PART 3 - EXECUTION
3.1 GENERAL
Cables/wires shall be installed as per the concerned local authorities regulations.
Where no concerned local authorities regulations exist IEE regulations shall be
followed.
3.2 EXAMINATION
A. Verify that interior of the building has been protected from weather
B. Ensure that all raceways are thoroughly cleaned.
C. Verify that all construction works likely to damage wires /cables have
been completed.
3.3 INSTALLATION
A. Use suitable wire /cable pulling lubricants.
B. Support cables above accessible ceiling. Do not rest cables on ceiling
panels.
C. Use suitable rollers and pulling devices.
D. Perform field inspection and testing in the presence of the Engineer.
E. Verify all earth continuities.
F. Identify all circuits (Cables) with appropriate marking devices.
*** END OF SECTION ***