Installation Guide
5724452-UIM-A-0619
8 Johnson Controls Ducted Systems
SECTION IX: UNIT DATA
TABLE 2:
Physical and Electrical Data - Cooling Only
Models ME08B ME12B ME12C ME14D ME16C ME20D
Blower - Diameter x Width 10 x 8 10 x 8 11 x 10 11 x 10 11 x 10 11 x 10
Motor
HP 1/3 HP 1/2 HP 1/2 HP 1/2 HP 3/4 HP 3/4 HP
Nominal RPM 1050 1050 1050 1050 1050 1050
Voltage 208/230 208/230 208/230 208/230 208/230 208/230
Full Load Amps @230 V 2.6 3.8 3.8 3.8 5.4 5.4
Filter
1
Type DISPOSABLE OR WASHABLE
Size 16 x 20 x 1 16 x 20 x 1 20 x 20 x 1 22 x 20 x 1 20 x 20 x 1 22 x 20 x 1
Bottom Rack Kit 1BR01117 1BR01117 1BR01121 1BR01124 1BR01121 1BR01124
Permanent Type Kit 1PF0601 1PF0601 1PF0602 1PF0603 1PF0602 1PF0603
Shipping / Operating Weight (lb) 52/51 52/51 68/67 75/74 68/67 75/74
1. Field supplied.
TABLE 3:
Electrical Data - Cooling Only
Models
Motor FLA
1
Minimum Circuit Ampacity
MOP
2
ME08B 2.6 3.3
15ME12B/ME12C/ME14D 3.8 4.8
ME16C/ME20D 5.4 6.8
1. FLA = Full Load Amps.
2. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. Refer to the latest edition of the
National Electrical Code or in Canada the Canadian Electrical Code and local codes to determine correct wire sizing.
TABLE 4:
Minimum Fan Speed - Electrical Heat with Heat Pump
Heat Kit Models
1,2,3
Nom. kW
@240 V
Air Handler Models
ME08B ME12B ME12C ME14D ME16C ME20D
6HK(0,1)6500206 2.4 kW Medium Low (2) Medium Low (2) Medium Low (2) Medium Low (2) Medium Low (2) Medium Low (2)
6HK(0,1)6500506 4.8 kW Medium (3) Medium Low (2) Medium (3) Medium Low (2) Medium Low (2) Medium Low (2)
6HK(0,1)6500806 7.7 kW Medium High (4) Medium Low (2) Medium High (4) Medium (3) Medium Low (2) Medium Low (2)
6HK(0,1)6501006
6HK36501025
9.6 kW Medium High (4) Medium Low (2) Medium High (4) Medium (3) Medium Low (2) Medium Low (2)
6HK(1,2)6501306 12.5 kW High (5) Medium High (4) Medium High (4) Medium (3) Medium Low (2) Medium Low (2)
6HK(1,2)6501506
6HK36501525
14.4 kW – High (5) Medium High (4) Medium (3) Medium Low (2) Medium Low (2)
6HK(1,2)6501806
6HK36501825
17.3 kW – High (5) Medium High (4) Medium High (4) Medium (3) Medium (3)
6HK(1,2)6502006
6HK46502025
19.2 kW – High (5) High (5) – Medium High (4) Medium (3)
6HK(1,2)6502506
6HK46502525
24 kW – – – – – Medium (3)
1. (0,1) - 0 = no service disconnect OR 1 = with service disconnect
2. (1,2) - 1 = with service disconnect, no breaker jumper bar OR 2 = with service disconnect and breaker jumper bar
3. 6HK3 = 3-phase with terminal block connectors only. 6HK4 = 3-phase with service disconnect