen VBN 10 = Gen VCN 11 = Bus Freq 12 = Bus Volts 13 = Gen Freq 14 = Gen PF 15 = Gen IA 16 = Gen IB 17 = Gen IC 18 = kW A 19 = k
Register 46670 46672 46674 46676 46678 46680 B-82 Description Int32 DeciVolt Scaling Factor Deci Int32 Milliamp x 10 Deci RW 40 – 200 Int32 DeciVolt Deci RW 0 – 100 Int32 Milliamp x 10 Deci RW 40 – 200 Int32 Centi Unit Centi RW (-100000000) – 99999900 Int32 Centi Unit Centi RW (-100000000) – 99999900 Type AEM Output 2 Max Voltage AEM Output 2 Max Current AEM Output 2 Min Voltage AEM Output 2 Min Current AEM Output 2 Param Max AEM Output 2 Param Min Units R/W Range RW 0 –
46682 AEM Output 2 Param Selection Uint32 N/A Scaling Factor N/A 46684 AEM Output 2 Out of Range Alarm Type Int32 N/A 46686 AEM Output 2 Out of Range Time Delay Int32 Second Register Description 9400200990 Rev U Type Units R/W Range RW 0 = Oil Pressure 1 = Coolant Temp 2 = Battery Volts 3 = RPM 4 = Fuel Level 5 = Gen VAB 6 = Gen VBC 7 = Gen VCA 8 = Gen VAN 9 = Gen VBN 10 = Gen VCN 11 = Bus Freq 12 = Bus Volts 13 = Gen Freq 14 = Gen PF 15 = Gen IA 16 = Gen IB 17 = Gen IC 18 = kW A 19 = k
Register 46688 46690 46692 46694 46696 46698 B-84 Description Int32 DeciVolt Scaling Factor Deci Int32 Milliamp x 10 Deci RW 40 – 200 Int32 DeciVolt Deci RW 0 – 100 Int32 Milliamp x 10 Deci RW 40 – 200 Int32 Centi Unit Centi RW (-100000000) – 99999900 Int32 Centi Unit Centi RW (-100000000) – 99999900 Type AEM Output 3 Max Voltage AEM Output 3 Max Current AEM Output 3 Min Voltage AEM Output 3 Min Current AEM Output 3 Param Max AEM Output 3 Param Min Units R/W Range RW 0 –
46700 AEM Output 3 Param Selection Uint32 N/A Scaling Factor N/A 46702 AEM Output 3 Out of Range Alarm Type Int32 N/A 46704 AEM Output 3 Out of Range Time Delay Int32 Second Register Description 9400200990 Rev U Type Units R/W Range RW 0 = Oil Pressure 1 = Coolant Temp 2 = Battery Volts 3 = RPM 4 = Fuel Level 5 = Gen VAB 6 = Gen VBC 7 = Gen VCA 8 = Gen VAN 9 = Gen VBN 10 = Gen VCN 11 = Bus Freq 12 = Bus Volts 13 = Gen Freq 14 = Gen PF 15 = Gen IA 16 = Gen IB 17 = Gen IC 18 = kW A 19 = k
Register 46706 46708 46710 46712 46714 46716 B-86 Description Int32 DeciVolt Scaling Factor Deci Int32 Milliamp x 10 Deci RW 40 – 200 Int32 DeciVolt Deci RW 0 – 100 Int32 Milliamp x 10 Deci RW 40 – 200 Int32 Centi Unit Centi RW (-100000000) – 99999900 Int32 Centi Unit Centi RW (-100000000) – 99999900 Type AEM Output 4 Max Voltage AEM Output 4 Max Current AEM Output 4 Min Voltage AEM Output 4 Min Current AEM Output 4 Param Max AEM Output 4 Param Min Units R/W Range RW 0 –
46718 AEM Output 4 Param Selection Uint32 N/A Scaling Factor N/A 46720 AEM Output 4 Out of Range Alarm Type Int32 N/A 46722 AEM Output 4 Out of Range Time Delay Int32 Second Register Description 9400200990 Rev U Type Units R/W Range RW 0 = Oil Pressure 1 = Coolant Temp 2 = Battery Volts 3 = RPM 4 = Fuel Level 5 = Gen VAB 6 = Gen VBC 7 = Gen VCA 8 = Gen VAN 9 = Gen VBN 10 = Gen VCN 11 = Bus Freq 12 = Bus Volts 13 = Gen Freq 14 = Gen PF 15 = Gen IA 16 = Gen IB 17 = Gen IC 18 = kW A 19 = k
