3.07 Flexible conduits shall be used for connection of motors, HVAC equipment,
recessed light fittings ...etc. Fixed conduits shall be terminated in a conduit box
and flexible conduit shall then connect to the equipment.
3.08 For flexible conduit on earth wire shall be wound around the flexible conduit and
connected at each end to earth terminal.
3.09 The conduit system shall, in general, be surface mounted in all plant rooms,
electrical rooms and in Service Tunnel.
3.10 The following general rules shall be adopted.
B. Conduit saddles shall be used at every 50 cms where the run is straight.
C. Saddles shall be used on both sides of a bend or coupling.