Specifications
NAIROBI OPERATIONAL HUB
UNOPS Building, UN Lane, Off UN Avenue Tel: +254 20 7621120
P.O Box 783,Village Market, 00621 E-mail: info@unops.org
Nairobi, Kenya Website: www.unops.org
UNOPS is ISO 9001 certified
1.06 SUBMITTALS
A. Shop Drawings
1. Submit 3 copies of shop drawings for approval.
2. Shop drawings shall be complete, as to be as-built drawings, not
general outline drawings used for sales and guide layouts.
3. Submit a complete wiring diagram for the generator set, drawn on a
single standard size sheet, showing the following:
a) All components of:
i) Engine starting control
ii) Engine alarm
iii) Generator control
iv) Battery
v) Battery charger
vi) Earthing
vii) Transfer switch control relays.
b) Interior wiring, terminals and interconnecting wiring.
c) Certified dimensions and weights.
d) Clear indication of all connections to remove equipment
including details of working interface with B.A.S. system
for alarm monitoring.
4. Submit a composite wiring diagram of the entire emergency
transfer system showing all wiring between the engine starting
panel, engine generator set and the automatic transfer switches.
5. Wiring diagrams shall clearly show:
a) Main current conductors, in heavy lines.
b) Control conductors, with colour and/or number coding.
c) Location of relays and apparatus.
d) Description of function, type and catalogue, of all
components.
6. Alternator Control Panel
7. Submit a schematic line diagram showing:
a) Interlocks
b) Protection
b) Instruments