Register Description Type Units Scaling Factor R/W 46724 46748 46750 FUTURE USE User Config Input 1 Config Type Int32 N/A N/A RW 46752 User Config Input 1 Time Delay User Config Input 1 Engine Running Only Int32 Second N/A RW Int32 N/A N/A RW 46756 User Config Input 2 Config Type Int32 N/A N/A RW 46758 User Config Input 2 Time Delay User Config Input 2 Engine Running Only Int32 Second N/A RW Int32 N/A N/A RW 46762 User Config Input 3 Config Type Int32 N/A N/A RW 4
46802 User Config Input 9 Engine Running Only Int32 N/A Scaling Factor N/A 46804 User Config Input 10 Config Type Int32 N/A N/A RW 46806 User Config Input 10 Time Delay User Config Input 10 Engine Running Only Int32 Second N/A RW Int32 N/A N/A RW Register 46808 Description Type Units R/W RW 46810 User Config Input 11 Config Type Int32 N/A N/A RW 46812 User Config Input 11 Time Delay User Config Input 11 Engine Running Only Int32 Second N/A RW Int32 N/A N/A RW 46814
46856 User Config Input 18 Engine Running Only Int32 N/A Scaling Factor N/A 46858 User Config Input 19 Config Type Int32 N/A N/A RW 46860 User Config Input 19 Time Delay User Config Input 19 Engine Running Only Int32 Second N/A RW Int32 N/A N/A RW Register 46862 Description Type Units R/W RW 46864 User Config Input 20 Config Type Int32 N/A N/A RW 46866 User Config Input 20 Time Delay User Config Input 20 Engine Running Only Int32 Second N/A RW Int32 N/A N/A RW 4686
46906 ATS Contact Input Int32 N/A Scaling Factor N/A 46908 46910 ATS Time Delay ATS Engine Running Only Int32 Int32 Second N/A N/A N/A RW RW 46912 Battle Override Contact Input Int32 N/A N/A RW 46914 Battle Override Time Delay Battle Override Engine Running Only Int32 Second N/A RW Int32 N/A N/A RW 46918 Low Coolant Level Contact Input Int32 N/A N/A RW 46920 Low Coolant Level Config Type Int32 N/A N/A RW 46922 Low Coolant Level Time Delay Low Coolant Level Engine Runn
46926 Battery Charge Failed Contact Input Int32 N/A Scaling Factor N/A 46928 Battery Charge Failed Config Type Int32 N/A N/A RW 46930 Battery Charge Failed Time Delay Battery Charge Failed Engine Running Only Int32 Second N/A RW Int32 N/A N/A RW Register 46932 Description Type Units R/W RW 46934 Fuel Leak Detect Contact Input Int32 N/A N/A RW 46936 Fuel Leak Detect Config Type Int32 N/A N/A RW 46938 Fuel Leak Detect Time Delay Fuel Leak Detect Engine Running Only Int
Single Phase Connection Override Time Delay Single Phase Connection Override Engine Running Only Single Phase AC Sense Override Contact Input Int32 Second Scaling Factor N/A Int32 N/A N/A RW 0 = Always 1 = While Engine Running Only Int32 N/A N/A RW Single Phase AC Sense Override Time Delay Single Phase AC Sense Override Engine Running Only Hi/Lo Line Contact Input Int32 Second N/A RW -1 = None 0 = Input 1 1 = Input 2 2 = Input 3 3 = Input 4 4 = Input 5 5 = Input 6 6 = Input 7 7 = Input 8 8
Register 46964 Description Type Grounded Delta Override Engine Running Only Int32 Units N/A Scaling Factor N/A R/W Range 0 = Always 1 = While Engine Running Only RW Legacy Parameter Table The DGC-2020 maps all legacy parameters previously associated with the DGC-500 and DGC-1000 into the Holding Register address space (40000 to 41999). Query address N will access the Holding Register N+1. The Data Format is Integer type data unless identified otherwise in the Data Format column.
