Dimensions Guide

8 Johnson Controls Unitary Products
5006168-CTG-C-1015
ELECTRICAL DATA FOR MULTI-SOURCE POWER SUPPLY: 208/230-1-60
Air Handler
Models
Heater
Models
1,2
Heater
Amps
@240V
Min. Circuit Ampacity
MOP.
3
208V 230V 208V 230V
Circuit Circuit
1st 2nd
1st
3
2nd
1st
3
2nd
1st
3
2nd
MP08B 6HK16501306 52 20.5 37.6 22.5 41.5 25 40 25 45
MP12B
6HK16501306 52 22.0 37.6 24.0 41.5 25 40 25 45
6HK16501506 60 24.9 43.3 27.2 47.9 25 45 30 50
6HK16501806 72 42.3 39.0 46.4 43.1 45 40
50 45
6HK16502006 80 46.6 43.3 51.2 47.9 50 45
60 50
MP14D
6HK16501306 52 22.3 37.6 24.3 41.5 25 40
25 45
6HK16501506 60 25.2 43.3 27.5 47.9 30 45
30 50
6HK16501806 72 29.5 39.0 46.6 43.1 30 40
50 45
6HK16502006 80 32.4 43.3 51.4 47.9 35 45
60 50
MP16C
6HK16501306 52
22.4 37.6 24.4 41.5 25 40 25 45
6HK16501506 60
25.3 43.3 27.6 47.9 30 45 30 50
6HK16501806 72
42.6 39.0 46.8 43.1 30 40 50 45
6HK16502006 80
47.0 43.3 51.5 47.9 35 45 60 50
MP20D
6HK16501306 52
23.9 37.6 25.9 41.5 25 40 30 45
6HK16501506 60 26.8 43.3 29.1 47.9 30 45 30 50
6HK16501806 72 44.1 39.0 48.3 43.1 45 40 50 45
6HK16502006 80 48.5 43.3 53.0 47.9 50 45 60 50
1. (0,1) - 0 = no service disconnect OR 1 = with service disconnect.
2. (1,2) - 1 = with service disconnect, no breaker jumper bar OR 2 = with service disconnect & breaker jumper bar.
3. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. The 1st circuit includes blower motor amps. Refer to the lat-
est edition of the National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing.
kW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT
For a power distribution voltage that is different than the provided nominal voltage, multiply the kW and MBH data from the table by the conversion
factor in the following table.
DISTRIBUTION POWER NOMINAL VOLTAGE CONVERSION FACTOR
208V 240V 0.75
220V 240V 0.84
230V 240V 0.92
APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM
% Of Rated Airflow (CFM)
80% 90% 100% 110% 120%
Capacity Factor
0.96 0.98 1.00 1.02 1.03
POWER WIRING - LINE CONNECTIONS
GND
.
FIELD POWER WIRING
(208/230V)
NO ELECTRIC HEAT
COMPONENT CODES
CKT - CIRCUIT
CN - WIRE CONNECTOR/NUT
GND - GROUND LUG
SD - SERVICE DISCONNECT
POWER
SUPPLY
CN
CN
GND
JUMPER BAR
SINGLE SOURCE POWER
MULTI-SOURCE POWERSINGLE-SOURCE POWER
WITH JUMPER BAR
TERMINAL BLOCK OR
SERVICE DISCONNECT
POWER
SUPPLY
POWER
SUPPLY
2 CIRCUITS ON 13KW-20KW
SD
SD
POWER
SUPPLY
GND
GND
L1
L2
L1
L2
L1
L2
L1
L2
SD
SD
CKT 2
CKT 1
SINGLE PHASE ELECTRIC HEAT OPTIONS:
2 CIRCUITS ON 13KW-20KW
A0429-001