Dimensions Guide

Subject to change without notice. Published in U.S.A. 5425619-BTG-C-1018
Copyright © 2017 by Johnson Controls, Inc. All rights reserved. Supersedes: 5425619-BTG-B-1217
York International Corp.
5005 York Drive
Norman, OK 73069
AIR FLOW DATA
HIGH / LOW SPEED COOLING AND HEAT PUMP CFM
040A10 060B12 080B12 080C16 Jumper Settings
HIGH COOL LOW COOL HIGH COOL LOW COOL HIGH COOL LOW COOL HIGH COOL LOW COOL COOL Tap ADJ Tap
1033 749 1425 838 1228 834 1741 1049 A B
941 666 1087 714 1058 739 1505 916 B B
950 675 1200 771 1143 781 1446 946 A A
877 611 996 658 952 686 1343 843 B A
886 620 1075 703 1037 728 1402 858 A C
785 538 861 579 845 611 1255 799 C B
804 547 895 590 866 622 1167 769 B C
685 483 669 454 686 505 1005 666 D B
740 492 782 533 792 568 1108 710 C A
630 428 613 421 632 473 916 593 D A
666 437 714 477 739 526 990 637 C C
565 428 556 421 579 473 828 534 D C
100C16 100C20 120D20 Jumper Settings
HIGH COOL LOW COOL HIGH COOL LOW COOL HIGH COOL LOW COOL COOL Tap ADJ Tap
1757 1093 2105 1423 2176 1374 A B
1531 966 1724 1121 1733 1100 B B
1474 995 1945 1282 1986 1248 A A
1376 896 1583 1021 1585 1016 B A
1432 910 1744 1141 1775 1121 A C
1291 854 1543 961 1501 973 C B
1206 825 1423 880 1374 910 B C
1051 727 1302 800 1248 847 D B
1150 769 1423 840 1332 889 C A
966 656 1182 700 1163 784 D A
1037 698 1242 760 1206 805 C C
882 600 1081 599 1037 699 D C
HIGH/LOW HEAT CFM
040A10 060B12 080B12 080C16 Jumper Settings
HIGH HEAT LOW HEAT HIGH HEAT LOW HEAT HIGH HEAT LOW HEAT HIGH HEAT LOW HEAT HEAT Jumper ADJ Jumper
890 770 1200 870 1366 1156 1580 1156 A ANY
790 660 1070 770 1293 1022 1422 1027 B ANY
711 578 970 693 1185 924 1293 924 C ANY
646 514 890 630 1094 840 1185 840 D ANY
100C16 100C20 120D20 Jumper Settings
HIGH HEAT LOW HEAT HIGH HEAT LOW HEAT HIGH HEAT LOW HEAT HEAT Jumper ADJ Jumper
1975 1444 1975 1284 2250 1539 A ANY
1778 1284 1778 1156 2133 1385 B ANY
1616 1156 1616 1050 1939 1259 C ANY
1481 1050 1481 963 1778 1154 D ANY
All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to 0.6” w.c.
static pressure. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 1.0” w.c. external static
pressure is not recommended.
NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower that what is required to operate an airflow switch on certain models of electronic air clean-
ers. Consult the instructions for the electronic air cleaner for further details.
* The ADJ “D” tap should not be used.