2.04 FLEXIBLE CORDS
Flexible cords shall be circular silicon rubber insulated glass fiber braided, three
core 300/500 volts and shall comply with BS 6500. The conductors shall be
tinned, annealed copper and the core shall be coloured Brown, Blue,
Green/Yellow for identification.
2.05 MICC CABLING/WIRING
In all hazardous areas the cabling/wiring shall be done with MICC cables/wires.
The decision of the engineer in respect of choosing such areas will be final and
binding. Generally such areas are gas stores, areas handling medical gases, cold
stores etc. MICC cables shall be to the following standards:
Flame Proof Barrier BS 5345 Part 1
Manufactured & Tested to BS 6207
Quality Assurance BS 5750
Cable Terminations BS 6081
IEC Standards IEC 702.1/IEC 702.2