User Guide

English
26 WILO SE 06/2011
The electrical connection must be established via a fixed power cable
which has a plug attachment or an all-pole switch with a contact
opening width of at least
1
/
8
” (3 mm). Use 140/167 °F (60/75 °C) cop-
per conductors only. The power cable is to be fed through the
NPT
3
/
4
“ threaded cable connection (Fig. 25, Item 1).
Cross-section of power cable to be maintained:
min. AWG16 (4 x 1.5 mm
2
)
max. AWG12 (4 x 4.0 mm
2
)
NOTE:
For the right screw tightening torque of the terminals see “Tab. 2
Screw tightening torques” on page 55. Be sure to use a calibrated
torque wrench.
In order to comply with electromagnetic compatibility standards, the
following cables must always be shielded:
DDG (if installed on-site)
•IN2 (setpoint)
DP communication (for cable lengths > 3.3 ft/1 m); (terminal “MP”)
Comply with polarity:
MA = L => SL = L
MA = H => SL = H
•Ext. Off
•AUX
Communication cable IF-Module
The shield must be applied to both sides: on the EMC cable clips in the
module and on the other end. The lines for SBM and SSM do not have
to be shielded.
In order to ensure drip protection and strain relief on the threaded
cable connection, cables with a sufficient outer diameter must be
used and must be screwed sufficiently tightly. Also, the cables near
the threaded cable connection are to be bent to form a drainage loop,
to drain any accumulated drips. Position the threaded cable connec-
tion or lay the cables accordingly to ensure that no drips can run into
the module. Non-assigned threaded cable connections must remain
sealed with the plugs provided by the manufacturer.
The supply cable is to be placed in such a way that under no circum-
stances can it come into contact with the pipe and/or the pump and
motor housing.
When pumps are used in systems with water temperatures above
90°C / 194°F, a suitably heat-resistant connection line must be used.
This pump is equipped with a frequency converter and may not be
protected by a residual-current-operated protection switch. Fre-
quency converters can impair the function of residual-current-oper-
ated protection circuits.
Exception: residual-current-operated protection switches which have
a selective type B universal-current-sensitive design are allowed.
•Labeling: RCD
Trigger current: > 30 mA
Check the current type and voltage of the mains connection.
Observe the name plate information for the pump. The current type
and voltage of the mains connection must correspond to the specifi-
cations on the name plate.
Suitable for use on a circuit capable of delivering not more than 5000
rms symmetrical Amperes, 480 V maximum when protected by CC, J
or RK5 Class Fuses, rated 20 A.
Fig. 25: NPT
3
/
4
” threaded cable connection
1