Spec Sheet

PG. 2
VOLTAGE REGULATION +/-5%
TOTAL HARMONIC DISTORTION
<5%
TEMPERATURE RISE
125°/40° C
PHASE SINGLE
TYPE 2 POLE ROTATING FIELD
BRUSHLESS YES
GENERATOR SPEED 3600 RPM
VOLTAGE CONTROL CAPACITOR
ROTOR 2/3 PITCH
WINDINGS 100% COPPER
LOAD ACCEPTANCE 100% RATING/SINGLE STEP
SEALED BALL BEARINGS 1
WAVE DISTORTION <1.5%
TELEPHONE INTERFERENCE <2%
INSULATION CLASS H
GENERATOR WARRANTY
(1)
2 YR
MOTOR STARTING (CODE G)
(1)
3 HP
PRIME APPLICATIONS YES
CARB/EPA APPROVED YES
CSA APPROVED YES
UL2200 LISTED YES
WINCO WARRANTY
(2)
1 YR/1000 HRS
Notes: (1) Review 'Derating Factors" while sizing this generator for your specic application.The solar panel option has a 25 Amp circuit breaker. (2)
Unity (1.0) power factor.
Notes: (1) Add 3' for each elbow. Do NOT use 'street ells'.
SPECIFICATIONS
SP-108/D • PSS8B/F
PSS8B
BRAND BRIGGS & STRATTON
MODEL VANGUARD
SPEED 3600 RPM
DISPLACEMENT 570 CC/OHV
CYLINDERS V-TWIN
LUBRICATION FORCED W/ SPIN-ON FILTER
IGNITION ELECTRIC
GOVERNOR MECHANICAL
REGULATION +/- 1.8 HZ STEADY STATE
EXHAUST CRITICAL GRADE, GLASS-PACK
LOW OIL PROTECTION STANDARD
HIGH OIL TEMP PROTECTION STANDARD
RECOMMENDED OIL
(1)
10W-30
OIL CAPACITY 1.5 QTS
ENGINE WARRANTY
(2)
2 YRS
GENERATOR
GENERATOR SET
ENGINE
FUEL GENSET
FUEL CONSUMPTION
LP
NG
1.6 GAL/HR - 158,760 BTU/HR
132 FT³/HR - 132,000 BTU/HR
FUEL TANK SIZING
60° F (16°C)
32° F (0° C)
0° F (-18° C)
-20° F (-29° C)
150 GAL
150 GAL
250 GAL
500 GAL
LINE SIZING
(1)
UP TO 25'
25'-100'
OVER 100'
3/4" PIPE
1" PIPE
USE A 2 REGULATOR SYSTEM
INLET PRESSURE 4-6 OZ / 7"-11" WATER COLUMN
OUTPUT LP GAS
(1)
NATURAL GAS
(1)
CIRCUIT BREAKER
WATTS KVA AMPS
(2)
WATTS KVA AMPS
(2)
AMPS
120/240V 1-PH 8,400 8.4 35 7,600 7.6 32 35
NOTES: (1) This oil is recommended for most applications. See Operator’s Manual for
more details on the appropriate oil type for your needs. (2) Contact your local Briggs &
Stratton service center for engine warranty assistance.
NOTES: (1) Gode G capacitor motor. (2) Unit warranty good for emergency and prime
uses. For generator warranty information contact your local WINCO service center.
NOTES: (1) Generator warranty good for emergency and prime uses. For generator
warranty information contact your local WINCO service center.
DERATING FACTORS
TEMPERATURE > 104°F 3% PER 10°F
ALTITUDE 3% PER 1000 FT
PRIME POWER 20%
MAX OPERATING TEMP 122°F/50°C