Specifications

NAIROBI OPERATIONAL HUB
UNOPS Building, UN Lane, Off UN Avenue Tel: +254 20 7621120
P.O Box 783,Village Market, 00621 E-mail: info@unops.org
Nairobi, Kenya Website: www.unops.org
UNOPS is ISO 9001 certified
PART 2 PRODUCTS
2.01 NAMEPLATES AND LABELS
A. Nameplates and labels shall be engraved on a three-layer 2 traffolyte
plate having minimum thickness of 2 mm, securely screwed to the housing
and have black letters on white background in Arabic and English.
B. The name plates and labels shall be required for each electrical
distribution board, control panels, equipment enclosures, substation
equipment, disconnect switches and equipment cabinets.
C. Lettering shall be block capitals standing :
6 mm high for identifying individual equipment and loads.
10 mm high for identifying grouped equipment and loads.
D. Labels using embossed adhesive tape with 6mm white letters on black
background or transparent adhesive tape with 6 mm black letters, as selected
by the Engineer, shall be used for identification of individual wall switches,
receptacles, low current outlets, speakers, control device stations,
junction/pull boxes, electrical boxes and fittings, etc.
2.02 WIRE MARKERS
A. Wire markers shall be split sleeve or tubing type.
B. The wire markers shall be required for each conductor at panelboard
gutters, pull boxes, outlets, junction boxes and each load connection.
C. All power and lighting circuits, branch or feeder circuits and control
circuits shall require wire markers.
2.03 COLOUR CODING OF RACEWAYS