Spec Sheet
27.375"
29.75”
36"
PG. 3
Notes: (1) All measurements are in db(a). (2) Tested at 7 meters (23 ft.).
Notes: Control displays generic fault codes.
225 S. Cordova Ave Le Center, MN 56057 • 1-800-733-2112 • www.wincogen.com
SP-108/D • PSS8B/F
Specications are subject to change without notice.
PSS8B
BRAND BRIGGS & STRATTON
MODEL VANGUARD
SPEED 3600 RPM
DISPLACEMENT 570 CC/OHV
CYLINDERS V-TWIN
LUBRICATION FORCED W/ SPIN-ON FILTER
IGNITION ELECTRIC
GOVERNOR MECHANICAL
REGULATION +/- 1.8 HZ STEADY STATE
EXHAUST CRITICAL GRADE, GLASS-PACK
LOW OIL PROTECTION STANDARD
HIGH OIL TEMP PROTECTION STANDARD
RECOMMENDED OIL
(1)
10W-30
OIL CAPACITY 1.5 QTS
ENGINE WARRANTY
(2)
3 YRS
FAIL TO START YES
FAIL TO STOP YES
LOW OIL PRESSURE YES
HIGH ENGINE OIL TEMP YES
UNDER FREQUENCY/SPEED YES
OVER FREQUENCY/SPEED YES
LOW VOLTAGE YES
HIGH VOLTAGE YES
BATTERY OVER/UNDER VOLTAGE YES
DIGITAL DISPLAY YES
2-WIRE CONTROL FEATURES
SOUND DATA
(1)(2)
DC SYSTEM VOLTAGE 12V
DC ALTERNATOR ENGINE MOUNTED
BATTER RACK/CABLE INCLUDED
BATTERY CHARGER 3 STAGE INCLUDED
REQUIRED BATTERY
(1)
GROUP 26 500 CCA
Notes: (1) Battery not included
DIMENSIONS (LxWxH) 36" x 29.75" x 27.375"
NET WEIGHT 388 LBS
SHIPPING DIMENSIONS 45” x 31” x 32”
SHIP WEIGHT 400 LBS
FREIGHT CLASS 70
BATTERY SHIPPING
Exclusive three chamber
design controls air movement
through the generator.
Critical grade mufer reduces
exhaust noise about 25 dba
making the generator very
neighbor friendly.
Pressurized engine
compartment prevents hot
spots by forcing total air
circulation.
After the engine is shut down
the venting system takes
advantage of convection to
reduce heat soak.
Heat is discharged away from
intakes to prevent recirculation.
Generator Cooling
System
Three intakes provide adequate air ow even if
intakes become partially obstructed.
FRONT
RIGHT
LEFT
BACK
Top View
NO LOAD FULL LOAD
LEFT RIGHT FRONT BACK LEFT RIGHT FRONT BACK
63.2 64.4 66.4 63.8 64.9 65.3 68.5 65.3