Installation Guide
1190828-UIM-G-0915
10 Johnson Controls Unitary Products
TABLE 7:
Electrical Data For Single Source Power Supply: 208/230-1-60
Air Handler Models
Heater
Models
1,2
1. (0,1) - maybe 0 (no service disconnect) or 1 (with service disconnect).
2. (1,2) maybe 1 (with service disconnect, no breaker jumper bar) or 2 (with service disconnect & breaker jumper bar).
Heater
Amps @240V
Field Wiring
Min. Circuit Ampacity
MOP.
3
3. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. Refer to the latest edition of the National Electric Code or in
Canada the Canadian electrical Code and local codes to determine correct wire sizing.
208V 230V 208V 230V
MP08B
6HK(0,1)6500206 10 12.4 13.7 15 15
6HK(0,1)6500506 20 23.2 25.7 25 30
6HK(0,1)6500806 32 36.4 40.3 40 45
6HK(0,1)6501006 40 44.9 49.6 45 50
6HK(1,2)6501306 52 58.1 64.3 60 70
MP12B
6HK(0,1)6500206 10 13.8 15.2 15 20
6HK(0,1)6500506 20 24.6 27.2 25 30
6HK(0,1)6500806 32 37.8 41.8 40 45
6HK(0,1)6501006 40 46.2 51.1 50 60
6HK(1,2)6501306 52 59.4 65.8 60 70
6HK(1,2)6501506 60 67.8 75.0 70 80
6HK(1,2)6501806 72 81.1 89.7 90 90
6HK(1,2)6502006 80 89.5 98.9 90 100
MP14D
6HK(0,1)6500206 10 14.0 15.5 15 20
6HK(0,1)6500506 20 24.8 27.4 30 30
6HK(0,1)6500806 32 38.0 42.1 40 45
6HK(0,1)6501006 40 46.4 51.3 50 60
6HK(1,2)6501306 52 59.7 66.0 60 70
6HK(1,2)6501506 60 68.1 75.2 70 80
6HK(1,2)6501806 72 81.3 89.9 90 90
6HK(1,2)6502006 80 89.7 99.2 90 100
MP16C
6HK(0,1)6500206 10 14.1 15.6 15 20
6HK(0,1)6500506 20 24.9 27.5 30 30
6HK(0,1)6500806 32 38.1 42.2 40 45
6HK(0,1)6501006 40 46.5 51.5 50 60
6HK(1,2)6501306 52 59.8 66.1 70 70
6HK(1,2)6501506 60 68.2 75.4 70 80
6HK(1,2)6501806 72 81.4 90.0 90 90
6HK(1,2)6502006 80 89.8 99.3 90 100
MP20D
6HK(0,1)6500206 10 15.5 17.1 20 20
6HK(0,1)6500506 20 26.3 29.0 30 30
6HK(0,1)6500806 32 39.5 43.7 40 45
6HK(0,1)6501006 40 47.9 53.0 50 60
6HK(1,2)6501306 52 61.1 67.6 70 70
6HK(1,2)6501506 60 69.5 76.9 70 80
6HK(1,2)6501806 72 82.8 91.5 90 100
6HK(1,2)6502006 80 91.2 100.8 100 110