Dimensions Guide
6 Johnson Controls Unitary Products
5006168-CTG-C-1015
ELECTRICAL HEAT - MINIMUM FAN SPEED
Heater Kit Models
1,2
Nom. kW
@240V
Air Handler Models
MP08B MP12B MP14D MP16C MP20D
6HK(0,1)6500206 2.4 Low Low Low Low Low
6HK(0,1)6500506 4.8 Low Low Low Low Low
6HK(0,1)6500806 7.7 Low Low Low Low Low
6HK(0,1)6501006 9.6 Low Low Low Low Low
6HK(1,2)6501306 12.5 Med Low Low Low Low
6HK(1,2)6501506 14.4 – Med Low Low Low
6HK(1,2)6501806 17.3 – Med Low Low
Low
6HK(1,2)6502006 19.2 – Med Med High
Low
1. (0,1) - 0 = no circuit breaker OR 1 = with circuit breaker.
2. (1,2) - 1 = with circuit breaker, no breaker jumper bar OR 2 = with circuit breaker & breaker jumper bar.
ELECTRIC HEAT PERFORMANCE DATA: 208/230-1-60
Heater
Models
1,2
Nominal kW
@240V
Total Heat
3
kW Staging
kW MBH W1 Only W1 + W2
208V 230V 208V 230V 208V 230V 208V 230V
1PH
6HK(0,1)6500206 2.4 1.8 2.2 6.2 7.5 1.8 2.2 1.8 2.2
6HK(0,1)6500506 4.8 3.6 4.4 12.3 15 3.6 4.4 3.6 4.4
6HK(0,1)6500806 7.7 5.8 7.1 19.7 24.1 5.8 7.1 5.8 7.1
6HK(0,1)6501006 9.6 7.2 8.8 24.6 30.1 7.2 8.8 7.2 8.8
6HK(1,2)6501306 12.5 9.4 11.5 32 39.2 3.1 3.8 9.4 11.5
6HK(1,2)6501506 14.4 10.8 13.2 36.9 45.1 3.6 4.4 10.8 13.2
6HK(1,2)6501806 17.3 13 15.9 44.3 54.2 6.5 7.9 13 15.9
6HK(1,2)6502006 19.2 14.4 17.6 49.2 60.2 7.2 8.8 14.4 17.6
1. (0,1) - 0 = no service disconnect OR 1 = with service disconnect.
2. (1,2) - 1 = with service disconnect, no breaker jumper bar OR 2 = with service disconnect & breaker jumper bar.
3. For different power distributions, see conversion table on Page 4.