- Under speed / Over speed
- loss of engine speed detection
- low/ high Battery voltage
- under volts/ Over volts
- under freq / over freq
- over current
5. The control shall be UL508 listed, CSA282-M1989 certified, and meet
IEC8528 part 4. All switches, lamps and meters shall be oil-tight and
dust-tight, and the enclosure door shall be gasketed. There shall be no
exposed points in the control (with the door open) that operate in
excess of 50 volts. The controls shall meet or exceed the requirements
of Mil-Std 461C part 9, and IEC Std 801.2, 801.3., and 801.5 for
susceptibility, conducted, and radiated electromagnetic emissions. The
entire control shall be tested and meet the requirements of IEEE587
for voltage surge resistance.
6. The generator set mounted control shall include the following features
and functions:
a) Three position control switch labeled RUN/OFF/AUTO.
In the RUN position the generator set shall automatically start,
and accelerate to rated speed and voltage. In the OFF position the
generator set shall immediately stop, bypassing all time delays. In
the AUTO position the generator set shall be ready to accept a
signal from a remote device to start and accelerate to rated speed
and voltage.
b) Red "mushroom-head" push-button EMERGENCY STOP switch.
Depressing the emergency stop switch shall cause the generator
set to immediately shut down, and be locked out from automatic
restarting.
c) Push-button RESET switch.
The RESET switch shall be used to clear a fault and allow
restarting the generator set after it has shut down for any fault
condition.
d) Push-button PANEL LAMP switch
Depressing the panel lamp switch shall cause the entire panel to
be lighted with DC control power. The panel lamps shall