Holding Register 40044 Parameter Range Enable Read/Write Supported Data Format Units 0-1 RW 40045 Threshold HIGH COOLANT TEMP PRE-ALARM 40046 Enable 95-140 RW 0-1 RW 40047 Threshold LOW OIL PRESSURE PRE-ALARM 40048 Enable 100-280 RW 0-1 RW 40049 Threshold LOW BATTERY VOLTAGE PRE-ALARM 40050 Enable 3-100 RW 0-1 RW 40051 60-120 (12V) 120-240 (24V) 1-10 RW 0.1 Volts DC RW Seconds 0-1 RW 40-80 (12V) 80-160 (24V) 1-10 RW 0.
Holding Register Parameter Range Read/Write Supported 40081 Sender Failure Alarm Code individual bits are 0 or 1 R 40082 Alarm Codes individual bits are 0 or 1 R 40083 Pre-Alarm Codes individual bits are 0 or 1 R 40084 Pre-Alarm Codes, Group 2 individual bits are 0 or 1 R Data Format Units 40085 Engine Coolant Temperature 40086 Engine Oil Pressure 40087 Battery Voltage 40088 Fuel Level 40089 Time Remaining until Maintenance 40090 Accumulated Engine Runtime(a) 40091 Accumulated Engine R
Holding Register Parameter Range Read/Write Supported Data Format Units RMS Volt x 10000 RMS Volt RMS Volt x 10000 RMS Volt RMS Amps RMS Amps RMS Amps KVA x 10000 KVA KVA x 10000 KVA KVA x 10000 KVA KVA x 10000 KVA KWatt x 10000 KWatt KWatt x 10000 KWatt KWatt x 10000 KWatt KWatt x 10000 KWatt KWH x 10000 x 10000 KWH x 10000 KWH 0.01 0.
Holding Register 40281 40282 40283 40287-97 40298 Parameter Range Embedded Code Version Number (a) Embedded Code Version Number (b) Embedded Code Version Number (c) RESERVED Read Relay Image of both Main and Aux Output 40299 RESERVED J1939 DIAGNOSTIC TROUBLE CODES Active DTC Number 16 – Lower 40300 Two Bytes Active DTC Number 16 – Upper 40301 Two Bytes Active DTC Number 15 – Lower 40302 Two Bytes Active DTC Number 15 – Upper 40303 Two Bytes Active DTC Number 14 – Lower 40304 Two Bytes Active DTC Number
Holding Register 40319 40320 40321 40322 40323 40324 40325 40326 40327 40328 40329 40330 40331 40332 40333 40334 40335 40336 40337 40338 40339 40340 40341 40342 40343 40344 40345 40346 40347 40348 40349 40350 Parameter Range Active DTC Number 7 – Upper Two Bytes Active DTC Number 6 – Lower Two Bytes Active DTC Number 6 – Upper Two Bytes Active DTC Number 5 – Lower Two Bytes Active DTC Number 5 – Upper Two Bytes Active DTC Number 4 – Lower Two Bytes Active DTC Number 4 – Upper Two Bytes Active DTC Number
Holding Register Parameter Range Read/Write Supported Previous DTC Number 10 – Upper Two Bytes Previous DTC Number 11 – Lower Two Bytes Previous DTC Number 11 – Upper Two Bytes Previous DTC Number 12 – Lower Two Bytes Previous DTC Number 12 – Upper Two Bytes Previous DTC Number 13 – Lower Two Bytes Previous DTC Number 13 – Upper Two Bytes Previous DTC Number 14 – Lower Two Bytes Previous DTC Number 14 – Upper Two Bytes Previous DTC Number 15 – Lower Two Bytes Previous DTC Number 15 – Upper Two Bytes Pre
Holding Register Parameter Range Read/Write Supported 40372 CAN Communications Diagnostics for use when CAN is enabled. individual bits are 0 or 1 R 40373 System Config individual bits are 0 or 1 RW 40374 System Status 0 - 10 R 40375 Used to display Value, NC, NS, NA, and SF R Data Format Units Bit 12 - .
Holding Register 40395 40396 Parameter Range Read/Write Supported Data Format Units 0-65535 0-65535 RW RW milliseconds minutes 0-65535 RW seconds 0-65535 RW seconds 40399-420 J1939 DATA 40421 Accelerator Pedal Position 40422 Percent Load At Current Speed 0 to 100% 0 to 125% R R 0.
