automatically be switched off 10 minutes after the switch is
depressed, or after the switch is depressed a second time.
e) Generator Set AC Output Metering:
The generator set shall be provided with a metering set including
the following features and functions:
2.5-inch, 90-degree scale analog voltmeter, ammeter, frequency
meter, and kilowatt (KW) meter. These meters shall be provided
with a phase select switch and an indicating lamp for upper and
lower scale on the meters. Ammeter and KW meter scales shall
be color coded in the following fashion: readings from 0-90% of
generator set standby rating: green; readings from 90-100% of
standby rating: amber; readings in excess of 100%: red.
Digital metering set, 0.5% accuracy, to indicate generator RMS
voltage and current, frequency, output current, output KW,
KW-hours, and power factor. Generator output voltage shall be
available in line-to-line and line-to-neutral voltages, and shall
display all three-phase voltages (line to neutral or line to line)
simultaneously.
f) Generator Set Alarm and Status Message Display:
The generator set shall be provided with alarm and status
indicating lamps to indicate non-automatic generator status, and
existing alarm and shutdown conditions. The lamps shall be
high-intensity LED type. The lamp condition shall be clearly
apparent under bright room lighting conditions.
The generator set control shall indicate the existence of the
following alarm and shutdown conditions on a digital display
panel:
Low oil pressure (alarm)
Low oil pressure (shutdown)
Oil pressure sender failure (alarm)
Low coolant temperature (alarm)
High coolant temperature (alarm)
High coolant temperature (shutdown)
Engine temperature sender failure (alarm)
Low coolant level (alarm or shutdown--selectable)
Fail to crank (shutdown)
Overcrank (shutdown)
Overspeed (shutdown)
Low dc voltage (alarm)
High dc voltage (alarm)