Specification Sheet

PG. 2
225 S. Cordova Ave Le Center MN • 1-800-733-2112 • www.wincogen.com
SPECIFICATIONS
SP-133/B • W120FPTOT-18
Specications are subject to change without notice.
W120FPTOT-18
VOLTAGE REGULATION +/- 5%
TOTAL HARMONIC DISTORTION
< 5%
RATING
150° C
TYPE 4 POLE ROTATING FIELD
BRUSHED NO
GENERATOR SPEED 1800 RPM
VOLTAGE CONTROL AVR SX460
INSULATION CLASS H
CONTINUOUS WATTS 120,000
AMPS
(1)
180
OUTPUT 277/480 V
PHASE THREE
PTO INPUT SPEED 1000 RPM
INPUT SHAFT SIZE 1 3/4" - 20 SPLINE
REQUIRED INPUT HP
(2)
240
MOTOR STARTING
(3)
50 HP
FREQUENCY METER YES
MAIN CIRCUIT BREAKER 175 AMP
BONDED NEUTRAL YES
GROUND LUG YES
GEARCASE OIL SAE 85W 90-140
GEARCASE OIL CAPACITY 2.75 PINTS
LIFTING EYE YES
WARRANTY
(4)
3 YRS
120/240 VOLT ANDERSON 350 AMPS
DIMENSIONS (LxWxH) 47" x 21.2" x 30.4"
NET WEIGHT 1206 LBS
SHIPPING DIMENSIONS 55.25” x 28.5” x 36”
SHIP WEIGHT 1216 LBS
FREIGHT CLASS 65
NOTES: (1) 0.8 power factor (2) Required HP at PTO of tractor for full rated output. Each
2 HP of tractor power equals approximately 1 kW of electric power. (3) Code G capacitor 
start motor. Please consult factory or authorized dealer for further information. (4) 3 year
warranty for farm use only, other uses have a 1 year warranty. Please consult factory or
authorized dealer for further information.
SHIPPING
W120FPTOT
RECEPTACLE
GENERATOR END
30.4"
21.2”
47"
16" 16"