Holding Register Parameter Range Read/Write Supported Data Format Units 40446 Barometric Pressure 0 to +125 kPa (0 to +18.1 psi) R Raw ECU Parameter Data 0.5 kPa/bit gain, 0 kPa offset 40447 Ambient Air Temperature -273 to +1735.0 °C (-459.4 to 3155.0 °F) R Raw ECU Parameter Data 0.03125 °C/bit gain, -273 °C offset 40448 Air Inlet Temperature -40 to +210 °C (-40 to 410 °F) R Raw ECU Parameter Data 1 °C/bit gain, -40 °C offset 40449 Boost Pressure 0 to +500 kPa (0 to 72.
Holding Register Parameter Range Read/Write Supported 40471 Speed Upper Limit 0 to 2500 rpm R 40472 Torque Lower Limit 0 to 125% R 40473 Torque Upper Limit 0 to 125% R 40474 Crankcase Pressure -250 to +251.99 kPa R 40475 Oil Filter Diff. Pressure 0 to 125 kPa R 40476 Fuel Filter Diff. Pressure 0 to 500 kPa R 40477-82 40493-99 40500 FUTURE USE FUTURE USE DGC-2020 product series identifier 2020 R 40501 Firmware Part Number - 2nd most significant digit.
Holding Register Parameter Range 40606 51 Time Dial – 3-phase 40607 40608 40609 51 Curve – 3-phase 51 Alarm Config. – 3-phase 51 Pick-up – 1-phase 40610 51 Time Dial – 1-phase 40611 51 Curve – 1-phase 40612 51 Alarm Config. – 1-phase PHASE IMBALANCE 40613 47 Pick-up 40614 47 Time Delay 40615 47 Alarm Configuration UNDERVOLTAGE 40616 27 Pick-up – 3-phase 40617 27 Time Delay – 3-phase 40618 27 Inhibit Frequency- 3-ph. 40619 27 Alarm Config.
Holding Register Parameter Range Read/Write Supported Data Format Units 40640 Gen Protection Pre-Alarms (lower 16 bits) 0-65535 R 40641 Gen Protection Alarms (upper 16 bits) Gen Protection Alarms (lower 16 bits) 0-65535 R 0-65535 R 0-23 0-59 0-59 1-12 1-31 0-1 RW RW RW RW RW RW RW 0-5000 0-5000 1-12 1-31 0-99 0-4294967295 0-4294967295 RW RW RW RW RW RW RW DP DP hours hours month day year hours hours 0-4294967295 RW DP hours 0-65535 1-12 1-31 0-99 0-4294967295 0-4294967295 0-4294967
Holding Register 40761 Parameter MTU Pre-alarms 9400200990 Rev U Range 0-65535 Read/Write Supported R Data Format Units b0 = High ECU Temp, b1 = High Oil Temp, b2 = High Intercooler Temp, b3 = High Charge Air Temp, b4 = High Coolant Temp, b5 = Shutdown Override, b6 = High Fuel Rail Press, b7 = Low Fuel Rail Press, b8 = Low Coolant Level, b9 = Low Charge Air Pressure, b10 = Low Fuel Deliv Pressure, b11 = Low Oil Pressure, b12 = Combined Yellow, b13-b15 UNASSIGNED DGC-2020 Modbus™ Communication B-107
B-108 DGC-2020 Modbus™ Communication 9400200990 Rev U
APPENDIX C • TUNING PID SETTINGS TABLE OF CONTENTS APPENDIX C • TUNING PID SETTINGS ................................................................................................. C-1 Introduction ............................................................................................................................................ C-1 Tuning Procedures .................................................................................................................................
ii DGC-2020 Tuning PID Settings 9400200990 Rev U
APPENDIX C • TUNING PID SETTINGS Introduction The LSM-2020 (Load Share Module) and DGC-2020 utilize four controllers to accomplish synchronization, load sharing, and speed trim functions. The controllers are a voltage controller, a var/PF controller, a speed controller, and a kW load controller. The voltage and speed controllers are in effect when the DGC-2020 is synchronizing the generator to a bus.
Table C-1 shows the effects of increasing parameters. Table C-1. Effects of Increasing Parameters Parameter Rise Time Overshoot Setting Time Steady State Error Kp Decrease Increase Small Change Decrease Ki Decrease Increase Increase Eliminate Kd Small Change Decrease Decrease None Tuning Procedures Voltage Controller Tuning Procedure The voltage controller is tuned prior to the speed controller.
