Owner manual
SERIAL MODULE INSTALLATION (continued)
3
label
DIP
switches
Figure 4. Termination resistor DIP switches on
bottom of Serial Module. Must be ON for ATS
farthest away from the h ost device.
Setting the ATS Address
Set the communication address in the ATS controller.
Follow either the 4000 & 7000 Series procedure or the
Series 300 procedure below. Use Table D to record the
address and other ATS information.
4000 & 7000 Series ATSs
1. R efer to Group 5 Controller User’s Guide 381333–126
pages 2–8 and 2–9 for how to set a unique address for
this Automatic Transfer Switc h.
2. If ASCObus II protocol is used (such as used with VPi
com puter software) and a Power Manager is included
with the ATS, the P ow er Manager mu st be
programmed with the same
address as that sel ected for
the ATS Group 5 Controll er connected to the Serial
Module.
However, if ModbusprotocolisusedandaPower
Manager is included with the ATS, the P ower Manager
must be programmed with a different and unique
address (not the same
as the address of the Controller).
F or setting the address in P ow er Manager Xp refer to
Operator’s Manual 381333–199.
Series 300 ATSs
1. Remove the cover from the control l er by releasing the
latchontherightsidewithyourthumb.SeeFigure5.
2. Locate DIP switc h S3 (left center) and set a unique
addr es s for this ATS. Use a ball---point pen (or similar
pointed tool) to slide the sw itch actu ators left or right
so that they m atc h the illustration next to the setting
(left=off, right=on). R echeck the setting. See Figures
6 and 7, and refer to Table C on the next page.
3. R einstall the c over on the controller by hooking it on
the left side and latching the right side.
4. The Series 300 ATS Group 1 Controller uses ASCO-
bus II protoc ol. Therefore, if a P ower Manager is
inc luded with the ATS, the Power Manager must be
programmed with the same
address as that sel ected for
the ATS Group 1 Controll er connected to the Serial
Modul e. Refer to Operator’s Manual 381333–199.
thumb
latch
cover
hook on
left side
Figure 5. Group 1 Controller cover latch.
S3 DIP
switch
Figure 6. Location of S3 DIP switch in
Group 1 Controller (Series 300 ATSs).
DIP
switch
SW3
actuator
onoff
(8 on each DIP switch)
Figure 7. Setting DIP switch actuators.