Weak battery (alarm)
Low fuel-daytank (alarm)
High ac voltage (shutdown)
Low ac voltage (shutdown)
Under frequency (shutdown)
Over current (warning)
Over current (shutdown)
Short circuit (shutdown)
Ground fault (alarm)(optional--when required by code or
specified)
Over load (alarm)
Emergency stop (shutdown)
In addition, provisions shall be made for indication of two
customer-specified alarm or shutdown conditions. Labeling of
the customer-specified alarm or shutdown conditions shall be of
the same type and quality as the above-specified conditions. The
non-automatic indicating lamp shall be red, and shall flash to
indicate that the generator set is not able to automatically respond
to a command to start from a remote location.
g) Engine Status Monitoring:
The following information shall be available from a digital status
panel on the generator set control:
i) Engine oil pressure (psi or kPA)
ii) Engine coolant temperature (degrees F or C) Both left and
right bank temperature shall be indicated on V-block
engines.
iii) Engine oil temperature (degrees F or C)
iv) Engine speed (rpm)
v) Number of hours of operation (hours)
vi) Number of start attempts
vii) Battery voltage (DC volts)
v) The control system shall also incorporate a data logging
and display provision to allow logging of the last 10
warning or shutdown indications on the generator set, as
well as total time of operation at various loads, as a
percent of the standby rating of the generator set.