Installation Guide

5724452-UIM-A-0619
Johnson Controls Ducted Systems 9
TABLE 5:
Default Blower Speeds for FER Compliance - Electrical Heat Only
Model Number
High Sales Volume
Heat Kit
1,2,3
Nom. kW
@240 V
Default Blower Speeds
w1/[w1+w2] Heat Max. Airflow Continuous Fan
ME08B 6HK(0,1)6500506 4.8 kW w1 Medium (3) High (5) Low (1)
ME12B 6HK(0,1)6500806 7.7 kW w1 Medium (3) High (5) Low (1)
ME12C 6HK(0,1)6501006 9.6 kW w1 Medium (3) High (5) Low (1)
ME14D
4
6HK(1,2)6501506 14.4 kW w1+w2 Medium (3) High (5) Low (1)
ME16C
4
6HK(1,2)6501506 14.4 kW w1+w2 Medium Low (2) High (5) Low (1)
ME20D 6HK(1,2)6502006 19.2 kW w1 Low (1) High (5) Low (1)
1. (0,1) - 0 = no service disconnect OR 1 = with service disconnect
2. (1,2) - 1 = with service disconnect, no breaker jumper bar OR 2 = with service disconnect and breaker jumper bar
3. 6HK3 = 3-phase with terminal block connectors only. 6HK4 = 3-phase with service disconnect
4. For ME14D and ME16C models with a 15 kW (6HK*65015**) heat kit, tie the AHU W1 and W2 thermostat inputs together for FER compliance.
TABLE 6: KW and MBH Conversions - For Total Power Input Requirement
For a power distribution voltage that is different than the provided nominal voltage, multiply the kW and MBH data from the table by the conversion
factor in the following table.
DISTRIBUTION POWER NOMINAL VOLTAGE CONVERSION FACTOR
208 V 240 V 0.75
220 V 240 V 0.84
230 V 240 V 0.92
TABLE 7:
Electric Heat Performance Data: 208/230-1-60 and 208/230-3-60
Heater Models
1,2,3
Nominal kW
@240 V
Total Heat
4
kW Staging
kW MBH W1 Only W1 + W2
208 V 230 V 208 V 230 V 208 V 230 V 208 V 230 V
1PH
6HK(0,1)6500206 2.4 1.8 2.2 6.2 7.5 1.8 2.2 1.8 2.2
6HK(0,1)6500506 4.8 3.6 4.4 12.3 15 3.6 4.4 3.6 4.4
6HK(0,1)6500806 7.7 5.8 7.1 19.7 24.1 5.8 7.1 5.8 7.1
6HK(0,1)6501006 9.6 7.2 8.8 24.6 30.1 7.2 8.8 7.2 8.8
6HK(1,2)6501306 12.5 9.4 11.5 32 39.2 3.1 3.8 9.4 11.5
6HK(1,2)6501506 14.4 10.8 13.2 36.9 45.1 3.6 4.4 10.8 13.2
6HK(1,2)6501806 17.3 13 15.9 44.3 54.2 6.5 7.9 13 15.9
6HK(1,2)6502006 19.2 14.4 17.6 49.2 60.2 7.2 8.8 14.4 17.6
6HK(1,2)6502506 24 18 22 61.5 75.2 7.2 8.8 18 22
3PH
6HK36501025 9.6 7.2 8.8 24.6 30.1 7.2 8.8 7.2 8.8
6HK36501525 14.4 10.8 13.2 36.9 45.1 10.8 13.2 10.8 13.2
6HK36501825 17.3 13 15.9 44.3 54.2 6.5 7.9 13 15.9
6HK46502025 19.2 14.4 17.6 49.2 60.2 7.2 8.8 14.4 17.6
6HK46502525 24 18 22 61.5 75.2 9 11 18 22
1. (0,1) - 0 = no service disconnect OR 1 = with service disconnect
2. (1,2) - 1 = with service disconnect, no breaker jumper bar OR 2 = with service disconnect and breaker jumper bar
3. 6HK3 = 3-phase with terminal block connectors only. 6HK4 = 3-phase with service disconnect
4. For different power distributions, see the conversion table above.