otherwise required for specified uses e.g. Above bench or near the
equipment etc.
3.2 FIXING
A. Fix outlet boxes securely
B. Fix exposed outlet boxes to permanent inserts or lead anchors with
machine screws.
3.3 LIGHTING SWITCHES
Locate at the strike side of the door.
3.4 PULL BOXES /JUNCTION BOXES
A. Fix pull boxes at minimum 10 Meter spacing and to limit the number of
bends in conduit to not more than two 90 deg. Bends
B. Locate junction boxes as inconspicuously as possible but accessible after
work is completed.
3.5 SPARES
Contractor / supplier shall provide 2 % of all supporting devices to the client for
future use before certificate of completion of the project.
*** END OF SECTION ***