PART 1 - GENERAL
1.01 VOLTAGE
All single phase devices shall be rated for 240/V 50 Hz and all three phase
devices shall be rated for 415/V 50Hz.
1.02 DESCRIPTION
Provide wiring devices including switches receptacles, switchfuse units, junction
boxes, control devices etc. as specified, indicated on drawings and as required for
proper functioning.
1.03 RELATED WORKS SPECIFIED ELSEWHERE
A. Section 16120 Conduits
B. Section 16110 Raceways
C. Section 16200 Cables & Wire
1.04 REFERENCE STANDARDS
Lighting Switches BS 3676 part 1/1989 &
CENELECPREN60669-1
Fuse Connecting unit BS 1362
20A DP Switch BS 3676 part1
Switch Socket Outlet BS 1363/1984
Flux Outlets BS 5733/1995
Dimmer light Switches IEC 669-2-1,BSEN 50082-1
Cooker Control Unit BS 4177/1992