Specifications
NAIROBI OPERATIONAL HUB
UNOPS Building, UN Lane, Off UN Avenue Tel: +254 20 7621120
P.O Box 783,Village Market, 00621 E-mail: info@unops.org
Nairobi, Kenya Website: www.unops.org
UNOPS is ISO 9001 certified
All cable terminations shall comply with the concerned local authorities
requirements.
1.08 TESTS
- The cables shall be factory tested in accordance with the applicable
standards, codes or recommendations.
- For each cable type, the following test certificates, providing tests have
been carried out shall be submitted to the Engineer for approval.
- Mechanical properties of insulation and sheathing components.
- Resistance to cracking.
- Pressure test at high temperature.
- Resistance to flame propagation.
Final tests shall be made at site and the following routine tests will be carried out
:
- Conductor resistance test.
- Insulation resistance.
1.09 RELATED SECTIONS
A. Section 16120 Conduits
B. Section 16110 Raceways
C. Section 16300 Supporting Devices
1.10 SUBMITTALS
A. Provide product data for each type of cable.
B. Shop floor drawings showing cable routes and method of laying, spacing
and space factor applied.
C. Submit cable assembly from each reel /drum.
D. Provide samples of cable markers, cable ties etc