Tuning of KD can be achieved through the following steps. First set TD=0 to eliminate filtering. Raise speed KD and check for stability. Each time KD is raised, disturb the system by changing the voltage on the bus input of the DGC-2020 so that the DGC-2020 will try to follow it. Verify that the DGC-2020 controls the voltage to go to the new value in a stable manner. Raise KD until the system is unstable, and then lower it to half the value where instability if first attained.
Speed Controller Tuning Procedure The speed controller is tuned prior to the kW load controller. Set Load Control to enabled, and speed trim to enabled. Set all Kp, Ki, and Kd gains in both speed controller and kW load controller to 0. Set the Kg values to 0.1. Start the generator and close the breaker onto some load. KP - Proportional Gain Set an initial value of 1 for KP. Each time KP is set, manually displace the governor lever if possible and see that control is regained in a stable manner.
If it is not possible to obtain stable kW operation, it may be necessary to reduce the control gains in the governor that has its analog bias input driven by the LSM-2020. KI - Integral Gain Set the initial value of KI to be a tenth of the value set for KP. Each time KI is set, parallel a second generator with the unit being tuned, and check for stable load sharing then open the generator breaker on the second generator and check that the unit being tuned is still stable.
C-6 DGC-2020 Tuning PID Settings 9400200990 Rev U
APPENDIX D • MTU FAULT CODES Introduction MTU fault codes displayed by the DGC-2020 are listed in Table D-1. Table D-1. MTU Fault Codes Fault Code Number String Description 3 HI T FUEL Fuel temperature too high (limit 1). 4 SS T FUEL Fuel temperature too high (limit 2). 5 HI T CHRG AIR Charge air temperature too high (limit 1). 6 SS T CHRG AIR Air temperature too high (limit 2). 9 HI T INTERCOOLER Coolant temperature of InterCooler too high (limit 1).
Fault Code Number D-2 String Description 69 L1 T EXTERN 1 Limit 1, out of range. 70 L2 T EXTERN 1 Limit 2, out of range. 71 L1 T EXTERN 2 Limit 1, out of range. 72 L2 T EXTERN 2 Limit 2, out of range. 73 L1 P EXTERN 1 Limit 1, out of range. 74 L2 P EXTERN 1 Limit 2, out of range. 75 L1 P EXTERN 2 Limit 1, out of range. 76 L2 P EXTERN 2 Limit 2, out of range. 77 LIM EXT CLNT LEV Binary signal 1 Plant active. 78 LIM INTERCLR LEV Binary signal 2 Plant active.
Fault Code Number String Description 143 BANK1 ECU DEFECT Internal electronic fault. 144 BANK2 ECU DEFECT Internal electronic fault. 145 15V GOODECU DFCT Internal electronic fault. 147 AD TST1ECU DEFCT Internal electronic fault. 149 AD TST2ECU DEFCT Internal electronic fault. 151 AD TST3ECU DEFCT Internal electronic fault. 170 MI MODULE FAIL Module in maintenance indicator defect. 171 MI NOT ACTIVE WI not active anymore. 172 TBO EXPIRED TBO expired.
Fault Code Number D-4 String Description 231 SD CAMSHAFT SPD Sensor defect on camshaft. 232 SD CHARGER1 SPEED Speed-sensor of basic charger defect. 233 SD CHARGER2 SPEED Speed-sensor of switching charger defect. 240 SD P FUEL Fuel pressure-sensor defect. 241 SD T UMBLASSEN Temperature-sensor of recirculated charge air defect. 242 SD T COOLANT R Redundant coolant temperature-sensor defect. 244 SD P LUBE OIL R Redundant pressure sensor for lube oil defect.
Fault Code Number String Description 288 SD CAN TRBOSW LCK Missing data CAN. 301 TIMING CYLNDR A1 Error in timing of injector cylinder A1: timing value too low/high. 302 TIMING CYLNDR A2 Error in timing of injector cylinder A2: timing value too low/high. 303 TIMING CYLNDR A3 Error in timing of injector cylinder A3: timing value too low/high. 304 TIMING CYLNDR A4 Error in timing of injector cylinder A4: timing value too low/high.
Fault Code Number D-6 String Description 348 OPN LD CYLNDR A8 Open load in injector cable of cylinder A8. 349 OPN LD CYLNDR A9 Open load in injector cable of cylinder A9. 350 OPN LD CYLNDR A10 Open load in injector cable of cylinder A10. 351 OPN LD CYLNDR B1 Open load in injector cable of cylinder B1. 352 OPN LD CYLNDR B2 Open load in injector cable of cylinder B2. 353 OPN LD CYLNDR B3 Open load in injector cable of cylinder B3.
Fault Code Number String Description 413 HIHI U PDU 414 HI L WATER FUEL PREFILT Water level of fuel prefilter too high (limit 1). 415 LO P COOLANT INTRCOOLR Coolant pressure of InterCooler too low (limit 1). 416 SS P COOLANT INTRCOOLR Coolant pressure of InterCooler too low (limit 2). 417 SD L WATER FUEL PREFILT Water level-sensor of fuel prefilter defect. 420 AL L1 AUX 1 Input of Aux 1 injured limit 1. 421 AL L2 AUX 1 Input of Aux 1 injured limit 2.
Fault Code Number D-8 String Description 510 AL OVERRIDE APPLIED Override applied. 515 STARTER NOT ENGAGED Starter of POM could not be engaged. 543 MULTIPLE FDH SLAVES There is more than one device which is configured as Backup for FDHFunctionality. 544 CONFIGURATION CHANGED Gets active in case of changing system configuration e.g. by changing ECU- or SAM-Device. Remains until undo procedure or data is transferred by a valid maintenance case. Is cancelled automatically.
APPENDIX E • EXHAUST TREATMENT TABLE OF CONTENTS APPENDIX E • EXHAUST TREATMENT ................................................................................................. E-1 Diesel Particulate Filter (DPF) ............................................................................................................... E-1 Regeneration ...................................................................................................................................... E-1 DPF Control ..................
ii DGC-2020 Exhaust Treatment 9400200990 Rev U
APPENDIX E • EXHAUST TREATMENT Diesel Particulate Filter (DPF) In order to meet Tier 4 emission requirements, some engine manufacturers are applying Diesel Particulate Filters (DPF) to the exhaust system of the engine. A Diesel Particulate Filter traps particulate matter contained in diesel exhaust and prevents it from distributing into the air. The particulate matter is later burned off during a regeneration process.
DPF Status and Pre-Alarms The DGC-2020 receives DPF status information which is broadcast from the engine ECU in various Parameter Group Numbers (PGN) and Suspect Parameter Numbers (SPN). The DGC-2020 displays this information on the front panel, and in BESTCOMSPlus, via DPF related pre-alarms. The J1939 parameters and the resulting DGC-2020 pre-alarms are summarized in the following paragraphs.
Exhaust After Treatment Systems (EATS) In order to meet Tier 4 emission requirements, some engine manufacturers are adding Exhaust After Treatment Systems (EATS) which treat the engine exhaust within the exhaust system to reduce particulate matter and harmful contaminants prior to releasing the exhaust into the atmosphere. One such system uses urea-based Diesel Exhaust Fluid (DEF) catalyst which is combined with the exhaust gasses in the EATS to bring the emissions to acceptable levels.
inducement will be active after the next restart. After the second restart, a service tool is required to exit the severe inducement. • E-4 With Service Tool Clearing: Invoke 0% torque reduction with service tool clearing until proper DEF level and quality evaluation. If low level or poor DEF quality is detected during the next monitoring cycle, the severe inducement will be active after the next restart.
12570 State Route 143 Highland IL 62249-1074 USA Tel: +1 618.654.2341 Fax: +1.618.654.2351 email: info@basler.com P.A.E. Les Pins 67319 Wasselonne Cedex FRANCE Tel: +33 3.88.87.1010 Fax: +33 3.88.87.0808 email: franceinfo@basler.com No. 59 Heshun Road Loufeng District (N) Suzhou Industrial Park 215122 Suzhou P.R. CHINA Tel: +86 512.8227.2880 Fax: +86 512.8227.2887 email: chinainfo@basler.com 111 North Bridge Road 15-06 Peninsula Plaza Singapore 179098 Tel: +65 68.44.6445 Fax: +65 68.44.